NOTIFIER NFW-100X Intelligent Addressable FACP with Communicator Instruction Manual
- June 9, 2024
- NOTIFIER
Table of Contents
NOTIFIER NFW-100X Intelligent Addressable FACP with Communicator
Instruction Manual
General
The FireWarden-100X (NFW-100X) is the latest intelligent addressable Fire Alarm Control Panel (FACP) within the FireWarden Series and is a direct replacement for the FireWarden-100 (NFW-100). The NFW-100X comes with a pre- installed communicator and supports up to 198 addressable devices (99 detectors and 99 modules). With an extensive list of powerful features, the NFW-100X programs just like FireWarden-100 products, yet fits into applications previously served only by conventional panels. The pre-installed IPOTS-COM is a dual technology (POTS and IP) communicator. The POTS transmits system status (alarms, troubles, AC loss, etc.) to a Central Station via the public switched telephone network. The IP communicator’s internet monitoring capability sends alarm signals over the Internet saving the monthly cost of two dedicated business telephone lines. Although not required, the secondary telephone line may be retained providing backup communication over the public switched telephone line. Optional cellular reporting is available using the CELL-MOD or CELL-CAB-N. Remote and local programming of the control panel is possible using the FS-Tools Upload/Download utility. Programming databases can be uploaded/downloaded via the panel’s USB port (and USB cable) or via an ethernet connection using the IPOTS-COM communicator. The USB port also allows for the download or upload of the entire program, history file, walk-test data, current status and system voltages by means of a USB flash drive. The power supply and all electronics are contained on a circuit board supported on a new quick install chassis and housed in a metal cabinet. Available accessories include local and remote upload/download software, remote annunciators, and reverse polarity/city boxtransmitter (4XTM).
Features
- Listed to UL Standard 864, 10th edition
- Pre-installed IPOTS-COM Ethernet IP and POTS (Plain Old Telephone Service) Central Station Communicator over AlarmNet
- Optional CELL-MOD or CELL-CAB-N GSM Central Station Communicator over AlarmNet®
- Automated activation of the NFC-50/100 Emergency Command Center
- NFC-FFT Firefighter Telephone option
- Compatible with SWIFT® wireless devices
- Auto-programming (learn mode) reduces installation time. Reports two devices set to the same address
- Four built-in, independently programmable Style Z (Class A) or Style Y (Class B) NAC circuits
- Selectable strobe synchronization for System Sensor, Wheelock, and Gentex devices
- Notification Appliance Circuit End of Line resistor matching
- Four programmable function keys for ease of maintenance
- Two programmable relays and one fixed trouble relay
- Built-in Programmer
- Integral 80-character LCD display with backlighting
- Real-time clock/calendar with automatic daylight savings control
- History file with 1,000 event capacity
- Addressable sounder base compatibility
- Control module delay timer
- Automatic detector sensitivity testing (NFPA 72 compliant)
- Automatic device type-code verification
- Point trouble identification
- Waterflow selection per module point
- Alarm verification selection per detector point
- Maintenance alert warns when smoke detector dust accumulation is excessive
- One-person audible or silent walk test with walk-test log and printout
- System alarm verification selection per detector point
- PAS (Positive Alarm Sequence) and Pre-signal per point (NFPA 72 compliant)
- Up to 16 ANN-BUS annunciators- 8 per each ANN-Bus
- Remote Acknowledge, Alarm Silence, Reset and Drill via addressable modules or remote annunciator
- Upload/Download of program and data via USB with optional FSTools Programming Utility
SLC COMMUNICATION LOOP
- Supports FlashScan® and CLIP protocols
- SLC operates up to 10,000 ft. (3,000 m) in FlashScan mode with twisted, unshielded wire
- Single addressable SLC loop which meets NFPA Class B and Class A requirements
- 198 addressable device capacity (99 addressable detectors and 99 modules)
- Compatible with NOTIFIER FireWarden and ONYX Series addressable devices (refer to the FireWarden SLC Wiring Manual)
NOTIFICATION APPLIANCE CIRCUITS (NACS)
- Four independently programmable output circuits. Circuits can be configured for the following outputs:
- Style Y (Class B)
- Style Z (Class A)
- Silence Inhibit and Autosilence timer options
- Continuous, March Time, Temporal, or California code for main circuit board NACs with two-stage capability
- Selectable strobe synchronization per NAC
- 2.5 A special application, 250mA regulated, total power for NACs
NOTE: Maximum or total 24VDC system power shared between all NAC circuits and the ANN-BUS is 2.7 A
PROGRAMMING AND SOFTWARE
- Autoprogramming (learn mode) reduces installation time
- Custom English labels (per point) may be manually entered or selected from an internal library file
- Two programmable Form-C relay outputs
- 99 software zones
- Continuous fire protection during online programming
- Program Check automatically catches common errors not linked to any zone or input point
- OFFLINE PROGRAMMING: Create the entire program in your office using FS-Tools, a Windows®-based software package, and upload/download system programming locally. Offline programming requires an ethernet connection. FS-Tools is available on www.notifier.com.
User interface
LED INDICATORS
- Fire Alarm (red)
- CO Alarm (red)
- AC Power (green)
- Supervisory (yellow)
- Trouble (yellow)
- Ground fault (yellow)
- Battery fault (yellow)
- Disabled (yellow)
- Maintenance (yellow)
- Communication (yellow)
- Alarm Silenced (yellow)
- F1-F4 Programmable Function Keys (yellow)
KEYPAD
- 16 key alpha-numeric pad
- Acknowledge
- Alarm Silence
- Drill (Manual Evacuate)
- Four (4) programmable function keys
- Reset (lamp test)
PRODUCT LINE INFORMATION
NFW-100X: Addressable Fire Alarm Control Panel with one SLC loop.
Includes main circuit board with display chassis with transformer, backbox
with door, plastic bag containing screws, cables, key, etc.
FS-Tools: Programming software for Windows®-based PC computer. Available
for download at www.notifier.com.
CELL-CAB-N/CELL-MOD: Optional GSM communicators.
IPOTS-COM: Dual technology (POTS and IP) communicator. (replacement
board)
DP-ES-R: Optional dress panel for the NFW-100X (red).
DP-ES-B: Optional dress panel for NFW-100X (black).
TR-CE-B: Optional trim ring for semi-flush mounting. (Black. For red,
order TR-CE.)
BB-XP: Optional cabinet for one or two modules.
BB-25: Optional cabinet for up to six modules mounted on CHS-6 chassis.
BB-26: Battery backbox, holds up to two 25 AH batteries and CHG75.
NFS-LBB: Battery box, houses two 55 AH batteries
CHS-6: Chassis, mounts up to six multi-modules in a BB-25 cabinet.
CHG-75: Battery charger for lead-acid batteries with a rating of 25 to 75
AH.
CHG-120: Remote battery charging system for lead-acid batteries with a
rating of 55 to 120 AH. Requires additional NFS-LBB for mounting.
NOTE: CHG-120 or CHG-75 required for batteries larger than 18AH.
BAT Series: Batteries, see data sheet DN-6933.
PRN Series: UL listed compatible event printer. Uses tractor-fed paper.
OPTIONAL MODULES
4XTM Reverse Polarity Transmitter Module: Provides a super vised output
for local energy municipal box transmitter, alarm and trouble. Includes a
disable switch and disable trouble LED.
PWRMOD24 Power Expander Module: Optional power module. Increases alarm
power output to 6 amps.
COMPATIBLE ANNUNCIATORS
N-ANN-80: Remote LCD annunciator mimics the information displayed on the
FACP LCD display. Recommended wire type is unshielded. (Basic model is
black; order -W for white; see DN-7114.)
N-ANN-100R: Remote LCD annunciator mimics the information displayed on
the FACP LCD display. Recommended wire type is unshielded. For use in FM
applications only. (Basic model is black; order R for red.)
N-ANN-I/O: LED Driver Module provides connections to a user supplied
graphic annunciator. (See DN-7105.)
N-ANN-LED: Annunciator Module provides three LEDs for each zone: Alarm,
Trouble, and Supervisory. Ships with red enclosure. (See DN-60242.)
N-ANN-RLED: Provides alarm (red) indicators for up to 30 input zones or
addressable points. (See DN-60242.)
N-ANN-RLY: Relay Module provides 10 programmable Form-C relays. Can be
mounted inside the cabinet. (See DN-7107.)
N-ANN-S/PG: Serial/Parallel Printer Gateway module provides a connection
for a serial or parallel printer. (See DN-7103.)
ADDRESSABLE DEVICES
FSP-951: Addressable low-profile photoelectric smoke detector. FlashScan
only.
FSP-951-IV: Addressable low-profile photoelectric smoke detector. Ivory.
FlashScan and CLIP mode.
NP-200: Addressable low-profile photoelectric smoke detector. B300-6 base
included, FlashScan only.
NP-200-IV: Addressable low-profile photoelectric smoke detector. Ivory,
B300-6-IV base included. FlashScan and CLIP mode.
FSP-951T: Addressable low-profile photoelectric smoke detector with
thermal sensor. FlashScan only.
FSP-951T-IV: Addressable low-profile photoelectric smoke detector with
thermal sensor. Ivory. FlashScan and CLIP mode.
NP-200T: Addressable low-profile photoelectric smoke detector with
thermal sensor. B300-6 base included. FlashScan only.
NP-200T-IV: Addressable low-profile photoelectric smoke detector with
thermal sensor. Ivory, B300-6-IV base included. FlashScan and CLIP mode.
FSP-951R: Remote test capable addressable photoelectric smoke detector
for use with DNR(W) duct detector housing. FlashScan only.
FSP-951R-IV: Remote test capable addressable photoelectric smoke detector
for use with DNR(W) duct detector housing. Ivory. FlashScan and CLIP mode.
NP-200R: Remote test capable addressable photoelectric smoke detector for
use with DNR(W) duct detector housing. FlashScan only.
NP-200R-IV: Remote test capable addressable photoelectric smoke detector
for use with DNR(W) duct detector housing. Ivory, FlashScan and CLIP mode.
FST-951: Low-profile 135°F fixed thermal sensor. FlashScan only.
FST-951-IV: Low-profile 135°F fixed thermal sensor. Ivory. FlashScan and
CLIP mode.
NH-200: Low-profile 135°F fixed thermal sensor. B300-6 base included,
FlashScan only.
NH-200-IV: Low-profile 135°F fixed thermal sensor. Ivory. B300-6-IV base
included, FlashScan and CLIP mode.
FST-951R: Low-profile, intelligent, rate-of-rise thermal sensor.
FlashScan only.
FST-951R-IV: Low-profile, intelligent, rate-of-rise thermal sensor.
Ivory.FlashScan and CLIP mode.
NH-200R: Low-profile 135°F fixed thermal sensor. B300-6 base included,
FlashScan only.
NH-200R-IV: Low-profile 135°F fixed thermal sensor. Ivory. B300-6- IV
base included, FlashScan and CLIP mode.
FST-951H: Low-profile intelligent 190°F/88°C fixed thermal sensor.
FlashScan only.
FST-951H-IV: Low-profile intelligent 190°F/88°C fixed thermal sensor.
Ivory. FlashScan and CLIP mode.
NH-200H: Low-profile intelligent 190°F/88°C fixed thermal sensor. B300-6
base included, FlashScan only.
NH-200H-IV: Low-profile intelligent 190°F/88°C fixed thermal sensor.
Ivory. B300-6-IV base included, FlashScan and CLIP mode.
Legacy Devices
FSI-851: Addressable low-profile ionization smoke detector.
NI-100: Addressable low-profile ionization smoke detector.
FSP-851: Addressable low-profile photoelectric smoke detector.
NP-100: Addressable low-profile photoelectric smoke detector.
FSP-851T: Addressable low-profile photoelectric smoke detector with
thermal sensor.
NP-100T: Addressable low-profile photoelectric smoke detector with
thermal sensor.
FSP-851R: Remote test capable addressable photoelectric smoke detector
for use with DNR(W) duct detector housing.
NP-100R: Remote test capable addressable photoelectric smoke detector for
use with DNR(W) duct detector housing.
FST-851: Fast-response, low-profile heat detector.
NH-100: Fast-response, low-profile heat detector.
FST-851R: Fast-response, low-profile heat detector with rate-of-rise
option.
NH-100R: Fast-response, low-profile heat detector with rate-of-rise
option.
FST-851H: Fast-response, low-profile heat detector that activates at
190°F/88°C.
NH-100H: Fast-response, low-profile heat detector that activates at
190°F/88°C.
FAPT-851: Addressable low-profile multi-sensor detector.
NP-A100: Addressable low-profile multi-sensor detector.
B200S: Programmable, addressable sounder base.
B200SR: Addressable sounder base.
DNR: InnovairFlex low-flow non-relay duct-detector housing. (Order FSP-
851R, FSP-951R, or NP-100R separately.)
DNRW: InnovairFlex low-flow non-relay duct-detector housing, with NEMA-4
rating. Watertight. (Order FSP-851R, FSP-951R, or NP-100R separately.)
Addressable Modules
FMM-1: Addressable Monitor Module for one zone of normally-open dry-
contact initiating devices. Mounts in standard 4.0″ (10.16 cm.) box. Includes
plastic cover plate and end-of-line resistor. Module may be configured for
either a Style B (Class B) or Style D (Class A) IDC.
NMM-100: Addressable Monitor Module for one zone of normallyopen dry
contact initiating devices. Mounts in standard 4.0″ (10.16 cm.) box. Includes
plastic cover plate and end-of-line resistor. Module may be configured for
either a Style B (Class B) or Style D (Class A) IDC.
FDM-1: Dual Monitor Module. Same as NMM-100 except it provides two Style
B (Class B) only IDCs.
NDM-100: Dual Monitor Module. Same as NMM-100 except it provides two
Style B (Class B) only IDCs.
FMM-101: Miniature version of NMM-100. Excludes LED and Style D option.
Connects with wire pigtails. May mount in device backbox.
NMM-100P: Miniature version of NMM-100. Excludes LED and Style D option.
Connects with wire pigtails. May mount in device backbox.
FZM-1: Similar to NMM-100. Addressable Monitor Module for one zone of
conventional two-wire detectors. Requires resettable 24 VDC power. Refer to
the Device Compatibility Document for listed compatible devices and quantity
limitation.
NZM-100: Similar to NMM-100. Addressable Monitor Module for one zone of
conventional two-wire detectors. Requires resettable 24 VDC power. Refer to
the Device Compatibility Document for listed compatible devices and quantity
limitation.
FCM-1: Addressable Control Module for one Style Y/Z (Class B/A) zone of
supervised polarized Notification Appliances. Mounts directly to a 4.0″ (10.16
cm.) electrical box. NAC option requires external 24 VDC to power notification
appliances.
NC-100: Addressable Control Module for one Style Y/Z (Class B/A) zone of
supervised polarized Notification Appliances. Mounts directly to a 4.0″ (10.16
cm.) electrical box. NAC option requires external 24 VDC to power notification
appliances.
FRM-1: Addressable relay module containing two isolated sets of Form-C
contacts, which operate as a DPDT switch. Mounts directly to a 4.0″ (10.16
cm.) box, surface mount using the SMB500.
NC-100R: Addressable relay module containing two isolated sets of Form-C
contacts, which operate as a DPDT switch. Mounts directly to a 4.0″ (10.16
cm.) box, surface mount using the SMB500.
NBG-12LX: Addressable manual pull station with interface module mounted
inside.
NOT-BG12LX: Addressable manual pull station with interface module mounted
inside.
ISO-X: Fault Isolator Module.
N100-ISO: Fault Isolator Module.
ISO-6: Six-fault isolator module. Mount one or two modules in a BBXP
cabinet (optional). Mount up to six modules on a CHS-6 chassis in a
CAB-3/CAB-4 series cabinet.
SMB500: Used to mount all modules except the FMM-101/NMM100P.
NMM-100-10: Ten-input monitor module. Mount one or two modules in a BB-2F
cabinet (optional). Mount up to six modules on a CHS-6 chassis in a BB-6F
cabinet.
NZM-100-6: Six-zone interface module. Mount one or two modules in a BB-XP
cabinet (optional). Mount up to six modules on a CHS-6 chassis in a
CAB-3/CAB-4 series cabinet
System Capacity
- Intelligent Signaling Line Circuits…………………………………………1
- Addressable device capacity …………………………………………..198
- Programmable software zones………………………………………….99
- Annunciators…………………………………………………………………..16
Electrical Specifications
AC Power: Operates in either 120 or 240 VAC, 50/60 Hz, 3.25 A, auto-
sensing- no switch required. Wire size: minimum 14 AWG (2.00 mm2) with 600 V
insulation. Nonpower-limited, supervised.
Battery: Two 12 V 18 AH lead-acid batteries. Battery Charger
Capacity: 7-18 AH (FireWarden-100X cabinet holds maximum of two 18 AH
batteries.)
Communication Loop: Supervised and power-limited.
Notification Appliance Circuits: Terminal Block provides connections for
four NACs, Style Y (Class B) or Style Z (Class A). Special Application power.
Power-limited, supervised circuitry. Maximum signaling current per circuit:
2.5 amps special application, 250mA regulated. End-of-Line Resistor: 4.7k ohm,
½ watt (P/N 71252 UL listed) for Style Y (Class B) NAC; system capable of 1.9
kΩ – 22 kΩ ELR range. Refer to the NOTIFIER Device Compatibility Documen for
listed compatible devices.
Two Programmable Relays and One Fixed Trouble Relay: Contact rating: 2.0
A @ 30 VDC (resistive), 0.5 A @ 30 VAC (resistive). Form-C relays, non-power-
limited, non-supervised.
Cabinet Specifications
Door: 19.26″ (48.92 cm.) high x 16.82″ (42.73 cm.) wide x 0.72″ (1.82
cm.) deep.
Backbox: 19.00″ (48.26 cm.) high x 16.65″ (42.29 cm.) wide x 5.25″ (13.34
cm.) deep.
Trim Ring (TR-CE/B): 22.00″ (55.88 cm.) high x 19.65″ (49.91 cm.) wide.
Shipping Specifications
Weight: 26.9 lbs. (12.20 kg.)
Dimensions: 20.00” (50.80 cm.) high x 22.5” (57.15 cm.) wide x 8.5”
(21.59 cm.) deep.
Temperature and Humidity Ranges
This system meets NFPA requirements for operation at 0 – 49°C/32 – 120°F and
at a relative humidity 93% ± 2% RH (noncondensing) at 32°C ± 2°C (90°F ± 3°F).
However, the useful life of the system’s standby batteries and the electronic
components may be adversely affected by extreme temperature ranges and
humidity. Therefore, it is recommended that this system and its peripherals be
installed in an environment with a normal room temperature of 15 – 27°C/60 –
80°F.
Addressable Device Accessories
End-of-Line Resistor Assembly (R-47K and R-3.9K): The 47k ohm assembly
supervises the NMM-100-10, NDM-100, NMM100P, and NC-100 module circuits. The
3.9k ohm assembly supervises the NZM-100-6 module circuit. These resistors are
included with each module.
Power Supervision Relay: Supervises the power to 4-wire smoke detectors
and notification appliances.
Wiring Requirements
While shielded wire is not required, it is recommended that all SLC wiring be
twisted-pair to minimize the effects of electrical interference. Refer to the
panel manual for wiring details.
NFPA Standards
The FireWarden-100X complies with the following NFPA 72 Fire Alarm Systems
requirements:
- LOCAL (Automatic, Manual, Waterflow and Sprinkler Supervisory).
- AUXILIARY (Automatic, Manual and Waterflow) (requires 4XTM).
- REMOTE STATION (Automatic, Manual and Waterflow) (Where a DACT is not accepted, the alarm, trouble and supervisory relays may be connected to UL 864 listed transmitters. For reverse polarity signaling of alarm and trouble, 4XTM is required.)
- PROPRIETARY (Automatic, Manual and Waterflow).
- CENTRAL STATION (Automatic, Manual and Waterflow, and Sprinkler Supervised).
- OT, PSDN (Other Technologies, Packet-switched Data Network)
- IBC 2012, IBC 2009, IBC 2006, IBC 2003, IBC 2000 (Seismic).
- CBC 2007 (Seismic)
Agency Listings and Approvals
The listings and approvals below apply to the basic FireWarden100X control
panel. In some cases, certain modules may not be listed by certain approval
agencies, or listing may be in process. Consult factory for latest listing
status.
- UL: S635
- CSFM: 7165-0028:0505
- FDNY: COA #6268
This document is not intended to be used for installation purposes. We try to keep our product information up-to-date and accurate. We cannot cover all specific applications or anticipate all requirements. All specifications are subject to change without notice.
AlarmNet®, NOTIFIER®, FireWarden®, SWIFT®, and System Sensor® are registered trademarks of Honeywell International Inc. Microsoft® and Windows® are registered trademarks of the Microsoft Corporation. ©2018 by Honeywell International Inc. All rights reserved. Unauthorized use of this document is strictly prohibited.
Country of Origin: USA
References
- Fire Alarm Resources | Download fire alarm documents
- Fire-Lite | Honeywell Building Technologies
- Home (USA) | NOTIFIER by Honeywell | Engineered Fire Alarm System.
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>