NOTIFIER EPR and EPR-M Series Protectowire Linear Heat Detector Instruction Manual
- June 9, 2024
- NOTIFIER
Table of Contents
NOTIFIER EPR and EPR-M Series Protectowire Linear Heat Detector
GENERAL
The System Sensor/Protectowire Linear Heat Detector is a proprietary cable
that detects heat conditions anywhere along its length. It is considered a
normally-open contact device and as such can be interfaced to a Notifier
intelligent addressable fire alarm control panel via monitor modules: FMM-1,
FDM-1, FMM-101, and XP10-M. The sensor cable is comprised of two steel
conductors individually insulated with a heat sensitive polymer. The insulated
conductors are twisted together to impose a spring pressure between them, then
wrapped with a protective tape and finished with an outer jacket suitable for
the environment in which the detector will be installed.
Protectowire is a fixed temperature digital sensor and is therefore capable of
initiating an alarm once its rated
activation temperature is reached. At the rated temperature, the heatsensitive
polymer insulation yields to the pressure between conductors, permitting them
to move into contact with each other, thereby initiating an alarm signal. It
is not required that a specific length be heated in order to initiate an
alarm, nor is system calibration necessary to compensate for changes in the
installed ambient temperature. Protectowire Linear Heat Detector provides the
advantages of line coverage with point sensitivity.
The Detector must be installed in continuous runs without taps or branches in accordance with locations and spacing prescribed by the approving authorities; NFPA 70 National Electrical Code, NFPA 72 National Fire Alarm Code or as determined by the local authority having jurisdiction. Except for zoning requirements (alarm source indication) the length of each run is limited, and controlled by the electrical characteristics of the control equipment to which the Detector is connected.
FEATURES
- Up to 1,000 ft. of the Protectowire Linear Heat Detector may be connected to the initiating device circuit of the addressable monitor module.
- Eight different Linear Heat Detector models available, each packaged in 500 ft. rolls.
- Fixed Temperature Digital Sensor
- Line Coverage with Point Sensitivity
- Wide Range of Industrial Applications, such as Aircraft Hangers, Manufacturing Facilities, Warehouses, Tank Farms, Coal Conveyors, Refrigerated Storage, Dust Collectors, Cooling Towers, Tunnels, and Floating Roof Tanks.
- Good Abrasion Resistance
- Excellent Weathering Properties and High Temperature Performance.
- A comprehensive range of mounting and installation accessories are available.
EPR Series
The EPR series contains an extruded flame retardant jacket of polypropylene elastomer with a special UV stabilizer added to enhance weathering performance. It is intended for a wide range of industrial applications and is characterized by high resiliency, good abrasion resistance, excellent weathering properties and exceptional high temperature performance. Messenger wire is also available for any model detector. It consists of high tensile strength stainless steel wire, which is wound around the detector. It is a support wire, which is designed to simplify the installation of the detector in areas where mounting is difficult due to the lack of appropriate support structures or mounting surfaces.
EPR-M Messenger wire Series
Messenger wire (a Protectowire exclusive), is available with any of the four EPR models offered from Notifier. It consists of high tensile strength stainless steel wire, which is wound around the Detector at the rate of approximately one turn per foot (.3 m). It is a carrier or support wire which is designed to simplify the installation of the Detector in areas where mounting is dif ficult due to the lack of appropriate support structures or mount ing surfaces. When using messenger wire to support the Detector, turnbuckles and eyebolts must be employed at each end of a straight run to place tension on the support wire.
NOTIFIER® is a Honeywell company. This document is not intended to be used for installation purposes. We try to keep our product information up-to-date and accurate. We cannot cover all specific applications or anticipate all requirements. All specifications are subject to change without notice. For more information, contact NOTIFIER. Phone: 203-484-7161 FAX: 203-484-7118 12 Clintonville Road, Northford, Connecticut 06472
Linear Heat Detectors
**Models*
PHSC-155-EPR 155ºF (68ºC) Alarm Temperature
PHSC-155-EPR-M 156-EPR with Messenger Wire
PHSC-190-EPR 190ºF (88ºC) Alarm Temperature
PHSC-190-EPR-M 190-EPR with Messenger Wire
PHSC-280-EPR 280ºF (138ºC) Alarm Temperature
P HSC-280-EPR-M 280-EPR with Messenger Wire
PHSC-356-EPR** 356ºF (180ºC) Alarm Temperature
PHSC-356-EPR-M**** 356-EPR with Messenger Wire
*Available in 500 ft. lengths only.
**Maximum Ambient Temperature of 250ºF (121ºC)
Approvals/Maximum Listed Spacing
Type EPR Linear Heat Detector UL (25 ft/7.6m) FM (25 ft./7.6m)
The distance between detector runs shall not exceed the listed spacing.
Reduced spacing may be required based upon factors such as ceiling height and
construction, physical obstructions, air movement, or the authority having jur
isdiction (AHJ). When Protectowire is used for sprinkler system activation,
special Factory Mutual (FM) reduced spacing guidelines may also be applicable.
CHEMICAL RESISTANCE CHART FOR PROTECTOWIRE TYPE EPR JACKET MATERIAL
Ratings-Chemical Effect:
A – Little or no effect. C – Moderate effect. (< 20% Volume Swell) (40-60%
Volume Swell)
B – Minor effect. D – Severe effect – Not (20-40% Volume Swell)
recommended (>60% Volume Swell)
(Immersion times were approximately 168 hours per ASTM D-471 at 23°C or as
stated.)
Fluids
Chemicals Rating
Acetic Acid 50% A
Sulfuric Acid 98% A
Hydrochloric Acid 10% A
Potassium Hydroxide 10% A
Sodium Hydroxide 50% A
Zinc Chloride 10% A
Water @ 100°C A
Water (Chlorine 4ppm) A
Water (Chloramines 4ppm) A
Sea Water A
Sodium Chloride 15% A
Acetone A
Acrylonitrile A
Aniline A
n-Butyl Acetate A
Ethanol A
Diethylether A
Glycerol A
n-Hexane A
Methanol A
Methylethylketone A
Nitrobenzene A
1- Propanol A
Petroleum Oils & Fuels Rating
Oil ASTM #1 @ 100°C A
Oil ASTM #2 @ 100°C A
Oil ASTM #3 @ 100°C B
Fuel B (Isooctane/Toluene, 70/30) B
Fuel C (Isooctane/Toluene, 50/50) B
Automotive Fluids Rating
Hydraulic Brake Fluid A
Hydraulic Brake Fluid @ 100°C A
Ethylene Glycol A
(Antifreeze/water 50/50) @ 125°C
Important Installation Information. Please Read!
Protectowire Linear Heat Detector may be installed at the ceiling level to
protect areas within buildings (area protection) in the same fashion as the
more familiar spot type heat detectors. Please refer to the National Fire
Alarm Code, NFPA 72, for basic information on the installation and spacing of
linear heat detectors for area protection. For special applications where the
Detector is installed close to the hazard, the manufacturer’s recommendations
and/or installation instructions should be followed. Whenever there is a
choice between two or more possible installation procedures, the one which
results in increased protection should be utilized.
For additional installation information on Protectowire Linear Heat Detectors
please refer to the Installation/Operation/ Maintenance Manual (MAN
2001E-0603) and the Important Installation Information document (DS-7736) on
www.Protectowire.com.
Page 2 of 4 — DN-6972 · 05/01/04
firealarmresources.com
Protectowire Accessories
System Sensor offers an assortment of approved Protectowire fasteners and splicing devices to facilitate installation for both standard and special applications. Protectowire approved fasteners are generally designed to lightly clamp the detector which enables a tension to be applied progressively. This method is better than arrangements which apply a high tensile load at the end of each run or clamp and compress the sensor cable so tightly that the inner insulation becomes damaged. To ensure a trouble-free installation, only Protectowire approved fasteners should be used. The use of non-approved fasteners may physically damage the detector thereby causing “false alarms” and in some cases void the detector’s warranty.
Accessories
Commercial Type Zone/End-of-Line Junction Box
Model Description
ZB-4-QC-MP Non-metallic Moisture proof Box with Compression terminals.
SR-502 Strain Relief Connector
Heavy Duty Type Zone/End-of-Line Junction Box
Model Description
ZB-HD-4-QC Fiberglass enclosure with compression terminals (NEMA 4x).
Splicing Connectors and Termination Assemblies Flexible Leads
Model Description
PFL Used when terminating 2 conductor Protectowire Linear Heat
Detector in constrained spaces such as pull station or smoke detector back
boxes Splicing Connector
Model Description
PWSC Used when splicing standard 2 conductor Protectowire Linear Heat
Detector.
Splicing Tape/Sealant Tape
Model Description
#35 -White Used to protect all splices of Protectowire Linear Heat
Detector after sealing against moisture using SFTS-1-8-F Sealant Tape.
33+ Used to protect all splices of Protectowire Linear Heat Detector
after sealing against moisture using SFTS-1-8-F Sealant Tape in cold
environments as low as 0ºF (–18ºC).
SFTS-1-8-F Used to seal all splices of Protectowire Linear Heat Detector
against moisture.
General Purpose Fasteners Clips
Model Description
WAW-P WAW Clips may be used for ceiling or wall mount applications, as
well as at corners.
Available in a polypropylene material.
OHS -1 Line Clip is used mainly as an intermediate fastener between
corner mounted WAW clips which provide the main support.
OHS -SS Stainless steel line clip with 1/ 4 inch hole. Used mainly as an
intermediate fastener between corner mounted WAW clips which provide the main
support.
Insulated Standoff
Model Description
TR-5G The Insulated Standoff can be used to install Protectowire on or
above conveyors or from other applicable mechanical structures.
Cable Ties for Cable Mount
Model Description
PLT1S-CO Used with EMS Cable Mounts, constructed of weather resistant
nylon suitable for outdoor use.
Beam Clamp Assemblies
Model Description
BC-2 The BC-2 Series Beam Clamp Assembly, consists of a beam clamp, WAW clip
and snap button.
BC-2 utilizes a plated steel clamp and is recommended for general
indoor use. This fastener may be used for mounting Protectowire on cable
trays, conveyors, angle irons, I-beams, bar joists. BC-3P The BC-3P consists
of a beam clamp, a Polypropylene WAW clip (type P) and snap button. These
fasteners are suitable for outdoor use. This fastener may be used for mounting
Protectowire on cable trays, conveyors, angle irons, I-beams, bar joists.
Adhesive Cable Mount/“L” Bracket
Model Description
EMS-A-CO Adhesive mounting system consists of EMS cable mounts, PLT cable
ties and approved industrial adhesive. Constructed of black weather resistant
nylon and suitable for outdoor use when used with approved adhesive.
RMC-2 Plated steel brackets used for mounting Protectowire to the rim
seals on floating roof tanks.
RMC-3 Stainless steel brackets used for mounting Protectowire to the rim
seals on floating roof tanks.
Cable Tray Application FastenersCable Tray Clip
Model Description
CC-2N Will clamp to material from .06 to .16 of an inch thick and is
designed to attach to the cable tray side rails and secure the Protectowire in
the recommended sine wave pattern.
CC-2W Will clamp to material ranging from .16 to .25 of an inch thick and
is designed to attach to the cable tray side rails and secure the Protectowire
in the recommended sine wave pattern.
CC-10N-S The CC-10 Series Clips, are particularly useful in applications
where excessive vibration may be encountered. CC-10N-S will clamp to material
from .06 to .16 of an inch thick.
CC-10W-S Are particularly useful in applications where excessive
vibration may be encountered. CC10W-S clamps to material ranging from .16 to
.25 of an inch thick.
Spring Clip
Model Description
HPC-2 The HPC-2 contains gripping teeth that will accommodate mounting
sur faces such as cable trays, storage racks, and ceiling joists.
Pipe Mounting Application Fasteners Pipe Straps
Model Description
PM-3A These double loop straps suitable for 3/4. to 2. pipe are made of
black weather resistant nylon and may be used in temperatures ranging from
–40ºF (-40ºC) to 185ºF (85ºC).
PM-3B These double loop straps suitable for 2.5. to 3.5. pipe are made of
black weather resistant nylon and may be used in temperatures ranging from
–40ºF (–40ºC) to 185ºF (85ºC).
PM -3C These 2 single loop straps suitable for 4. to 6. are made of black
weather resistant nylon and may be used in temperatures ranging from –40ºF
(–40ºC) to 185ºF (85ºC).
Messenger Wire Applications Eyebolt
Model Description
TR-4A Used to attach one end of messenger wire to supporting structure. TR-4A
is steel construction. TR-4A-S Stainless steel construction used to attach and
tension one end of messenger wire to supporting structure.
Turnbuckle
Model Description
TR-24 Used to attach and tension one end of messenger wire supporting
structure.
TR-24-S Stainless steel construction used to attach and tension one end of
messenger wire to supporting structure.
Typical Class B Protectowire installation using FMM-1 Monitor Module: ANY NUMBER OF UL LISTED CONTACT CLOSURE DEVICES MAY BE USED. DO NOT MIX FIRE ALARM INITIATING, SUPERVISORY, OR SECURITY DEVICES ON THE SAME MODULE
Reference
Documention Install, Operation, and Maintenance Manual MAN 2001E-0603
(Found on on www.protectowire.com)