NOTIFIER SpectrAlert SP2C Series Ceiling-Mount Speaker/Strobes Instructions

June 9, 2024
NOTIFIER

NOTIFIER SpectrAlert SP2C Series Ceiling-Mount Speaker/Strobes

NOTIFIER-SpectrAlert-SP2C-Series-Ceiling-Mount-Speaker-Strobes-
PRODUCT

GENERAL

System Sensor’s SP2C Series Speaker/Strobes combine leading-edge strobe and speaker technology with a design specifically intended for ceiling-mount applications.
Technology — SpectrAlert® SP2C ceiling speaker/strobes combine the low current draw of the ceiling-mount SpectrA-lert® strobes, with the intelligible, fidelity sound quality of the SpectrAlert® SP200 Series evacuation speaker.
Flexibility — Like all SpectrAlert® products, the SP2C Series ceiling speaker/strobes feature the flexibility to meet a wide variety of applications. The 24-volt strobe is available in six different candelas, including 177 candela for sleeping areas. The speaker offers field-selectable 25.0/70.7 voltage and 1/4, 1/2, 1, and 2 watt power taps.
Aesthetics — The SP2C Series ceiling speaker/strobes offer a design that is sensitive to the aesthetic demands of ceiling-mount applications. The round shape maintains a low-profile appearance, similar to that of a smoke detector. Its stylish curves and design further refine the aesthetics over other generic wall/ceiling-mount designs. Yet SpectrAlert®’s round shape provides clearly visible “FIRE” identification from all angles.
Installation — The SP2C Series ceiling speaker/strobes include several features to simplify installation. By incorporat-ing the SP200 Series speaker, the entire unit may be mounted to a standard 4″ x 4″ x 2-1/8″ (101.6 x 101.6 x 53.975 mm) backbox without an extension ring. An optional backbox skirt is also available for surface-mount applications. With SpectrA-lert®’s round shape, aligning the backbox with the room’s walls is not necessary — SpectrAlert® always lines up.

FEATURES

  • Combines SpectrAlert® ceiling-mount strobe and speaker technologies for low current draw, fidelity sound quality.
  • 24-volt models available with 15, 15/75, 30, 75, 95, 115, and 177 candela strobes.
  • 25.0 and 70.7 volt speaker with four field-selectable power taps.
  • Ceiling-specific shape, profile, and aesthetics.
  • Strobe is synchronizable with MDL Sync•Circuit™ module.
  • Mounts to a 4″ x 4″ x 2-1/8″ (101.6 x 101.6 x 53.975 mm) backbox without an extension ring.
  • Round shape offers greater placement flexibility.

SPECIFICATIONS

GENERAL

  • Dimensions: 6.8″ (172.72 mm) diameter.
  • Mounting: 4″ x 4″ x 2-1/8″ (101.6 x 101.6 x 53.975 mm) back-box.
  • Indoor Operating Temperature: 32°F to 120°F (0°C to 49°C).

STROBES

  • Strobe Operating Voltage: 24 VDC and FWR unfiltered.
  • Input Terminals: 12 to 18 AWG (3.25 to 0.75 mm²).
  • Operating Voltage Range: 24 volts, 16 – 33 volts.
  • Operating Voltage Range with Sync•Circuit™ Module: 24 volts, 17 – 33 volts.

SPEAKERS

  • Input Voltage: 25.0 or 70.7 volts (nominal).
  • Input Terminals: 12 to 18 AWG (3.25 to 0.75 mm²).
  • Frequency Range: 400 – 4,000 Hz.
  • NOTE: The SP2C Series is UL listed from 400 to 4,000 Hz, but will provide an output from 100 to 10,000 Hz.
  • Power Taps: 1/4, 1/2, 1, and 2 watts.

SOUND OUTPUT

dBA @ 10 Feet 2 W 1 W 1/2 W 1/4 W
**UL Reverberant*** 84 81 78 75
UL Anechoic 87 84 81 78

* Assumes flush-mount installation

ARCHITECTURAL/ENGINEERING SPECIFICATIONS
Ceiling speaker/strobe shall be a System Sensor Model ____ listed to UL 1480 and UL 1971 and be approved for fire protective signaling systems. Speaker shall be capable of operating at 25.0 or 70.7 nominal Vrms, and shall have a fre-quency range of 400 to 4,000 Hz. Speaker shall have power taps which are selected by shunts. The strobe shall comply with the NFPA 72 requirements for visible signaling appli-ances, flashing at 1 Hz over the strobe’s entire operating volt-age range. The strobe light shall consist of a xenon flash tube and associated lens/reflector system.

AGENCY LISTINGS AND APPROVALS
These listings and approvals apply to the modules specified in this document. In some cases, certain modules or applica-tions may not be listed by certain approval agencies, or listing may be in process. Consult factory for latest listing status.

  • UL Listed: S4048
  • MEA Listed: 63-00-E (15, 15/75, 30, 75, 95 cd models); 218- 00-E (115, 177 cd models)
  • CSFM: 7320-1653:143

ORDERING INFORMATION WITH CURRENT DRAW


Description

| Model No. (white)| ****

Candela

| FWR Max. Operating Strobe Current

(mA RMS)

| DC Max. Operating Strobe Current (mA RMS)
---|---|---|---|---




Ceiling Speaker/ Strobes

| SP2C2415| 15| 68| 64
SP2C241575| 15/75| 77| 78
SP2C2430| 30| 107| 113
SP2C2475| 75| 197| 205
SP2C2495| 95| 239| 274
SP2C24115| 115| 298| 325
SP2C24177| 177| 399| 489
Surface-Mount Back- Box Skirt| BBSCW|  |  |

NOTIFIER-SpectrAlert-SP2C-Series-Ceiling-Mount-Speaker-Strobes-FIG
1

SpectrAlert® is a registered trademark and Sync•Circuit™ is a trademark of Honeywell International Inc.
©2008 by Honeywell International Inc. All rights reserved. Unauthorized use of this document is strictly prohibited.

This document is not intended to be used for installation purposes.
We try to keep our product information up-to-date and accurate.
We cannot cover all specific applications or anticipate all requirements.
All specifications are subject to change without notice.
For more information, contact Notifier. Phone: 203-484-7161, FAX: 203-484-7118. www.notifier.com

firealarmresources.com

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

NOTIFIER User Manuals

Related Manuals