GENERAL

System Sensor’s Sound Choice™ SP100 Series and V400Series Speakers are for voice and tone signaling. The SP100 Series are high quality speakers and speaker/strobe combinations for evacuation signaling designed to meet UL1480 Fire Standard Specifications. For installations requiring a more compact device fitting to a standard 4″ electrical backbox, the V400 Series speakers provide an unobtrusive profile. Both series feature excellent full-range audio response, dual voltages, easy wattage tap selectability, and a three-year warranty.

FEATURES

  • One stock-keeping unit with dual voltages, 25/70.7 VRMS. • Square models (V400 and SP101) for wall mounting and round models (SP100) for ceiling mounting.

  • Variety of power output tabs. SP100: 1/8, 1/4, 1/2, 1, 2, or 4 watts. V400: 1/4, 1/2, 1, or 2 watts.

  • Variable decibel output (dependent on wattage tap) to meet demands of your unique environment.

  • Color options to satisfy aesthetic demands: SP100 in red or white; V400 in red, beige, or white.

  • Vandal-resistant speaker grille.

  • 400 to 4,000 Hz frequency response for full-range audio.

  • V400 Series fits to a standard 4″ electrical box.

  • SP100 Series fits to a standard 4″ electrical box with an additional extension ring.

  • Surface, semiflush, flush, and ceiling mounting options.

  • No tools needed to change power output level.

  • Strobe options: 1.5 or 15.0 candela UL-1638; or UL-1971/
    ADA version in 15, 15/75, 75 or 110 candela.

  • Peak speaker dBA @ 10 feet (3.048 m) reverberant:
    SP100: 90 @ 4 watts. V400: 84 @ 2 watts.

  • UL listed to Standard 1480.

  • Three-year warranty.

  • • Available in combination with System Sensor ADA and LO/M strobe products.

APPLICATIONS

Ideally suited for hotel/motel rooms, lobbies, corridors, conference rooms, offices, hospitals, dorms, condominiums, and other commercial/industrial applications with low ambient sound levels

CONSTRUCTION AND OPERATION

The device has a capacitive input to allow for DC supervision.

NOTE: The strobe is operated as an independent device and requires separate wires from the panel Notification Appliance Circuit (NAC). Select strobe which is compatible with the panel voltage.

This document is not intended to be used for installation purposes. We try to keep our product information up-to-date and accurate. We cannot cover all specific applications or anticipate all requirements. All specifications are subject to change without notice.  Formore information, contact NOTIFIER. Phone: 203-484-7161 FAX: 203-484-7118

ENGINEERING SPECIFICATIONS

Speaker shall be a System Sensor model __ dual-transformer speaker capable of operating at 25 and 70.7 VRMS.
Speaker shall be listed to Underwriter’s Laboratories Standard 1480 for fire protective signaling systems. Speaker shall have a frequency range of 400 to 4,000 Hz and shall havean operating temperature between 32°F and 120°F (0°C and 49°C). Speaker shall have power taps which are selected by means of a jumper wire(s).

For Speaker/Strobe Combination: Speaker/strobe shall be a System Sensor model __ dual-transformerspeaker capable of operating at 25 and 70.7 Vrms. Speaker/ strobe shall be listed to Underwriter’s Laboratories Standard 1480 for fire protective signaling systems. Speaker shall have a frequency range of 400 to 4,000 Hz and shall have an operating temperature between 32°F and 120°F (0°C and 49°C). Speaker shall have power taps which are selected by means of a jumper wire(s). Strobe shall be powered independently of the speaker and shall operate from a 24 VDC or 24 VRMS full-wave rectified unfiltered power supply. Strobe shall havea light output rating of 1.5, 15, 75, or 110 candela, and shall be UL 1638 or 1971 listed as a primary signaling device.

ISO-9001

Engineering and Manufacturing Quality System Certified to International Standard ISO-9001

POWER TAP SELECTION AND SOUND OUTPUT

| SP 100 | V400
---|---|---
4Watts| 2Watts| 1Watt| 1l2 Watt| 1l4 Watt| 1l8 Watt| 2Watts| 1Watt| 1l2 Watt| 1l4 Watt
Jumper Wire, 25 V:
| 1 B| 1 A| 2 B| 2 A| 3 B| 4 B| —| —| —| —
Jumper Wire, 70.7 V:*| 2 A| 3 B| 4 B| 5 B| 6 B| 6 A| —| —| —| —
UL Reverberant (dBA @ 10 ft. [3.048 m]):| 90| 87| 84| 81| 78| 75| 84| 81| 78| 75
Anechoic (dBA @ 10 ft. [3.048 m]):| 93| 90| 87| 84| 81| 78| 87| 84| 81| 78

*EXAMPLE: To select 1/4 watt output @ 25 V, connect Blue lead to post #3, and  ellow to post B. For further information, consult System Sensor installation instructions for this product.

SP100 SERIES SPEAKER/STROBE POWER REQUIREMENTS

| SP1W2415ADA SP1R2415ADA| SP1W241575ADA SP1R241575ADA| SP1W2475ADA SP1R2475ADA| SP1W24110ADA SP1R24110ADA
---|---|---|---|---
Supply voltage:| 20 to 30 VDC| 20 to 30 VDC| 20 to 30 VDC| 20 to 30 VDC
Maximum current @ listed voltage:| 75 mA| 93 mA| 170 mA| 210 mA
Operating current @ rectified unfiltered voltage:| 90 mA| 120 mA| 200 mA| 245 mA
Rated light output:| 15.0 candela| 15/75 candela| 75.0 candela| 110.0 candela

V400 Semiflush Mounting Diagram

Mounting Diagram

V400 Power Tap Selection

Power Tap Selection

SP100 Mounting Diagram
Mounting Diagram

SP100 SERIES SPECIFICATIONS

  • Input terminals: 12 AWG (3.25 mm²) to 18 AWG (0.75 mm²).
  • Grille size/color: Round: 7-3/8″ (187.325 mm) in white.
  • Square: 5″ (127.0 mm) in red or white (color availability varies with models, see Ordering Information chart below).
  • Weight: 1.6 lb. (725.75 g).
  • Mounting: 4″ (101.6 mm) x 4″ (101.6 mm) x 2-1/8″ (53.975 mm) backbox with 4″ (101.6 mm) x 4″ (101.6 mm) x 1-1/2″ (38.1 mm) extension ring.
  • Filler plugs: included.
  • Operating temperature range: 32°F to 120°F (0°C to 49°C).
  • Input voltage: 25 volts or 70.7 volts (nominal).
  • Frequency range: 400 to 4,000 Hz.
    Although the SP100 Series speaker/strobe combination is
    sold as a unit, the speaker and strobe are electrically independent and require separate power sources. See chart on page 2 for strobe operating requirements.

V400 SERIES SPECIFICATIONS

  • Input terminals: 14 AWG (2.0 mm²) to 18 AWG (0.75 mm²).
  • Grille size/color: Square: 4″ (101.6 mm) in red, beige, or white (color availability varies with models, see Ordering Information chart below).
  • Weight: 0.7 lb. (317.51 g).
  • MOUNTING (order mounting plates separately, see Ordering Information below): Semiflush: 4″ (101.6 mm) x 4″ (101.6 mm) x 1-1/2″ (38.1 mm) to 2-1/8″ (53.975 mm) standard backbox. For 12 AWG (3.25 mm²) or 14 AWG (2.0 mm²) wire, a 2-1/8″ (53.975 mm) deep backbox is recommended.
  • Flush: 2-3/4″ (69.85 mm) deep backbox (BB-D) with flush mounting plate.
  • Filler plugs: N/A.
  • Operating temperature range: 32°F to 120°F (0°C to 49°C).
  • Input voltage: 25 volts or 70.7 volts (nominal).
  • Frequency range: 400 to 4,000 Hz.

ORDERING INFORMATION

RED (R) MODELS| BEIGE & WHITE MODELS (B, W)| DESCRIPTION| SPEAKER VOLTAGE| STROBE VOLTAGE| CANDELA
---|---|---|---|---|---
SP100 Series Speakers
—| SP100W| Round, 7-3l8″ grille, 1l8 – 4 watt power taps.| 25l70.7 VRMS| —| —
SP101R| SP101W| Square, 5″ grille, 1l8 – 4 watt power taps.| 25l70.7 VRMS| —| —
SP1R2415ADA| SP1W2415ADA| Square, 5″ grille, 1l8 – 4 watt power taps.| 25l70.7 VRMS| 24 VDC| 15.0 cd
SP1R241575ADA| SP1W241575ADA| Square, 5″ grille, 1l8 – 4 watt power taps, wall strobe, UL-1971.| 25l70.7 VRMS| 24 VDC| 15l75 cd
SP1R2475ADA| SP1W2475ADA| Square, 5″ grille, 1l8 – 4 watt power taps, wall strobe, UL-1971.| 25l70.7 VRMS| 24 VDC| 75 cd
SP1R24110ADA| SP1W24110ADA| Square, 5″ grille, 1l8 – 4 watt power taps, wall strobe, UL-1971.| 25l70.7 VRMS| 24 VDC| 110 cd
V400 Series Speakers
V400R| V400B, V400W| Square, 4″ grille, 1l4 – 2 watt power taps.| 25l70.7 VRMS| —| —
V4R2415ADA| —| Square, 4″ grille, 1l4 – 2 watt power taps, wall strobe, UL-1971.| 25l70.7 VRMS| 24 VDC| 15.0 cd
V4R241575ADA| —| Square, 4″ grille, 1l4 – 2 watt power taps, wall strobe, UL-1971.| 25l70.7 VRMS| 24 VDC| 15l75 cd
V4R2475ADA| —| Square, 4″ grille, 1l4 – 2 watt power taps, wall strobe, UL-1971.| 25l70.7 VRMS| 24 VDC| 75 cd
V4R24110ADA| —| Square, 4″ grille, 1l4 – 2 watt power taps, wall strobe, UL-1971.| 25l70.7 VRMS| 24 VDC| 110 cd
MP-FlR| MP-FlB| Flush mounting plate.| —| —| —
BB-D| —| Flush-mounting deep (2-3l4″l69.85 mm) backbox.| —| —| —
MP-SFlR| MP-SFlB| Semi-flush mounting plate.| —| —| —
**Strobe Attachments for V400**
SS12LO| —| Signal strobe, red only.| —| 12 VDC| 1.5 cd
SS24LO| SS24LOB| Signal strobe.| —| 24 VDC| 1.5 cd
SS24LOC| —| Ceiling-mount signal strobe, red only.| —| 24 VDC| 1.5 cd
SS24M| —| Signal strobe, red only.| —| 24 VDC| 15.0 cd
SS24MC| —| Ceiling-mount signal strobe, red only.| —| 24 VDC| 15.0 cd
Although the SSLO and SSM Series signal strobes are UL listed as primary signaling devices, when combined with the V400 speaker, they are considered as a secondary signaling device only.

firealarmresources.com