JinkoSolar Photovoltaic Module Installation Guide
- June 9, 2024
- JinKo
Table of Contents
- General Information
- Installation
- Wiring and Connection
- Maintenance and Care
- Electrical Specification
- Disclaimer of Liability
- Appendix 1: Applicable Products
- Appendix 2: Electrical Specifications
- 99 Shouyang Road, Jingan District,
- References
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
JinkoSolar
Photovoltaic Module
Installation Manual
General Information
1.1 Overview
Thanks for choosing Jinko Solar PV modules. In order to ensure the PV modules
are installed correctly, please read the following installation instructions
carefully before modules are installed and used.
Please remember that these products generate electricity and certain safety
measures need to be taken to avoid danger.
Make sure the module array is designed in such a way not to exceed the maximum
system voltage of any system component such as connectors or inverters.
The assembly is to be mounted over a fire resistant roof covering rated for
the application. Before mounting the module, please consult your local
building department to determine approved roofing materials.
The modules are qualified for application class A: Hazardous voltage (IEC
61730: higher than 50V DC; EN 61730: higher than 120V), hazardous power
applications (higher than 240W) where general contact access is anticipated.
Modules qualified for safety through EN IEC 61730 -1 and – 2 within this
application class are considered to meet the requirements for Safety Class II.
1.2 Warnings
-
PV modules generate DC electrical energy when exposed to sunlight or other light sources. Active parts of module such as terminals can result in burns, sparks, and lethal shock.
-
Artificially concentrated sunlight shall not be directed on the module or panel.
-
Front protective glass is utilized on the module. Broken solar module glass is an electrical safety hazard (may cause electric shock or fire). These modules cannot be repaired and should be replaced immediately.
-
To reduce the risk of electrical shocks or burns, modules may be covered with an opaque material during installation to avoid injury.
-
The installation work of the PV array can only be done under the protection of sun-sheltering covers or sunshades and only qualified person can install or perform maintenance work on this module.
-
Follow the battery manufacture’s recommendations if batteries are used with modules.
-
Do not use this module to replace or partly replace roofs and walls of living buildings.
-
Do not install modules where flammable gas may be present.
-
Do not remove any part installed by Jinko Solar or disassemble the module.
-
All instructions should be read and understood before attempting to install, wire, operate and maintain the module.
-
Don’t lift up PV modules using the attached cables or the junction box.
-
Do not touch live terminals with bare hands. Use insulated tools for electrical connections.
- All PV systems must be grounded to earth. If there is no special regulation, please follow the National Electrical Code or other national code.
- Under normal conditions, a photovoltaic module is likely to experience conditions that produce more current and/or voltage than reported at standard test conditions. Accordingly, the value of Isc and Voc marked on the module should be multiplied by 1.25 when determining PV system component voltage ratings, conductor current ratings, fuse sizes, and size of controls connected to the PV output.
- Once the PV module has been shipped to the installation site, all of the parts should be unpacked properly with care.
- Do not stand or step on the PV module like below pictures show. This is prohibited and there is a risk of damage to the module and cause injury for you.
- Only PV modules with the same cell size should be connected in series.
- During transporting modules, please attempt to minimize shock or vibration to the module, as this may damage the module or lead to cell micro cracks.
- During all transportation situations, never drop the module from a vehicle, house or hands. This will damage module.
- Do not clean the glass with chemicals. Only use tap water. Make sure the module surface temperature is cool to the touch. Cleaning modules with cool water when module surface temp is high may result in glass breakage.
- Do not disconnect any of the modules when under load.
- When looking at PV modules with anti-reflection (AR) coating technology, it will be normal to see some cells with a slight color difference at different angles. Modules with LRF(light reflective film) and without LRF should not be built in the same array or roof.
- Connector of junction box can not be contacted with oily substances, for example, lubricant, rust inhibitor etc.
- The maximum altitude the PV module is designed for ≤ 2000m.
- The maximum irradiance is 1300W/m2 for module with transparent rear.
- Meaning of crossed –out wheeled dustbin:
Do not dispose of electrical appliances as unsorted municipal waste, use separate collection facilities.
Contact your local government for information regarding the collection systems available.
If electrical appliances are disposed of in landfills or dumps, hazardous substances can leak into the groundwater and get into the food chain, damaging your health and well-being.
When replacing old appliances with new ones, the retailer is legally obligated to take back your old appliance for disposals at least free of charge.
Installation
2.1 Installation Safety
- Always wear protective head gear, insulating gloves and safety shoes (with rubber soles).
- Keep the PV module packed in the carton until installation.
- Do not touch the PV module unnecessarily during installation. The glass surface and the frame may be hot. There is a risk of burns and electric shock.
- Do not work in rain, snow or windy conditions.
- Due to the risk of electrical shock, do not perform any work if the terminals of the PV module are wet.
- Use insulated tools and do not use wet tools.
- When installing PV modules, do not drop any objects (e.g., PV modules or tools).
- Make sure flammable gasses are not generated or present near the installation site.
- Insert module connectors fully and correctly. An audible “click” sound should be heard. This sounds confirms the connectors are fully seated. Check all connections.
- The module leads should be securely fastened to the module frame, Wire Management should be done in a way to avoid the connector from scratching or impacting the back sheet of the module.
- Do not touch the junction box and the end of the interconnect cables (connectors) with bare hands during installation or under sunlight, regardless if the PV module is connected to or disconnected from the system.
- Do not expose the PV module to excessive loads on the surface of the PV module or twist the frame.
- Do not hit or put excessive load on the glass or back sheet, this may break the cells or cause micro cracks.
- During the installation or operation, don’t use sharp tools to wipe the back sheet and glass. Scratches can appear on the module.
- Do not drill holes in the frame. It may cause corrosion of the frame.
- When installing modules on roof mounted structures, please try to follow the “from top to bottom” and/or “from left to right” principle, and don’t step on the module. This will damage the module and would be dangerous for personal safety.
2.2 Installation Condition
2.2.1 Climate Condition
Please install the modules in the following conditions:
a) Operating temperature: within –40°C(-40℉) to 85°C (185℉)
b) Humidity: < 85RH%
﹡Note: The mechanical load bearing (include wind and snow loads) of the module
is based on the approved mounting methods. The professional system installer
must be responsible for mechanical load calculation according to the system
design.
2.2.2 Site Selection
In most applications, Jinko solar PV modules should be installed in a location
where they will receive maximum sunlight throughout the year. In the Northern
Hemisphere, the module should typically face south, and in the Southern
Hemisphere, the modules should typically face north. Modules facing 30 degrees
away from true South (or North) will lose approximately10 to 15 percent of
their power output. If the module faces 60 degrees away from true South (or
North), the power loss will be 20 to 30 percent. When choosing a site, avoid
trees, buildings or obstructions, which could cast shadows on the solar
photovoltaic modules especially during the winter months when the arc of the
sun is lowest over the horizon. Shading causes loss of output, even though the
factory fitted bypass diodes of the PV module will minimize any such loss.
Do not install the PV module near open flame or flammable materials.
When solar modules are used to charge batteries, the battery must be installed
in a manner, which will protect the performance of the system and the safety
of its users. Follow the battery manufacturer’s guidelines concerning
installation, operation and maintenance recommendations. In general, the
battery
(or battery bank) should be away from the main flow of people and animal
traffic. Select a battery site that is protected from sunlight, rain, snow,
debris, and is well ventilated. Most batteries generate hydrogen gas when
charging, which can be explosive. Do not light matches or create sparks near
the battery bank.
When a battery is installed outdoors, it should be placed in an insulated and
ventilated battery case specifically designed for the purpose.
Do not install the PV module in a location where it would be immersed in water
or continually exposed to water from a sprinkler or fountain etc.
The PV module can be installed at a distance of 50 m to 500m from the
seashore. However, when installing module within the distance, protect the
connectors or add dust plugs. After removing the dust plugs, connect the
connectors immediately and take other anti-rust measures to prevent rust.
When the modules are installed on the roof, they must be separated from the
roof by more than 10cm to facilitate air circulation and heat dissipation.
2.2.3 Tilt Angle Selection
The tilt angle of the PV module is measured between the surface of the PV
module and a horizontal ground surface (Figure 1). The PV module generates
maximum output power when it faces the sun directly.
For standalone systems with batteries where the PV modules are attached to a
permanent structure, the tilt angle of the PV modules should be selected to
optimize the performance based on seasonal load and sunlight. In general, if
the PV output is adequate when irradiance is low (e.g., winter), then the
angle chosen should be adequate during the rest of the year. For grid-
connected installations where the PV modules are attached to a permanent
structure, PV modules should be tilted so that the energy production from the
PV modules will be maximized on an annual basis.
2.3
Mechanical Installation Introduction
Solar PV modules usually can be mounted by using the following methods: bolts
and clamps.
﹡Note:
- All installation methods herein are only for reference, and Jinko solar will not provide related mounting components, the system installer or trained professional personnel must be responsible for the PV system’s design, installation, and mechanical load calculation and security of the system.
- Before installation, the following items should be addressed:
a) Visually check the module for any damage. Clean the module if any dirt or residue remains from shipping .
b) Check if module serial number stickers match. - Jinko modules are designed to meet a maximum positive (or downward)
pressure of 3600Pa (Only refer to the mentioned module type in this manual)
and negative (or upward) pressure of 1600Pa.
This design load was then tested with a safety factor of 1.5 times. So Jinko modules are tested under a maximum downward pressure of 5400Pa and upward pressure of 2400Pa. When mounting modules in snow-prone or high-wind environments, special care should be taken to mount the modules in a manner that provides sufficient design strength while meeting local code requirements.
2.3.1 Mounting with Bolts
For mounting with bolts, the following modules in tables 1 are applicable.
The frame of each module has 8 mounting holes (Length Width: 14mm9mm) used to secure the modules to support structure. Always use all the eight mounting holes to secure the modules. The module frame must be attached to a mounting rail using M8 corrosion-proof bolts together with spring washers and flat washers in eight symmetrical locations on the PV module. The applied torque value should be big enough to fix the modules steadily. The reference value for M8 bolt is 16~20N*m. As to special support system or special installation requirement, please reconfirm with the support’s supplier for the torque value. Please find detailed mounting information in the below illustration as Figure 2&3&4. 2.3.1.1 Mounting with Bolts(eight mounting holes)
Module type| Max. Design Pressure:3600Pa(positive ) &1600Pa
(negative)mechanical load| Max. Design Pressure: 3600Pa(positive ) &1600Pa
(negative)mechanical load
---|---|---
Module dimensions(mm)AB
54P| Height of the frame(mm)| 35| 30
Group 21| /| 17221134
60P| Height of the frame(mm)| 35| 30
Group 1| 1650992 & 16651002| /
Group 2| 1665992 & 16841002| /
Group 3| 1650992 & 16651002| /
Group 4| 1665992 & 16841002| /
Group 5| 1665992 & 16841002
1672992 & 17041008| /
Group 17| /| 19041134
Group 20| /| 17561039
72P| Height of the frame(mm)| 40| 30
Group 6| 1956992 & 19791002| /
Group 7| 1987992 & 20081002| /
Group 8| 1956992 & 19791002| /
Group 9| 1987992 & 20081002| /
Group 10| 1987992 & 20081002 &20311008| /
Height of the frame(mm)| 35|
Group 18| 22741134|
Group 19| 20901039 & 20901038| /
66P| Height of the frame(mm)| 35| 30
Group 12| 1840998 & 18411002|
Group 14| 18681008 & 18651005|
| Group 16| 1840998 & 18411002|
---|---|---|---
78P| Height of the frame(mm)| 40| 35
Group 11| 2163995 & 2167997 & 2167998& 21661002|
Group 13| 21941008 & 21901005|
Group 15| 2163995 & 2167997 & 2167998& 21661002|
Table 1: Mechanical dimensions for bolt fitting method(eight mounting
holes)
Note:Group 1~20 refer to appendix 1 for details.
The load described in this manual is the design load. When calculating the
maximum test load, 1.5 times of safety factor should be considered.
2.3.1.2 Mounting with Bolts(four mounting holes)
Figure 3:
PV module installed with bolt fitting method(four mounting holes)
Module type| Max. Design Pressure: 3600Pa (positive ) &1600Pa (negative)
mechanical load
---|---
Module dimensions(mm)AB
60P| Height of the frame(mm)| 30
Group 1| 1650992 & 16651002
Group 2| 1665992 & 16841002
Group 3| 1650992 & 16651002
Group 4| 1665992 & 16841002
Group 5| 1665992 & 16841002
1672992 & 17041008
72P| Height of the frame(mm)| 30
Group 6| 1956992 & 19791002
Group 7| 1987992 & 20081002
Group 8| 1956992 & 19791002
Group 9| 1987992 & 20081002
Group 10| 1987992 & 20081002 & 20311008
Height of the frame(mm)| 35
| Group 18| 22741134
---|---|---
66P| Height of the frame(mm)| 30
Group 12| 1840998 & 18411002
Group 14| 18681008 & 18651005
Group 16| 1840998 & 18411002
78P| Height of the frame(mm)| 35
Group 11| 2163995 & 2167997 & 2167998 & 21661002
Group 13| 21941008 & 21901005
Group 15| 2163995 & 2167997 & 2167998 & 2166*1002
Table 2: Mechanical dimensions for bolt fitting method(four mounting
holes)
Note:The installation method of bolt fitting(four mounting holes)is based
on the internal results in Jinko.
The load described in this manual is the design load. When calculating the
maximum test load, 1.5 times of safety factor should be considered.
2.3.1.3 Mounting with Bolts(Nextracker four mounting holes)
Figure 4: PV
module installed with bolt fitting method (NEX)
Module type| Max. Design Pressure: 1067Pa (positive ) &1067Pa (negative)
mechanical load
---|---
Module dimensions(mm)AB
72P| Height of the frame(mm)| 40| 30
Group 6| 1956992 & 19791002
Group 7| 1987992 & 20081002
Group 8| 1956992 & 19791002
Group 9| 1987992 & 20081002
Group 10| 1987992 & 20081002 & 20311008
78P| Height of the frame(mm)| 40| 35
Group 11| 2163995 & 2167997 & 2167998 & 21661002
Group 13| 21941008 & 21901005
Group 15| 2163995 & 2167997 & 2167998 & 21661002
Table 3: Mechanical dimensions for bolt fitting method (NEX)
Note:The installation method of bolt fitting (NEX) is based on the
experimental results in Jinko.
The design of the Nextracker tracking bracket, the selection of accessories
and the installation of modules should be completed by a professional system
installer, which can refer to Jinko’s mechanical load.
The load described in this manual is the design load. When calculating the
maximum test load, 1.5 times of safety factor should be considered.
2.3.2 Mounting with clamps
The module clamps should not come into contact with the front glass and must
not deform the frame. Be sure to avoid shadowing effects from the module
clamps. The module frame is not to be modified under any circumstances. When
choosing this type of clamp-mounting method, please be sure to use at least
four clamps on each module, two clamps should be attached on each long sides
of the module. Depending on the local wind and snow loads, if excessive
pressure load is expected, additional clamps or support would be required to
ensure the module can bear the load.
The applied torque value should be big enough to fix the modules steadily
(Please consult with the clamp or support’s supplier for the specific torque
value). Please find detailed mounting information in the below illustration,
the mounting place distance is suggested bigger than J and less than K. The
installation diagram of clamp is shown in figure 5.
Note : The Movement of the mounting rail and the clamps center line are
recommended to be within the black arrow area. As shown in the figure on the right, the
minimum length L of the clamps is 50mm. Figure 5: PV module installed at the side with Clamp
fitting method
Clamp type | Dimension(mm) | Composition material |
---|---|---|
End Clamp (40 mm thickness) | 39 x 50 x 42 | |
39 x 60 x 42(For 1.5mm thickness frame) | Aluminum-alloy | |
End Clamp (35 mm thickness) | 41.5 x 50 x 40 | |
End Clamp (30 mm thickness) | 41.5 x 50 x 35 | |
Middle Clamp (40 mm & 35 mm thickness) | 42 x 50 x 28 |
42 x 60 x 28(For 1.5mm thickness frame)
Q| R| P
13.5| 15| 2.5
Middle Clamp (30 mm thickness)| 42 x 50 x 29.5
Q| R| P
14| 14| 3
Table 4: Mechanical dimensions, specification and material when modules
installed with mid Clamp When installing modules using clamps on the long side
of the frame, the applicable product types and installation locations are
shown in figure 6 and table 5.
When installing modules using clamps on the short side of the frame, the
applicable product types and installation locations are shown in figure 7 and
table 6.
When installing modules using clamps on the long side & short side of the
frame, the applicable product types and installation locations are shown in
figure 8 and table 7.
When installing modules using clamps on the long side of the frame, the
applicable product types and installation locations (The without C transparent
backsheet series module) are shown in figure 9 and table 8.
2.3.2.1 Clamp Mounting on Long Sides of the Frames
Figure 6:
Installation of clamps on long side of frames
Module type| *** Max. Design Pressure:| 3600Pa (positive ) &1600Pa
(negative) mechanical load| 3600Pa (positive ) &1600Pa (negative) mechanical
load
---|---|---|---
Module dimensions(mm) AB| J| K| J| K
54P
| Height of the frame(mm)| 35| 30
Group 21| 1722*1134| /| /| L/4±50mm( L is the length
of the long side of the module)
60P
| Height of the frame(mm)| 35| 30
Group 1| 1650992 & 16651002| 280| 420| L/4±50mm( L is the length of the long
side of the module)
Group 2| 1665992 & 16841002| 280| 420
Group 3| 1650992 & 16651002| 280| 420
Group 4| 1665992 & 16841002| 280| 420
Group 5| 1665992 & 16841002
1672992 & 17041008| 280| 420
Group 17| 19041134| /| /
Group 20| 17561039| /| /
72P| Height of the frame(mm)| 40| 30
---|---|---|---
Group 6| 1956992 & 19791002| 280| 420| L/4±50mm( L is the length of the long
side of the module)
Group 7| 1987992 & 20081002| 280| 420
Group 8| 1956992 & 19791002| 280| 420
Group 9| 1987992 & 20081002| 280| 420
Group 10| 1987992 & 20081002 & 20311008| 280| 420
Height of the frame(mm)| 35| /
Group 18| 22741134| 400| 580| /
Group 19| 20901039 & 20901038| L/4±50mm|
66P| Height of the frame(mm)| 35| 30
Group 12| 1840998 & 18411002| 280| 420| L/4±50mm( L is the length of the
long side of the module)
Group 14| 18681008 & 18651005| 280| 420
Group 16| 1840998 & 18411002| 280| 420
78P| Height of the frame(mm)| 40| 35
Group 11| 2163995 & 2167997
2167998 & 21661002| 380| 520| L/4±50mm( L is the length of the long side of
the module)
Group 13| 21941008 & 21901005| 380| 520
Group 15| 2163995 & 2167997
2167998 & 21661002| 380| 520
Table 5: Mechanical dimensions of modules installed with clamps on long
side of frame
Note:The load described in this manual is the design load. When calculating
the maximum test load, 1.5 times of safety factor should be considered.
2.3.2.2 Clamp Mounting on Short Sides of the Frames
Module type| Max. Design Pressure:| 1067Pa (positive ) &1067Pa (negative)
mechanical load| 1067Pa (positive ) &1067Pa (negative) mechanical load
---|---|---|---
Module dimensions(mm) AB| J| K| J| K
54P| Height of the frame(mm)| 35| 30
| Group 21| 17221134| /| /| 100| 240
---|---|---|---|---|---|---
60P| Height of the frame(mm)| 35| 30
Group 1| 1650992 & 16651002| 50| 240| 100| 240
Group 2| 1665992 & 16841002| 50| 240| 100| 240
Group 3| 1650992 & 16651002| 50| 240| 100| 240
Group 4| 1665992 & 16841002| 50| 240| 100| 240
Group 5| 1665992 & 16841002
1672992 & 17041008| 50| 240| 100| 240
72P| Height of the frame(mm)| 40| 30
Group 6| 1956992 & 19791002| 50| 240| 100| 240
Group 7| 1987992 & 20081002| 50| 240| 100| 240
Group 8| 1956992 & 19791002| 50| 240| 100| 240
Group 9| 1987992 & 20081002| 50| 240| 100| 240
Group 10| 1987992 & 20081002 & 20311008| 50| 240| 100| 240
66P| Height of the frame(mm)| 35| 30
Group 12| 1840998 & 18411002| 130| 240| 130| 240
Group 14| 18681008 & 18651005| 130| 240| 130| 240
Group 16| 1840998 & 1841*1002| 130| 240| 130| 240
Table 6: Mechanical dimensions of modules installed with clamps on short
side of frame
Note:The installation method of clamps on short sides is based on the
internal results in Jinko.
The load described in this manual is the design load. When calculating the
maximum test load, 1.5 times of safety factor should be considered.
2.3.2.3 Clamp Mounting on Long & Short Sides Figure 8: Installation methods of clamps on
long and short sides
Module type| Max. Design Pressure:| 1600Pa (positive ) &1600Pa (negative)
mechanical load| 1600Pa (positive ) &1600Pa (negative) mechanical load
---|---|---|---
| Module dimensions(mm) AB| J| K| M| N| J| K| M| N
---|---|---|---|---|---|---|---|---|---
54P| Height of the frame(mm)| 35| 30
Group 21| 17221134| /| /| /| /| 100| 240|
L/4±50mm( L is the length of the long side of themodule)
60P
| Height of the frame(mm)| 35| 30
Group 1| 1650992 &16651002| 50| 240| 280| 420| 100| 240| L/4±50mm( L is the
length of the long side of the module)
Group 2| 1665992 &16841002| 50| 240| 280| 420| 100| 240
Group 3| 1650992 &16651002| 50| 240| 280| 420| 100| 240
Group 4| 1665992 &16841002| 50| 240| 280| 420| 100| 240
Group 5| 1665992 &16841002
1672992 &17041008| ****
50
| ****
240
| ****
280
| ****
420
| ****
100
| ****
240
Group 17| 19031134| /| /| /| /| 100| 240
Group 20| 17561039| /| /| /| /| 100| 240
72P| Height of the frame(mm)| 40| 30
Group 6| 1956992 &19791002| 50| 240| 280| 480| 100| 240| L/4±50mm( L is the
length of the long side of the module)
Group 7| 1987992 &20081002| 50| 240| 280| 480| 100| 240
Group 8| 1956992 &19791002| 50| 240| 280| 480| 100| 240
Group 9| 1987992 & 20081002| 50| 240| 280| 480| 100| 240
Group 10| 1987992 &2008
1002 &2031*1008| ****
50
| ****
240
| ****
280
| ****
480
| ****
100
| ****
240
66P| Height of the frame(mm)| 35| 30
Group 12| 1840998 &18411002| 130| 240| 280| 420| 130| 240| L/4±50mm( L is
the length of the long side of the module)
Group 14| 18681008 &18651005| 130| 240| 280| 420| 130| 240
Group 16| 1840998 &18411002| 130| 240| 280| 420| 130| 240
78P| Height of the frame(mm)| 40| 35
Group 11
| 2163995 & 2167997
2167998 &21661002| 130| 240| 380| 520| 130| 240| L/4±50mm( L is the length
of the long side of the module)
Group 13| 21941008 & 21901005| 130| 240| 380| 520| 130| 240
Group 15| 2163995 &2167997
2167998 & 21661002| 130| 240| 380| 520| 130| 240
Table 7: Mechanical dimensions of modules installed with clamps on
short side of frame
Note:The installation method of clamps on long and short sides is based
on the internal results in Jinko.
The load described in this manual is the design load. When calculating the
maximum test load, 1.5 times of safety factor should be considered.
2.3.2.4 Clamp Mounting on Long Sides of the Frames (The without C
transparent backsheet series module) Figure 9: Installation methods of clamps on long sides
Module type| Max. Design Pressure:| 3600Pa (positive ) &1600Pa (negative)
mechanical load
---|---|---
Module dimensions(mm)A*B| J| K
78P
| Height of the frame(mm)| 40
Group 13| 21941008 & 21901005| 300| 480
Table 8: Mechanical dimensions when modules installed at long side with
Clamp fitting method
Note:The load described in this manual is the design load. When
calculating the maximum test load, 1.5 times of safety factor should be
considered.
Wiring and Connection
a) Before this procedure, please read the operation instructions of the PV
system carefully. Make wiring by Multi-connecting cables between the PV
modules in series or parallel connection, which is determined by user’s
configuration requirement for system power, current and voltage.
b) PV modules connected in series should have similar current, and modules
must not be connected together to create a voltage higher than the permitted
system voltage. The maximum number of modules in series depends on system
design, the type of inverter used and environmental conditions.
c) The maximum fuse rating value in an array string can be found on the
product label or in the product datasheet. The fuse rating value is also
corresponding to the maximum reverse current that a module can withstand, i.e.
when one string is in shade then the other parallel strings of modules will be
loaded by the shaded string and the current will pass through to create a
current circuit. Based on the maximum series fuse rating of module and local
electrical codes and standards, make sure the modules strings in parallel are
protected with the appropriate in-line string fusing.
d) Open the combiner box of the control system and connect the conductor from
the PV arrays to the combiner box in accordance with the design and local
codes and standards. The cross-sectional area and cable connector capacity
must satisfy the maximum short-circuit of the PV system (for a single
component, we recommended that the cross-sectional area of cables be 4mm2 and
the rated current of connectors be more than 10A), otherwise cables and
connectors will become overheating for large
current. Please pay attention to the temperature limit of cables is 85℃.
e) All module frames and mounting racks must be properly grounded in
accordance with local and national electrical codes. Attach the equipment
grounding conductor to the module frame using the hole and hardware provided.
Note that a stainless steel star washer is used between the ground wire and
module frame (see Figure 10 below).This washer is used to avoid corrosion due
to dissimilar metals. Tighten the screw securely. f) Follow the requirements of applicable local
and national electrical codes.
g) These modules contain factory installed by pass diode .If these modules are
incorrectly connected to each other, the bypass diodes, cable or junction box
may be damaged.
h) The cable of the junction box is defined as L, as showed below in Figure
11. For Jinko standard full module L is 900/1200mm, the half–cut module L is
145/290mm, and the SWAN bifacial module L is 150/250mm. For customized module,
L can be based on your condition. Please take the cable length into
consideration before designing the wiring layout. i) It is recommend to use negatively grounded
inverters to avoid the PID effect for non-PID free modules.
j) If modules are connected in series, the total voltage is equal to the sum
of individual voltages. The recommended as below,
System voltage≥NVoc[1+TCVoc (Tmin-25)] Where
N module numbers in series
Voc Open circuit voltage (refer to product label or data sheet)
TCVoc Temperature coefficient of open circuit voltage (refer to product label
or data sheet)
Tmin Minimum ambient temperature
Maintenance and Care
It is required to perform regular inspection and maintenance of the modules,
especially during the warranty period. To ensure optimum module performance,
Jinko recommends the following maintenance measures:
4.1 Visual Inspection
Inspect the modules visually to find if there are any visual defects, If
there are, the following items should be evaluated:
a) If modules are observed having slight cell color differences at different
angles, this is a normal phenomenon of modules with anti-reflection coating
technology.
b) Whether the glass is broken.
c) No sharp objects are in contact with the PV module surfaces.
d) PV modules are not shaded by unwanted obstacles and; or foreign material.
e) Corrosion along the cells’ bus-bar. The corrosion is caused by moisture
intrusion thought the module back sheet. Check the back sheet for damage.
f) Check whether the back sheet is burn out.
g) Check if screws and mounting brackets are tight, adjust and tighten as
necessary.
4.2 Cleaning
a) A build up of dust or dirt on the module(s) front face will result in a
decreased energy output. Clean the panel(s) preferably once per annum if
possible (depend on site conditions) using a soft cloth dry or damp, as
necessary. Water with high mineral content may leave deposits on the glass
surface and is not recommended.
b) Never use abrasive material under any circumstances.
c) In order to reduce the potential for electrical and thermal shock, Jinko
recommends cleaning PV modules during early morning or late afternoon hours
when solar radiation is low and the modules are cooler, especially in regions
with hotter temperatures.
d) Never attempt to clean a PV module with broken glass or other signs of
exposed wiring, as this presents a shock hazard.
e) Never use chemicals when cleaning modules as this may affect the module
warranty and energy output.
4.3 Inspection of Connector and Cable
It’s recommended to implement the following preventive maintenance every 6
months:
a) Check the sealing gels of the junction box for any damage.
b) Examine the PV module(s) for signs of deterioration. Check all wiring for
possible rodent damage, weathering and that all connections are tight and
corrosion free. Check electrical leakage to ground.
Electrical Specification
The module electrical rating are measured under Standard Test Conditions, which are 1000W/m2,irradiance with AM 1.5 spectrum and 25 deg (77°F) ambient temperature. The module might produce more or less voltage or current than rated value in uncertainty condition.
Disclaimer of Liability
Because the use of the manual and the conditions or methods of installation,
operation, use and maintenance of photovoltaic (PV) product are beyond Jinko’s
control, Jinko does not accept responsibility and expressly disclaims
liability for loss ,damage, or expense arising out of or in any way connected
with such installation, operation, use or maintenance.
No responsibility is assumed by Jinko for any infringement of patents or other
rights of third parties, which may result from use of the PV product. NO
license is granted by implication or otherwise under any patent or patent
rights.
The information in this manual is based on Jinko’s knowledge and experience
and is believed to be reliable, but such information including product
specification (without limitations) and suggestions do not constitute a
warranty, expresses or implied. Jinko reserve the right to change the manual,
the PV produce, the specifications, or product information sheets without
prior notice.
Appendix 1: Applicable Products
This document is applicable to the series of solar modules as listed below:
With 6” poly and mono c-Si:
Group 1
MMxxx-60LA-MB | MMxxx-60LA-AB | SMMxxx-60LA-MB-TI | SMMxxx-60LA-AB-TI |
---|---|---|---|
MMxxx-60LA-MBV | MMxxx-60LA-ABV | SMMxxx-60LA-MBV-TI | SMMxxx-60LA-ABV-TI |
(xxx =270~340,in increment of 5)
Group 2
MMxxx-60HLA-MB | MMxxx-60HLA-AB | SMMxxx-60HLA-MB-TI | SMMxxx-60HLA-AB-TI |
---|---|---|---|
MMxxx-60HLA-MBV | MMxxx-60HLA-ABV | SMMxxx-60HLA-MBV-TI | SMMxxx-60HLA-ABV-TI |
(xxx =270~350,in increment of 5)
Group 3
SMMxxx-60LA-MBV-MX3| SMMxxx-60LA-ABV-MX3| SMMxxx-60LA-MB-MX3| SMMxxx-60LA-AB-
MX3
---|---|---|---
(xxx =270~340,in increment of 5)
Group 4
SMMxxx-60HLA-MBV-MX3| SMMxxx-60HLA-ABV-MX3| SMMxxx-60HLA-MB-MX3| SMMxxx-60HLA-
AB-MX3
---|---|---|---
(xxx =270~340,in increment of 5)
Group 5
MMxxx-60HLA-BBV| MMxxx-60HLA-BB| |
---|---|---|---
(xxx =315~355,in increment of 5)
Group 6
MMxxx-72LA-MB | MMxxx-72LA-AB | SMMxxx-72LA-MB | SMMxxx-72LA-MB-TI |
---|---|---|---|
MMxxx-72LA-MBV | MMxxx-72LA-ABV | SMMxxx-72LA-MBV | SMMxxx-72LA-MBV-TI |
SMMxxx-72LA-AB-TI | |||
SMMxxx-72LA-ABV-TI |
(xxx =335~410,in increment of 5)
Group 7
MMxxx-72HLA-MB | MMxxx-72HLA-AB | SMMxxx-72HLA-MB-TI | SMMxxx-72HLA-AB-TI |
---|---|---|---|
MMxxx-72HLA-MBV | MMxxx-72HLA-ABV | SMMxxx-72HLA-MBV-TI | SMMxxx-72HLA-ABV-TI |
(xxx =335~425,in increment of 5)
Group 8
SMMxxx-72LA-MB-MX3| SMMxxx-72LA-MBV-MX3| SMMxxx-72LA-AB-MX3| SMMxxx-72LA-ABV-
MX3
---|---|---|---
(xxx =335~395,in increment of 5)
Group 9
SMMxxx-72HLA-MB-MX3| SMMxxx-72HLA-MBV-MX3| SMMxxx-72HLA-AB-MX3| SMMxxx-72HLA-
ABV-MX3
---|---|---|---
(xxx =335~395,in increment of 5)
Group 10
MMxxx-72HLA-BBV| MMxxx-72HLA-BB| |
---|---|---|---
(xxx =375~425,in increment of 5)
Group 11
MMxxx-78HLA-MB | MMxxx-78HLA-MBV | SMMxxx-78HLA-MB-TI | SMMxxx-78HLA-MBV-TI |
---|
(xxx =405-445,in increment of 5)
Group 12
MMxxx-66HLA-MB | MMxxx-66HLA-MBV | SMMxxx-66HLA-MB-TI | SMMxxx-66HLA-MBV-TI |
---|
(xxx =340-375,in increment of 5)
Group 13
MMxxx-78HLA-BBV| | |
---|---|---|---
(xxx =405-455,in increment of 5)
Group 14
MMxxx-66HLA-BBV| | |
---|---|---|---
(xxx =340-385,in increment of 5)
Group 15
MMxxx-78HLA-AB | MMxxx-78HLA-ABV | SMMxxx-78HLA-AB-TI | SMMxxx-78HLA-ABV-TI |
---|
(xxx =405-435,in increment of 5)
Group 16
MMxxx-66HLA-AB | MMxxx-66HLA-ABV | SMMxxx-66HLA-AB-TI | SMMxxx-66HLA-ABV-TI |
---|
(xxx =340-365,in increment of 5)
Group 17
MMxxx-60HLD-MBV| | |
---|---|---|---
(xxx = 400-450,in increment of 5)
Group 18
MMxxx-72HLD-MBV| | |
---|---|---|---
(xxx = 475-540,in increment of 5)
Group 19
MMxxx-72HLM- MBV| | |
---|---|---|---
(xxx = 420-455,in increment of 5)
Group 20
MMxxx-60HLM- MBV| | |
---|---|---|---
(xxx = 350-375,in increment of 5)
Group 21
MMxxx-54HLD-MBV| | |
---|---|---|---
(xxx = 360-415,in increment of 5).
Notes:
- SM: The smart module
- V: Module with 1500V
- H: Half-cut series module
- LA: 158 large cell series module
- MB/MBV: Normal monofacial series module
- BB/BBV: Transparent backsheet series module
- MX3: Module with Z8S Junction Box
- AB/ABV: Black backsheet series module
- TI: module with RSD Junction Box
- LD: 182 large cell series module
- LM: 166 large cell series module
Appendix 2: Electrical Specifications
Module Type| Maximum PoweratSTC (Pmax, Wp)| MaximumPower
Voltage(V mp,V)| MaximumPower Current(Im p, A)| Open-circuit
Voltage(Voc,V)| Short-ircuit
Current(Isc,A)| Rated Max. outputvoltage (Optimized) [V]:| Rated
Max.
outputcurrent (Optimized )[A]:
---|---|---|---|---|---|---|---
Group1| 270| 31.4| 8.60| 38.4| 9.29| |
275| 31.6| 8.71| 38.5| 9.40| |
280| 31.8| 8.81| 38.6| 9.51| |
285| 32.0| 8.91| 38.7| 9.63| |
290| 32.2| 9.02| 39.5| 9.76| |
295| 32.4| 9.11| 39.7| 9.88| |
300| 32.6| 9.21| 40.1| 9.98| |
305| 32.8| 9.30| 40.3| 10.07| |
310| 33.0| 9.40| 40.5| 10.15| |
315| 33.2| 9.49| 40.7| 10.23| |
320| 33.4| 9.59| 40.9| 10.31| |
325| 33.6| 9.68| 41.1| 10.50| |
330| 33.8| 9.77| 41.3| 10.61| |
335| 34.0| 9.86| 41.5| 10.73| |
340| 34.2| 9.95| 41.7| 10.82| |
345| 34.4| 10.03| 41.9| 10.91| |
350| 34.6| 10.12| 42.1| 11.00| |
Group 2| 270| 30.34| 8.24| 36.90| 8.70| |
275| 30.54| 8.35| 37.10| 8.96| |
280| 30.70| 8.47| 37.20| 9.10| |
285| 30.89| 8.58| 37.50| 9.19| |
290| 31.07| 8.69| 37.70| 9.29| |
295| 31.25| 8.80| 37.80| 9.40| |
300| 31.46| 8.90| 37.90| 9.51| |
305| 31.70| 8.99| 38.00| 9.63| |
310| 31.90| 9.09| 38.80| 9.76| |
315| 32.10| 9.19| 39.00| 9.88| |
320| 32.30| 9.29| 39.40| 9.98| |
325| 32.52| 9.38| 39.60| 10.07| |
330| 32.74| 9.47| 39.80| 10.15| |
335| 32.95| 9.56| 40.00| 10.23| |
340| 33.16| 9.65| 40.20| 10.31| |
345| 33.37| 9.74| 40.40| 10.50| |
350| 33.54| 9.84| 40.60| 10.61| |
Group 3
Group 4| 270| 31.4| 8.60| 38.4| 9.29| 33.6| 12.0
---|---|---|---|---|---|---|---
275| 31.6| 8.71| 38.5| 9.40| 33.6| 12.0
280| 31.8| 8.81| 38.6| 9.51| 33.6| 12.0
285| 32.0| 8.91| 38.7| 9.63| 33.6| 12.0
290| 32.2| 9.02| 39.5| 9.76| 33.6| 12.0
295| 32.4| 9.11| 39.7| 9.88| 33.6| 12.0
300| 32.6| 9.21| 40.1| 9.98| 33.6| 12.0
305| 32.8| 9.30| 40.3| 10.07| 33.6| 12.0
310| 33.0| 9.40| 40.5| 10.15| 33.6| 12.0
315| 33.2| 9.49| 40.7| 10.23| 33.6| 12.0
320| 33.4| 9.59| 40.9| 10.31| 33.6| 12.0
325| 33.6| 9.68| 41.1| 10.50| 33.6| 12.0
330| 33.8| 9.77| 41.3| 10.61| 33.6| 12.0
335| 34.0| 9.86| 41.5| 10.73| 33.6| 12.0
340| 34.2| 9.95| 41.7| 10.82| 33.6| 12.0
Group 5 ( P)| 315| 32.70| 9.63| 39.90| 9.99| |
320| 32.90| 9.73| 40.10| 10.07| |
325| 33.10| 9.82| 40.30| 10.15| |
330| 33.24| 9.93| 40.39| 10.25| |
335| 33.40| 10.03| 40.46| 10.34| |
340| 33.62| 10.11| 40.60| 10.43| |
345| 33.76| 10.22| 40.75| 10.53| |
350| 33.94| 10.31| 40.87| 10.62| |
355| 34.11| 10.41| 41.00| 10.71| |
Group 6| 335| 38.4| 8.72| 46.9| 9.79| |
340| 38.7| 8.79| 47.1| 9.81| |
345| 38.9| 8.87| 47.3| 9.85| |
350| 39.1| 8.94| 47.5| 9.88| |
355| 39.3| 9.04| 47.8| 9.93| |
360| 39.5| 9.12| 48.0| 10.02| |
365| 39.7| 9.20| 48.2| 10.09| |
370| 39.9| 9.28| 48.5| 10.15| |
375| 40.2| 9.33| 48.7| 10.23| |
380| 40.5| 9.39| 48.9| 10.30| |
385| 40.8| 9.44| 49.1| 10.38| |
390| 41.1| 9.49| 49.3| 10.46| |
395| 41.4| 9.55| 49.5| 10.54| |
400| 41.7| 9.60| 49.8| 10.61| |
405| 42.0| 9.65| 50.1| 10.69| |
410| 42.3| 9.70| 50.3| 10.76| |
415| 42.6| 9.75| 50.6| 10.82| |
| 420| 42.9| 9.80| 50.9| 10.88| |
---|---|---|---|---|---|---|---
425| 43.2| 9.85| 51.2| 10.94| |
Group 7| 335| 34.36| 8.44| 44.50| 8.87| |
340| 34.63| 8.52| 44.60| 8.93| |
345| 34.89| 8.60| 44.80| 9.01| |
350| 35.14| 8.68| 45.00| 9.08| |
355| 35.43| 8.75| 45.20| 9.15| |
360| 35.68| 8.83| 45.40| 9.21| |
365| 35.96| 8.90| 45.60| 9.28| |
370| 36.20| 8.98| 45.80| 9.37| |
375| 36.47| 9.05| 46.00| 9.46| |
380| 36.74| 9.12| 46.20| 9.79| |
385| 37.00| 9.19| 46.40| 9.81| |
390| 37.25| 9.26| 46.60| 9.85| |
395| 37.53| 9.33| 46.80| 9.88| |
400| 37.81| 9.39| 47.10| 9.93| |
405| 38.06| 9.46| 47.30| 10.02| |
410| 38.34| 9.52| 47.50| 10.09| |
415| 38.58| 9.59| 47.80| 10.15| |
420| 38.86| 9.65| 48.00| 10.23| |
425| 39.10| 9.72| 48.20| 10.30| |
Group 8
Group 9| 335| 38.4| 8.72| 46.9| 9.79| 37.2| 12.0
340| 38.7| 8.79| 47.1| 9.81| 37.2| 12.0
345| 38.9| 8.87| 47.3| 9.85| 37.2| 12.0
350| 39.1| 8.94| 47.5| 9.88| 37.2| 12.0
355| 39.3| 9.04| 47.8| 9.93| 37.2| 12.0
360| 39.5| 9.12| 48.0| 10.02| 37.2| 12.0
365| 39.7| 9.20| 48.2| 10.09| 37.2| 12.0
370| 39.9| 9.28| 48.5| 10.15| 37.2| 12.0
375| 40.2| 9.33| 48.7| 10.23| 37.2| 12.0
380| 40.5| 9.39| 48.9| 10.30| 37.2| 12.0
385| 40.8| 9.44| 49.1| 10.38| 37.2| 12.0
390| 41.1| 9.49| 49.3| 10.46| 37.2| 12.0
395| 41.4| 9.55| 49.5| 10.54| 37.2| 12.0
400| 41.7| 9.60| 49.8| 10.61| 37.2| 12.0
405| 42.0| 9.65| 50.1| 10.69| 37.2| 12.0
410| 42.3| 9.70| 50.3| 10.76| 37.2| 12.0
Group 10 ( P )
| 375| 39.25| 9.56| 47.92| 9.92| |
380| 39.36| 9.66| 47.96| 10.02| |
385| 39.50| 9.76| 48.10| 10.08| |
390| 39.62| 9.84| 48.14| 10.17| |
| 395| 39.83| 9.92| 48.26| 10.23| |
---|---|---|---|---|---|---|---
400| 40.01| 10.00| 48.35| 10.32| |
405| 40.19| 10.08| 48.45| 10.42| |
410| 40.38| 10.16| 48.56| 10.51| |
415| 40.50| 10.25| 48.64| 10.61| |
420| 40.65| 10.33| 48.74| 10.70| |
425| 40.80| 10.42| 48.84| 10.80| |
Group 11| 405| 42.91| 9.44| 51.07| 10.20| |
410| 43.03| 9.53| 51.16| 10.27| |
415| 43.10| 9.63| 51.25| 10.34| |
420| 43.17| 9.73| 51.34| 10.41| |
425| 43.23| 9.83| 51.43| 10.48| |
430| 43.49| 9.89| 51.52| 10.57| |
435| 43.55| 9.99| 51.61| 10.67| |
440| 43.65| 10.08| 51.70| 10.77| |
445| 43.72| 10.18| 52.04| 10.84| |
450| 43.82| 10.27| 52.13| 10.92| |
455| 43.92| 10.36| 52.22| 11.00| |
460| 44.02| 10.45| 52.32| 11.08| |
465| 44.12| 10.54| 52.43| 11.16| |
Group 12| 340| 36.56| 9.30| 43.24| 10.20| |
345| 36.67| 9.41| 43.32| 10.27| |
350| 36.77| 9.52| 43.41| 10.34| |
355| 36.87| 9.63| 43.49| 10.41| |
360| 36.97| 9.74| 43.58| 10.48| |
365| 37.06| 9.85| 43.66| 10.55| |
370| 37.15| 9.96| 43.75| 10.62| |
375| 37.24| 10.07| 44.02| 10.69| |
380| 37.33| 10.18| 44.09| 10.77| |
385| 37.42| 10.29| 44.17| 10.83| |
390| 37.54| 10.39| 44.29| 10.93| |
Group 13| 405| 42.90| 9.44| 51.55| 10.15| |
410| 43.03| 9.53| 51.58| 10.20| |
415| 43.20| 9.61| 51.61| 10.28| |
420| 43.35| 9.69| 51.64| 10.36| |
425| 43.50| 9.77| 51.67| 10.44| |
430| 43.66| 9.85| 51.70| 10.52| |
435| 43.85| 9.92| 51.80| 10.60| |
440| 43.92| 10.02| 51.90| 10.68| |
445| 43.98| 10.12| 52.00| 10.78| |
450| 44.04| 10.22| 52.10| 10.87| |
| 455| 44.14| 10.31| 52.20| 10.96| |
---|---|---|---|---|---|---|---
Group 14| 340| 36.72| 9.26| 43.56| 10.12| |
345| 36.82| 9.37| 43.64| 10.20| |
350| 36.92| 9.48| 43.67| 10.28| |
355| 37.02| 9.59| 43.71| 10.36| |
360| 37.12| 9.70| 43.75| 10.44| |
365| 37.21| 9.81| 43.83| 10.52| |
370| 37.30| 9.92| 43.92| 10.60| |
375| 37.39| 10.03| 44.00| 10.68| |
380| 37.48| 10.14| 44.11| 10.76| |
385| 37.57| 10.25| 44.17| 10.84| |
Group 15| 405| 43.23| 9.37| 51.55| 10.01| |
410| 43.30| 9.47| 51.58| 10.11| |
415| 43.37| 9.57| 51.61| 10.21| |
420| 43.44| 9.67| 51.64| 10.31| |
425| 43.51| 9.77| 51.67| 10.41| |
430| 43.57| 9.87| 51.70| 10.51| |
435| 43.64| 9.97| 51.73| 10.61| |
Group 16| 340| 36.56| 9.30| 43.60| 10.01| |
345| 36.63| 9.42| 43.63| 10.13| |
350| 36.69| 9.54| 43.65| 10.25| |
355| 36.76| 9.66| 43.68| 10.37| |
360| 36.81| 9.78| 43.70| 10.49| |
365| 36.87| 9.90| 43.73| 10.61| |
Group 17| 400| 32.87| 12.17| 40.38| 13.25| |
405| 32.98| 12.28| 40.46| 13.31| |
410| 33.09| 12.39| 40.54| 13.37| |
415| 33.20| 12.50| 40.62| 13.43| |
420| 33.31| 12.61| 40.70| 13.49| |
425| 33.42| 12.72| 40.78| 13.55| |
430| 33.52| 12.83| 40.86| 13.61| |
435| 33.62| 12.94| 40.94| 13.67| |
440| 33.72| 13.05| 41.02| 13.73| |
445| 33.82| 13.16| 41.10| 13.79| |
450| 33.91| 13.27| 41.18| 13.85| |
Group 18| 475| 39.69| 11.97| 48.38| 12.94| |
480| 39.77| 12.07| 48.46| 13.01| |
485| 39.86| 12.17| 48.54| 13.08| |
490| 39.94| 12.27| 48.62| 13.15| |
495| 40.02| 12.37| 48.70| 13.22| |
500| 40.10| 12.47| 48.78| 13.29| |
| 505| 40.18| 12.57| 48.86| 13.36| |
---|---|---|---|---|---|---|---
510| 40.26| 12.67| 48.94| 13.43| |
515| 40.33| 12.77| 49.02| 13.50| |
520| 40.41| 12.87| 49.10| 13.57| |
525| 40.48| 12.97| 49.18| 13.64| |
530| 40.56| 13.07| 49.26| 13.71| |
535| 40.63| 13.17| 49.34| 13.79| |
540| 40.70| 13.27| 49.42| 13.85| |
Group 19| 420| 40.17| 10.46| 48.07| 11.11| |
425| 40.37| 10.53| 48.27| 11.18| |
430| 40.57| 10.60| 48.47| 11.25| |
435| 40.77| 10.67| 48.67| 11.32| |
440| 40.97| 10.74| 48.87| 11.39| |
445| 41.17| 10.81| 49.07| 11.46| |
450| 41.37| 10.88| 49.27| 11.53| |
455| 41.56| 10.95| 49.46| 11.60| |
Group 20| 350| 33.62| 10.41| 40.20| 11.14| |
355| 33.81| 10.50| 40.39| 11.23| |
360| 34.00| 10.59| 40.58| 11.32| |
365| 34.18| 10.68| 40.76| 11.41| |
370| 34.36| 10.77| 40.94| 11.50| |
375| 34.53| 10.86| 41.12| 11.59| |
Group 21| 360| 29.54| 12.19| 36.34| 13.22| |
365| 29.65| 12.31| 36.42| 13.29| |
370| 29.77| 12.43| 36.50| 13.36| |
375| 29.88| 12.55| 36.58| 13.43| |
380| 30.00| 12.67| 36.66| 13.50| |
385| 30.11| 12.79| 36.74| 13.57| |
390| 30.21| 12.91| 36.82| 13.64| |
395| 30.32| 13.03| 36.90| 13.71| |
400| 30.42| 13.15| 36.98| 13.78| |
405| 30.52| 13.27| 37.06| 13.85| |
410| 30.62| 13.39| 37.14| 13.92| |
415| 30.79| 13.48| 37.31| 14.01| |
Global Sales & Marketing Center
Jinko Building
99 Shouyang Road, Jingan District,
Shanghai, China 200027
Tel: +86 21 5183 8777
Fax: +86 21 5180 8600
Jiangxi Manufacture Base
No.1 Jinko Road,
Shangrao Economic Development Zone,
Jiangxi Province, China 334100
Tel:+86 793 858 8188
Fax:+86 793 846 1152
Zhejiang Manufacture Base
No.58 Yuanxi Road,
Haining Yuanhua Industrial Park,
Zhejiang Province, China 314416
Tel: +86 573 8798 5678
Fax: +86 573 8787 1070
www.jinkosolar.com
Technic Support: technic@jinkosolar.com
After-sales: cs@jinkosolar.com
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>