BRASCH GSE2-CM-24 Factory Calibration Kit Instruction Manual

June 9, 2024
BRASCH

BRASCH GSE2-CM-24 Factory Calibration Kit

Overview

Brasch Generation 2 sensor boards are calibrated at the factory and have an expected calibration duration of approximately two years. Environmental conditions may shorten or prolong this period of time, but once the sensor parameters drift outside of acceptable tolerances, the sensor board must be either be recalibrated or replaced.
This document outlines the procedure for installing a factory calibration kit of all Brasch Generation 2 sensor boards including:

Carbon Monoxide Models

  • GSE2-CM-24
  • GSE2-CM-120
  • GSE2-CM-Remote
  • TRNS2-CM-Analog
  • TRNS2-CM-Digital
  • GDCP-CM-Remote

Nitrogen Dioxide Models

  • GSE2-ND-24
  • GSE2-ND-120
  • GSE2-ND-Remote
  • TRNS2-ND-Analog
  • TRNS2-ND-Digital
  • GDCP-ND-Remote

Combination Models

  • GSE2-NCM-24
  • GSE2-NCM-120
  • GSE2-NCM-Remote
  • TRNS2-NCM-Analog
  • TRNS2-NCM-Digital
  • GDCP-NCM-Remote

Required

  • Phillips Screwdriver
  • Factory Calibration Kit
  • Pliers (Long or Needle Nose)

Procedure

  1. Loosen the two lid screws and open the enclosure

  2. Turn power OFF to the sensor board
    Verify the Green Power LED is dark before proceeding

  3. Remove all wire connections to the sensor board
    Note the locations of these wires so they can be returned on the new board

  4. Remove the retaining screws
    For local sensors, there are three retaining screws (6-32 x 1/4”)
    For remote sensors, there are four retaining screws (10-24 x 1/4”)

  5. For local sensors only, pinch the locking standoff with a pair of pliers and gently lift on the closest corner of the sensor board

  6. Extract the sensor board from the enclosure and set it aside

  7. Make sure that all jumpers and switches on the new sensor board match those on the old sensor board

  8. Place the new sensor board into the enclosure

  9. Return the screws and tighten until the board is secure

  10. Connect the wires to the sensor board in their original positions
    Use the diagram on the following page for assistance

  11. Turn power ON to the sensor board
    Verify the Green Power LED is illuminated before proceeding

  12. Close the lid and firmly tighten the two screws

  13. Check for proper operation

Troubleshooting

  • If any of the following errors are present, press firmly on the sensor itself to ensure it is fully seated in the socket on the PCB.
    • Standalone Detectors: 9996
    • BMS Transmitters: 0x0004
    • Control Panel Remotes: Sensor # Missing
  • If any of the following errors are present, check the wiring connections to the sensor board.
    • Standalone Detectors: 960x
    • BMS Transmitters: No Communication
    • Control Panel Remotes: Sensor # Communication Loss

BRASCH GSE2-CM-24 Factory Calibration Kit-FIG2
BRASCH GSE2-CM-24 Factory Calibration Kit-FIG3

General Contact Information

Phone: 314-291-0440
Fax: 314-291-0646
Email: customerservice@braschenvtech.com
Website: www.braschenvtech.com

Technical Support Contact Information

Phone: 314-291-0440 ext. 1006
Fax: 314-291-0646
Email: customerservice@braschenvtech.com
Website: www.braschenvtech.com/support-for-existing- systems

Revision: 1.0
Issue Date: March 10, 2022
Document Number: FG02
© Brasch Environmental Technologies, LLC
All Rights Reserved

FG02
Rev 1.0 – March 10, 2022

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Related Manuals