Surge Suppression

There are three (3) primary surge protectors that are approved for use with the FACP’s noted.

  • DTK-2LVLP-F Diversified Technology Group, Inc. 1720 Starkey Rd. Largo, FL 33771 727-812-5000
  • SLCP-030 EDCO 1805 N.E. 19th Ave. Ocala, FL 34470 352-732-3029
  • PLP-42N Northern Technologies, Inc. 23123 E. Madison Ave. Liberty Laic, WA 99019 800-727-9119

Note: For detailed information referto the installation documentation that was supplied with the unit.

One primary surge protector must be used with each SLC wiring pair whenever SLC wiring runs outside the building.

  • Install primary protection only as shown in this document.
  • Refer to NEC Article 800 and local building code requirements.

Additional primary surge suppressors maybe added as required by the NEC. Add these additional suppressors in series with the SLC wiring at the building entry/exit.

Wiring connected to the surge suppressor output must remain within the building while wiring connected to the surge suppressor input may be routed outside the building as shown below.
Surge Suppression

Unit Installation

Mounting is inside the FACP enclosure or in a separate enclosure listed for fire protective signalling use.

  • Locate on an available stud and secure with nut.
  • Unit is connected in series with the SLC Loop to protect the Control Panel.
  • Provide a common ground to eliminate the possibility of a differential in ground potentials.

AFP-100 & AFP-200
DTK-2LVLP-F Connections

Connections

PLP-42N Connections
Connections

Note: Use 12AGWto 18AGWwhe with crimp-on connectors to connect the unit’s ground temiinalto equipment ground. Wire la ngth must be minimized to provide test protection.

SLCP-030 Connections
Connections

AFP-300 & AFP-400
DTK-2LVLP-F Connections
Connections
PLP-42N Connections
Connections
Note: Use 12AGWto 18AGWwhe with crimp-on connectors to connect the unit’s ground terminalto equipment ground. Wire length must be minimized to provide test protecion

SLCP-030 Connections
Connections

Document 51246:A 08/9/99