NOTIFIER VXP-25/50 Distributed Audio Voice Transponder Instruction Manual

June 9, 2024
NOTIFIER

October 1, 1998
VXP-25/50
Distributed Audio Voice Transponder
Section: Voice Control Systems
PRELIMINARY

GENERAL

The VXP-25/50 Distributed Audio Voice Transponder is a dual-channel, 25 watt (expandable to four-channel, 50 watt), 25 VRMS, distributed audio, emergency voice evacuation panel which is compatible with existing NOTIFIER voice equipment. The VXP-25/50 can be used to distribute voice evacuation audio over a building’s speaker system. A separate custom power supply module (FC-PSM) with battery charger is included. An optional second audio amplifier (FC- AAM25) is available as a backup to the primary amplifier or to expand speaker power to 50 watts (providing dual, 25-watt speaker circuits). This same 25-watt amplifier can also be used for backup purposes when the panel is configured for 50-watt operation. 70 VRMS conversion modules (FC-XRM70) are also available as options for installations where 70 VRMS speakers are to be installed or already exist. The modular design permits greater installation and servicing ease.
The FC-VTM Voice Transponder Module, supplied with the BE-VXP basic equipment kit, allows connection to a NOTIFIER addressable Fire Alarm Control Panel SLC loop. The five SLC device addresses for the VXP are set using the FC-VTM rotary switch for the “10’s” address and individual slide switch for a “1” or “5” at the “1’s” address. The SLC/FlashScan control points permit VXP activation from a control panel connected to the SLC loop. This module also provides two firefighter-telephone or NAC circuits (requires an APS-6R power supply).
Significant technological enhancements set the VXP apart from other distributed audio voice panels. These enhancements include full supervision in both active alarm and standby conditions. Supervision is provided for: amplifier outputs, field wiring (shorts and opens), optional message generator (FC-MGM), all tone generators.
If the single audio riser input fails, the VXP can be programmed to switch to the optional FC-MGM Message Generator Module or built-in tone generator. If the FC-MGM fails or is not installed, the two tone generators on the main circuit board can be automatically switched in as backups.
Power is fed independently to each amplifier so that a short circuit in one amplifier will not shut down the other. Full output power of 25 watts per amplifier is generated while in a low battery condition. Power is not diminished when the 70 VRMS option is installed. Audio is amplified from modern integrated circuits instead of transformer technology. This provides very low signal distortion for crystal-clear audio.
The VXP is designed to interface directly to the VEC-25/50 Voice Evacuation Control Panel and compatible NOTIFIER voice alarm equipment such as the AMG and ATG.

FEATURES

  • Transformer-isolated single audio riser input (including dual channel).
  • Integral 25 Watt, 25 VRMS audio amplifier with single Class A or Class B speaker circuit.
  • Built-in alert tone generators with steady, slow whoop, high/ low or chime tone capability.
  • Alert tone selection(s) may be field-programmed to conform with ANSI S3.41 Audible Emergency Evacuation Signal (Temporal Pattern), per NFPA.
  • Powered from local 120 VAC (backup batteries required).
  • Integral diagnostic LEDs include: Power, System Trouble, ALARM, Tone Generator Trouble, Amplifier Fault and others.
  • For ease of service and maintenance, plug-in style terminal blocks are utilized for most field-wiring terminations.
  • Auxiliary Form-C trouble relay.
  • Direct interface to AMG, ATG, or VEC-25/50.
  • Fully supervised, including amplifier output, optional message generator, speaker wiring, and tone generators, in Standby and Active states.
  • Independent amplifier supervision: current limit, audio level, short circuit protection.
  • All outputs fully power-limited to meet latest UL requirements.
  • Auxiliary power output.
  • Unique amplifier design features high signal-to-noise ratio.
  • Utilizes Surface Mount Technology.
  • Compatible with most NOTIFIER Addressable Fire Alarm Control Panels.
  • Aesthetically pleasing design has an appearance and layout similar to NOTIFIER’s popular FACPs.

BE-VXP STANDARD MODULES

FC-SCB: Slave Command Board

  • System status LEDs.
  • Audio input.
  • Tone generators.
  • Provides mounting location for all standard and optional modules.
  • System micro-controller.
  • Auxiliary power output.
  • Programming dip switches.

FC-VTM: Voice Transponder Module

  • Houses third FC-AAM25 amplifier when used as backup to primary and secondary amps.
  • Provides five SLC/Flash Scan points (4 control, 1 monitor).
  • Provides dual, 3 Amp NACs, OR… dual firefighter-telephone circuits (switch point only, no jacks), OR… a combination of one NAC and one FFT circuit.
  • Includes slide switches to independently disable SLC points.
  • Provides “10’s” code switch and “1’s” slide switch to set address of first SLC point.
  • Mounts directly to FC-SCB.

FC-AAM25: Audio Amplifier Module

  • 25 Watt, 25 VRMS audio amplifier module.
  • Provides single Class A or Class B speaker circuit.
  • Utilizes plug-in style terminal blocks for ease of service and maintenance.
  • Fully supervised and power-limited.
  • Diagnostic LEDs include: yellow trouble LED (cable fault, 70 VRMS fault, amp fault) and green, amp functional LED.
  • Also available: 1) as an option for system expansion to 50 watts (providing dual 25-watt speaker circuits); or 2) as a backup to the primary 25-watt amplifier, where one-to-one backup is required; or 3) as a backup to either FC-AAM25 in systems configured for 50 watts, in the event that either amp fails.
  • Optional second FC-AAM25 mounts to FC-SCB while third optional amp mounts to FC-VTM.

FC-PSM: Power Supply Module

  • Power supply/battery charger module.
  • Ground fault detection with diagnostic LED (yellow).
  • Brownout detection with battery transfer.
  • Battery trouble detect with diagnostic LED (yellow).
  • Battery saver operation.
  • Independent AC loss relay provides AC loss delay per UL, for independent monitoring by DACT (2 Amps @ 24 VDC).
  • AC power on LED (green).
  • 18 AH battery charging capacity — up to 25 AH may be utilized in CAB-A3 enclosure.
  • Large, teeter-plate terminal blocks easily accept up to 12 AWG (3.25 mm²) for power terminations.
  • Mounts adjacent to FC-SCB.

OPTIONAL MODULES

FC-XRM70: Optional Transformer Module

  • Converts 25 VRMS audio outputs to 70.7 VRMS for retrofit applications.
  • Plugs directly on FC-AAM25 module(s), allowing independent conversion to 70.7 VRMS.

FC-LPS: Optional Local Playback Speaker

  • Provides local digital message playback for user review of field-recorded custom messages.

FC-MGM: Optional Message Generator Module

  • Optional Digital Message Generator for VXP with standard, factory-prerecorded, emergency evacuation message.
  • Message generator includes 60-second capacity, with primary and secondary message capability (30 seconds each).
  • Custom messages are field recordable through PCB mounted microphone or integral RCA-type jack.
  • Digital message may be field-selected for 1, 2, 4, 8 or infinite repeat.

STANDARDS AND CODES

The VXP-25/50 will comply with the following standards:

  • NFPA 72-1996 National Fire Alarm Code
  • NFPA 101-1994 Life Safety Code
  • UL 864 Standard for Control Units for Fire Alarm Systems

SPECIFICATIONS

Primary (AC) Power:

  • 1.0 Amp max. @ 120 VAC, 60 Hz.

Secondary Power (Battery) Charging Circuit:

  • Supports lead acid batteries only.
  • Float charge voltage: 27.6V.
  • Maximum charge current: 800 mA.
  • Maximum battery capacity: 18 AH.

Trouble Contact Rating:

  • 2.0 Amps at 30 VDC (resistive), 0.06 Amps @125 VAC resistive.

Auxiliary Power Output:

  • Specific application power: 35 mA maximum.

CABINET SPECIFICATIONS

Door: 20.13″ (51.13 cm) high x 24.13″ (61.29 cm) wide x 1.25″ (3.175 cm) deep. Backbox: 20.0″ (50.80 cm) high x 24.0″ (60.96 cm) wide x 5.22″ (13.259 cm) deep.

CONTROLS AND INDICATORS

LED INDICATORS:

  • Power On (green).
  • ALARM (red).
  • System Trouble (yellow).
  • Tone Generator Trouble (yellow).
  • Message Generator Trouble (yellow) on FC-MGM option.
  • Record (green) on FC-MGM option.
  • Playback (green) on FC-MGM option.

SWITCH CONTROLS:

  • Record (on FC-MGM option).
  • Playback (on FC-MGM option).

ORDERING INFORMATION

BE-VXP: Basic Equipment Kit, includes: FC-SCB, FC-VTM, FC-AAM25, FC-PSM, FC-CHS (chassis), and installation instructions.
FC-DR-A3: VXP Door only, “A” style, dead-front, one (1) tier.
SBB-A3: Backbox only, “A” style, one (1) tier.
FC-AAM25: Optional 25 Watt, 25 VRMS Audio Amplifier Module with single Class A or Class B speaker circuit (may be used as a backup).
FC-PSM: Replacement 120 VAC, 60 Hz Power Supply/Battery Charger Module (included with BE-VXP).
FC-XRM70: Optional 70.7 VRMS Converter Module (one required per amplifier). Consult factory for availability.
FC-MGM: Optional Digital Message Generator. Consult factory for availability.
FC-VTM: Replacement five-SLC-point Transponder Module.
FC-LPS: Optional Local Playback Speaker.
PS-12120: Battery, 12 volt, 12.0 AH, (two required).
PS-12180: Battery, 12 volt, 18.0 AH, (two required).
PS-12600: Battery, 12 volt, 60.0 AH, (two required).
BB-55: Battery Box, required to mount PS-12250 or PS-12600 batteries (when CHG-120 is installed in CAB-A3).
CHG-120: 25 AH to 120 AH battery charger (required for 60- hour battery- backed systems).
APS-6R: Auxiliary Power Supply, one required to power two NAC outputs on FC-VTM.

This document is not intended to be used for installation purposes. We try to keep our product information up-to-date and accurate. We cannot cover all specific applications or anticipate all requirements. All specifications are subject to change without notice. For more information, contact NOTIFIER. Phone: 203-484-7161 FAX: 203-484-7118

One Fire-Lite Place, Northford, Connecticut 06472
ISO-9001
Engineering and Manufacturing
Quality System Certified to
International Standard ISO-9001
DN-6655 Made in the U.S. A.
firealarmresources.com

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

NOTIFIER User Manuals

Related Manuals