NOTIFIER APS-6R 6.0 Amp Auxiliary Power Supply Instruction Manual
- June 9, 2024
- NOTIFIER
Table of Contents
NOTIFIER APS-6R 6.0 Amp Auxiliary Power Supply
GENERAL
The APS-6R is a state-of-the-art, 150 watt, switching auxiliary power supply providing 24 VDC of filtered DC power. The APS-6R provides two 24 VDC output circuits, each rated for 3.0 Amps in alarm and 2.0 Amps continuous. It is used for the operation of peripheral audible/visual devices (alarm signaling appliances) for the NOTIFIER AM2020, AFP1010, NFS-3030, NFS-640, AFP-400, AFP-300, AFP-200, System 5000, and System 500 control panels.
FEATURES
- Lightweight, compact design.
- “Off-line” switching technology.
- Forward topology.
- Unique design — magnetic flux-sensed converter elimi- nates need for opto-coupler feedback.
- 120 or 240 VAC (@ 50/60 Hz) field-selectable.
- Wide input voltage range: 90 132 VAC, 180 264 VAC. · High efficiency. · Output circuits with overload protection.
- Built-in “brown-out” circuitry.
- Diagnostic trouble LED.
- Plug-in connector for in cabinet applications and screw terminals for remote device applications.
- Shares battery and charger circuit with control panel.
- Power-limited design, per UL requirements.
- Surface-mount technology conserves panel space.
- AC Fail supervision with field-selectable delay per UL 864.
- Heavy-duty clamp-type terminals accept up to 12 AWG (3.1 mm²) wire.
CONSTRUCTION AND OPERATION
When used with the CAB-3 or CAB-4 Series (CAB-A3/-A4, B3/-B4, -C3/-C4, or
-D3/-D4), the APS-6R mounts to a CHS-4 or CHS-4L mounting chassis. If more
than one APS-6R is necessary to satisfy Audible/Visual (DC) power
requirements, connect additional APS-6R power supplies together as described
in the Installation Instruction Manual. When used with the AFP-200, the APS-6R
mounts in the lower portion of the cabinet where batteries would normally
mount (BB-17 required). When used with the System 500, only one APS-6R may be
mounted in the right-most position in the cabinet.
Underwriters Laboratories requires that all Signaling Appliances be approved
for use with the selected control system due to voltage operating range
criteria. Use only those appliances listed for use with the associated control
system. Refer to Device Compatibility Document #15378.
SPECIFICATIONS
Compatible with: AM2020, AFP1010, NFS-3030, NFS-640, AFC-600, AFP-400, AFP-300, AFP-200, System 5000, and System 500 control panels.
DIMENSIONS:
6.125″ (15.558 cm.) high x 4.25″ (11.43 cm.) wide x 3.0″ (7.62 cm.) deep at protruding edge, 2.25″ (5.715 cm.) deep at box edge on opposite side.
ELECTRICAL SPECIFICATIONS
-
AC primary input power (TB1): 120 VAC: 120 VAC, 60 Hz, 2.5 A. 240 VAC (cut JP1): 240 VAC, 50 Hz, 1.2 A.
-
DC secondary input power (TB3): TB3-1 (+), TB3-2 ().
-
24 VDC output power (TB2) : Total 6.0 A (4.0 A continuous). Circuit 1 (TB2-1, TB2-2; or J1): 3.0 A @ 24 VDC power-limited. Circuit 2 (TB2-3, TB2-4; or J2): 3.0 A @ 24 VDC powerlimited.
-
Fuses: F1 (AC supervision): 250 VAC, 4.0 A, 3 AG. F2 (battery supervision): 32 VAC, 10.0 A, 3 AG.
-
Trouble supervision bus: J3 output: Form-A contact (open collector). J4 input: Form-A contact (open collector).
NOTE: J3 and J4 can be interchanged. -
Loss of AC indication: Immediate indication (default); 8hour delay (cut JP2); 16-hour delay (cut JP2 and JP3).
MECHANICAL SPECIFICATIONS
The APS-6R in its enclosure measures approximately 6″ (15.24 cm) x 4″ (10.16 cm) x 3″ (7.62cm).
CABINETS FOR MOUNTING
- CAB-3/CAB-4 Series: Use CHS-4 and CHS-4L chassis, for AM2020, AFP1010, NFS-3030, NFS-640, AFP-400, AFP-300, and System 5000 control panels.
- System 500: Can mount one APS-6R if the face module expansion card (such as an ICE-4) is not installed.
- CAB-400AA: For AFP-300 and AFP-400 control panels. Mounts up to one APS-6R. An option module, without expansion card, is allowed.
- AFP-200 backbox. Mount up to one APS-6R in the lower position of the box (where batteries mount). A BB-17 battery box is required.
PRODUCT LINE INFORMATION
- APS-6R: 24-volt, filtered power supply (120/220 VAC input).
- EOLR-1: 12/24 VDC end-of-line relay.
- CHS-4: Four-module chassis.
- CHS-4L: Four-module chassis (low-profile).
Agency Listings and Approvals
The listings and approvals below apply to the basic APS-6R. In some cases, certain modules may not be listed by certain approval agencies, or listing may be in process. Consult factory for latest listing status.
- UL: S624
- ULC: CS118/CS733/CBP696 Vol. IX
- FM: Approved (AFP-200, AFP-300/400, AFC-600, NFS640, AFP 1010/AM2020, NFS-3030, System 500, System 5000)
- CSFM: 7315-0028:190, 7165-0028:214 (NFS-640); 7165:0028:224 (NFS-3030, NFS2-3030); 7170-0028:216 (NFS-640); 7170-0028:223 (NFS-3030, NFS2-3030)
- MEA: 195-97-E Vol. II, 447-99-E (AFC-600), 317-01-E (NFS-640), 345-02-E (NFS-3030), 232-02-E (NFS23030)
![Mounting APS-6R to the
CHS-4 Chassis](https://manuals.plus/wp-content/uploads/2023/03/NOTIFIER-APS- 6R-6.0-Amp-Auxiliary-Power-Supply-Instruction-Manual-3.png)
NOTIFIER® is a registered trademark of Honeywell International Inc. ©2009 by Honeywell International Inc. All rights reserved. Unauthorized use of this document is strictly prohibited.
Customer Support
This document is not intended to be used for installation purposes. We try
to keep our product information up-to-date and accurate.
We cannot cover all specific applications or anticipate all requirements.
All specifications are subject to change without notice.
For more information, contact Notified.
Phone:203-484-7161, FAX:
203-484-7118.
www.notifier.com
firealarmresources.com
Documents / Resources
|
NOTIFIER APS-6R 6.0 Amp Auxiliary Power
Supply
[pdf] Instruction Manual
APS-6R 6.0 Amp Auxiliary Power Supply, APS-6R, 6.0 Amp Auxiliary Power Supply,
6.0 Amp Power Supply, Auxiliary Power Supply, APS-6R Power Supply, Power
Supply
---|---
References
- Fire Alarm Resources | Download fire alarm documents
- Home (USA) | NOTIFIER by Honeywell | Engineered Fire Alarm System.