NOTIFIER SpectrAlert SP200, 300 Series Dual Voltage Evacuation Speakers Instruction Manual
- June 9, 2024
- NOTIFIER
Table of Contents
NOTIFIER SpectrAlert SP200, 300 Series Dual Voltage Evacuation Speakers
General
System Sensor® SP2 and SP3 Series speakers combine performance, functionality,
and flexibility in the latest line of dual voltage evacuation speakers.
Performance. With its low total harmonic distortion, the Spectr Alert SP2
Series offers fidelity-quality sound output. This performance provides greater
assurances that the SP2’s output more closely matches the source signal. This
fidelity sound quality is achieved at any of the SP2’s four field-selectable
power taps: 1/4, 1/2, 1, and 2 watts. The SpectrAlert SP3 Series offers
greater sound output at every tap setting for applications with high ambient
noise levels.
Functionality. Installation ease and functionality are achieved via the
speaker’s compact design, which allows flush mounting to a 4.0″ x 4.0″ x
2.125″ (10.16 x 10.16 x 5.398 cm) backbox, without the need for an extension
ring.
Flexibility. The SP2 and SP3 Series speakers are designed for a variety
of application requirements. Offered with round and square grilles, they can
be ceiling or wall mounted. White and red grille color options are also
available to meet specific aesthetic requirements.
Features
- Fidelity sound quality (SP2).
- Enhanced SPL (SP3).
- 25.0 and 70.7 VRMS dual-voltage settings.
- Four field-selectable power taps.
- No extension ring required.
- Low-profile design.
- Ceiling- and wall-mount applications.
- Grilles available in white and red.
- Color-matched mounting screws.
Engineering Specifications
Speaker shall be a System Sensor Model ____ dual-voltage transformer speaker capable of operating at 25.0 or 70.7 nominal VRMS. Speaker shall be listed to Underwriters Laboratories’ Standard 1480 for fire protective signaling systems. Speaker shall have a frequency range of 400 to 4000 Hz and shall have an operating temperature between 32°F and 120°F (0°C and 49°C). Speaker shall have power taps that are selected by shunts.
Operating Specifications
MECHANICAL
- Input terminals: 12 to 18 AWG (3.31 to 0.821 mm²).
- Speaker size: 4 inches (101 mm).
- Grille size: round 6.875 inches (107 mm); square 5 inches (127 mm).
ELECTRICAL
- Voltage Input: 25.0 volts or 70.7 volts nominal.
- Frequency range: 400 to 4000 Hz. NOTE: The SP200 and SP300 Series are UL Listed from 400 to 4000 Hz. The SP200 Series will provide a flat (±10 dB) output from 100 to 15,000 Hz. The SP300 Series will provide a flat (±10 dB) output from 500 to 13,000 Hz.
- Operating temperature range: 32°F to 120°F (0°C to 49°C).
- Power: 1/4, 1/2, 1 and 2 watts.
Sound Output
UL Reverberant (dBA @ 10 ft./3.048 m)
| 2 W| 1 W| 1/2 W| 1/4 W
SP2| 84| 81| 78|
75
SP3
| 89| 86| 84|
80
Agency Listings and Approvals
The listings and approvals below apply to Spectra Alert Dual Voltage Evacuation Speakers. In some cases, certain modules may not be listed by certain approval agencies, or listing may be in process. Consult factory for latest listing status.
-
UL Listed: file S4048.
-
ULC Listed: file CS548 (SP200W/R[A], SP200W/R[A]).
-
MEA approved:
– file 461-05-E (SP300W, SP301R, SP301W).
– file 353-98-E (SP200W/R[A], SP201W/R[A]).
– file 139-05-E (SP201K, SP2R1224MCK). -
CSFM approved: 7320-1653:183
Voltage and Power Selection
Example shown: selecting a 1/4 watt input when a 25.0 volt (nominal) amplifier is being used.
Mounting Diagrams
Ordering Information
White | Red | Description | Speaker Voltage |
---|
SpectrAlert Dual-Voltage Evacuation Speakers
SP200W| —| Round, standard SPL, 1/4 – 2 watt power tap.| 25.0/70.7 VRMS
SP201W| SP201R| Square, standard SPL, 1/4 – 2 watt power tap.| 25.0/70.7 VRMS
SP300W| —| Round, high SPL, 1/4 – 2 watt power tap.| 25.0/70.7 VRMS
SP301W| SP301R| Square, high SPL, 1/4 – 2 watt power tap.| 25.0/70.7 VRMS
Accessories
BBSCW| —| Surface-mount backbox skirt for SP200W, SP300W.| NA
BBS- SP201W| BBS-SP201R| Surface-mount backbox skirt for SP201W, SP301W.| NA
NOTIFIER®, SpectrAlert®, and System Sensor® are registered trademarks of
Honeywell International Inc.
©2006 by Honeywell International Inc. All rights reserved. Unauthorized use of
this document is strictly prohibited.
Customer Support
This document is not intended to be used for installation purposes.
We try to keep our product information up-to-date and accurate.
We cannot cover all specific applications or anticipate all requirements.
All specifications are subject to change without notice.
For more information, contact Notifier.
Phone:203-484-7161, FAX:
203-484-7118.
www.notifier.com
firealarmresources.com
Documents / Resources
|
NOTIFIER SpectrAlert SP200, 300 Series Dual Voltage Evacuation
Speakers
[pdf] Instruction Manual
SP200 SP201 SP300 SP301 Dual-Voltage Evacuation Speakers, SpectrAlert SP200
300 Series Dual Voltage Evacuation Speakers, SpectrAlert SP200 Series Dual
Voltage Evacuation Speakers, SpectrAlert SP300 Series Dual Voltage Evacuation
Speakers, Dual Voltage Evacuation Speakers, Evacuation Speakers, Speakers
---|---
References
- Fire Alarm Resources | Download fire alarm documents
- Home (USA) | NOTIFIER by Honeywell | Engineered Fire Alarm System.
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>