NOTIFIER NP-200 Series Photoelectric Smoke Detectors for FireWarden Owner’s Manual
- June 9, 2024
- NOTIFIER
Table of Contents
NOTIFIER NP-200 Series Photoelectric Smoke Detectors for FireWarden
INTRODUCTION
The NOTIFIER® NP-200 Series intelligent plug-in smoke detectors are designed for both performance and aesthetics and are direct replacements for the NP-100 Series. A new modern, sleek, contemporary design and enhanced optical sensing chamber is engineered to sense smoke produced by a wide range of combustion sources in accordance with more stringent code standards. Exclusively for use with NOTIFIER’s FireWarden Series addressable fire alarm control panels, the NP-200 Series point ID capability allows each detector’s address to be set with rotary, decimal address switches, providing exact detector location for emergency personnel to quickly locate a fire during its early stages, potentially saving precious rescue time while also reducing property damage. Two LEDs on each sensor light to provide a local, visible sensor indication. The NP-200 Series also offers 135°F (57°C) fixed temperature thermal sensing on the NP-200T and a remote test capable detector on the NP-200R for use with DNR(A)/DNRW duct smoke detector housings.
Features
SLC LOOP:
- Two-wire SLC loop connection
- Unit uses base for wiring
- Compatible with FlashScan® and CLIP protocol systems
- Stable communication technique with noise immunity
ADDRESSING:
- Addressable by device
- Rotary, decimal addressing (Refer to the FireWarden panel manuals for device capacity.)
ARCHITECTURE:
- Sleek, low-profile, stylish design
- Unique single-source design to respond quickly and dependably to a broad range of fires
- Integral communications and built-in device-type identification
- Built-in tamper-resistant feature
- Remote test feature from the panel
- Walk test with address display (an address on 121 will blink the detector LED: 12-[pause]-1(FlashScan systems only)
- Built-in functional test switch activated by an external magnet
- Removable cover and insect-resistant screen for simple field cleaning
- Expanded color options
OPERATION:
- Designed to meet UL 268 7th Edition
- Factory preset at 1.5% nominal sensitivity for panel alarm threshold level
- LED “blinks” when the unit is polled (communicating with the fire panel) and latches in alarm.
- Low standby current
MECHANICALS:
- Sealed against back pressure
- SEMS screws for wiring of the separate base
- Designed for direct-surface or electrical box mounting
- Plugs into a separate base for ease of installation and maintenance
- A separate base allows the interchange of photoelectric, ionization and thermal sensors
OPTIONS:
- Optional relay, isolator, and sounder bases
Installation
NP-200 Series plug-in intelligent smoke detectors use a detachable base to
simplify installation, service and maintenance. Installation instructions are
shipped with each detector. Mount detector base (all base types) on an
electrical backbox that is at least 1.5″ (3.81 cm) deep. For a chart of
compatible junction boxes, see DN-60054.
NOTE: Because of the inherent supervision provided by the SLC loop, end-
of-line resistors are not required. Wiring “T-taps” or branches are permitted
for Style 4 (Class “B”) wiring only. When using relay or sounder bases,
consult the N100-ISO installation sheet I56-3625 for device limitations
between isolator modules and isolator bases.
Construction
These detectors are constructed of fire-resistant plastic. The NP-200 Series
plug-in intelligent smoke detectors are designed to commercial standards and
offer an attractive appearance.
Operation
Each NP-200 Series detector uses one of the panel’s addresses (total limit is panel dependent) on the FireWarden Signaling Line Circuit (SLC). It responds to regular polls from the control panel and reports its type and status. If it receives a test command from the panel (or a local magnet test), it stimulates its electronics and reports an alarm. It blinks its LEDs when polled and turns the LEDs on when commanded by the panel. The NP-200 Series offers features and performance that represent the latest in smoke detector technology.
Detector Sensitivity Test
Each detector can have its sensitivity tested (required per NFPA 72, Chapter
14 on Inspection, Testing and Maintenance) when installed/ connected to a
FireWarden Series addressable fire alarm control panel. The results of the
sensitivity test can be printed for record keeping.
Product Line Information
NOTE: “-IV” suffix indicates CLIP and FlashScan device.
- NP-200: White, low-profile intelligent photoelectric sensor, FlashScan only
- NP-200-IV: Ivory, low-profile intelligent photoelectric sensor
- NP-200T: White, same as but includes a built-in 135°F (57°C) fixedtemperature thermal device, FlashScan only
- NP-200T-IV: Ivory, same as T but includes a built-in 135°F (57°C) fixed-temperature thermal device
- NP-200R: White, low-profile intelligent photoelectric sensor, remote test capable, for use with DNR/DNRW, FlashScan only
- NP-200R-IV: Ivory, low-profile intelligent photoelectric sensor, remote test capable, for use with DNR/DNRW
INTELLIGENT BASES
NOTE: For details on intelligent bases, see DN-60981.
- B300-6: White, 6” base, standard flanged low-profile mounting base (CSFM: 7300-1653:0109)
- B300-6-IV: Ivory,6” base, standard flanged low-profile mounting base (CSFM: 7300-1653:0109)
- B300-6-BP: Bulk pack of B300-6, package contains 10
- B501-WHITE: White, 4” standard European flangeless mounting base. UL/ULC listed (CSFM: 7300-1653:0109)
- B501-BL: Black, 4” standard European flangeless mounting base. UL/ULC listed (CSFM: 7300-1653:0109)
- B501-IV: Ivory color, 4” standard European flangeless mounting base. UL/ULC listed (CSFM: 7300-1653:0109)
- B501-WHITE-BP: Bulk pack of B501-WHITE contains 10
- B224RB-WH: White, relay base (CSFM: 7300-1653:0216)
- B224RB-IV: Ivory, relay base (CSFM: 7300-1653:0216)
- B224BI-WH: White, isolator detector base (CSFM: 7300-1653:0216)
- B224BI-IV: Ivory isolator detector base (CSFM: 7300-1653:0216)
- B200S-WH: White, Intelligent addressable sounder base capable of producing sound output in high or low volume with ANSI Temporal 3, ANSI Temporal 4, continuous tone, marching tone, and custom tone. Uses FlashScan protocol. (CSFM: 7300-1653:0213)
- B200S-IV: Ivory, Intelligent addressable sounder base capable of producing sound output in high or low volume with ANSI Temporal 3, ANSI Temporal 4, continuous tone, marching tone, and custom tone. Uses FlashScan protocol. (CSFM: 7300-1653:0213)
- B200S-LF-WH: White, Low-Frequency Intelligent, programmable sounder base. Produces a fundamental frequency of 520 Hz +/- 10% with a square wave or its equivalent; designed to meet the NFPA 72 sleeping space requirement. (CSFM: 7300-1653:0238)
- B200S-LF-IV: Ivory, Low-Frequency Intelligent, programmable sounder base. Produces a fundamental frequency of 520 Hz +/- 10% with a square wave or its equivalent; designed to meet the NFPA 72 sleeping space requirement. (CSFM: 7300-1653:0238)
- B200SR-WH: White, Intelligent sounder base capable of producing sound output with ANSI Temporal 3 or continuous tone. Intended for retrofit applications. (CSFM: 7300-1653:0213)
- B200SR-IV: Ivory, Intelligent sounder base capable of producing sound output with ANSI Temporal 3 or continuous tone. Intended for retrofit applications. (CSFM: 7300-1653:0213)
- B200SR-LF-WH: White, Low-Frequency Intelligent, programmable sounder base. Produces a fundamental frequency of 520 Hz +/- 10% with a square wave or its equivalent; designed to meet the NFPA 72 sleeping space requirement. Intended for retrofit applications. (CSFM: 7300-1653:0238)
- B200SR-LF-IV: Ivory, Low-Frequency Intelligent, programmable sounder base. Produces a fundamental frequency of 520 Hz +/- 10% with a square wave or its equivalent; designed to meet the NFPA 72 sleeping space requirement. Intended for retrofit applications. (CSFM: 7300-1653:0238)
MOUNTING KITS AND ACCESSORIES
- TR300: White, replacement flange for B210LP(A) base
- TR300-IV: Ivory, replacement flange for B210LP(A) base
- RA100Z(A): Remote LED annunciator. 3-32 VDC. Mounts to a U.S. single-gang electrical box. For use with B501(A) and B300-6(A).
- M02-04-00: Test magnet
- M02-09-00: Test magnet with telescoping handle
- CK300: Color Kit (includes cover and trim ring), white, 10-pack
- CK300-IV: Color Kit (includes cover and trim ring), ivory, 10-pack
- CK300-BL: Color Kit (includes cover and trim ring), black, 10-pack
SPECIFICATIONS
-
Sensitivity:
- UL Applications: 0.5% to 4.0% per foot obscuration.
- ULC Applications: 0.5% to 3.5% per foot obscuration
-
Size: 2.0″ (5.3 cm) high; base determines diameter
- B300-6: 6.1″ (15.6 cm) diameter
- B501: 4″ (10.2 cm) diameter
For a complete list of detector bases see DN-60981
-
Shipping weight: 3.4 oz. (95 g)
-
Operating temperature range:
- NP-200: 32°F to 122°F (0°C to 50°C)
- NP-200T Series: 32°F to 100°F(0°C to 38°C)
- NP-200R Series: installed in a DNR/DNRW, -4°F to 158°F (-20°C to 70°C)
-
UL/ULC Listed Velocity Range: 0-4000 ft/min. (1219.2 m/min.), suitable for installation in ducts
-
Relative humidity: 10% – 93% non-condensing
-
Thermal ratings: fixed-temperature set point 135°F (57°C), rate-ofrise detection 15°F (8.3°C) per minute, high temperature heat 190°F (88°C)
ELECTRICAL SPECIFICATIONS
- Voltage range: 15 – 32 volts DC peak
- Standby current (max. avg.): 200μA @ 24 VDC (one communication every 5 seconds with LED enabled)
- Max current: 4.5 mA @ 24 VDC (“ON”)
DETECTOR SPACING AND APPLICATIONS
NOTIFIER recommends spacing detectors in compliance with NFPA 72. In low
airflow applications with smooth ceiling, space detectors 30 feet (9.1m). For
specific information regarding detector spacing, placement, and special
applications refer to NFPA 72. A System Smoke Detector Application Guide,
document A05-1003, is available at
www.systemsensor.com.
Listings and Approvals
Listings and approvals below apply to the NP-200 Series detectors. In some
cases, certain modules may not be listed by certain approval agencies, or
listing may be in process. Consult factory for latest listing status.
- UL/ULC Listing: S1115
- FM Approved
- CSFM: 7272-0028:0503
This document is not intended to be used for installation purposes. We try to
keep our product information up-to-date and accurate. We cannot cover all
specific applications or anticipate all requirements. All specifications are
subject to change without notice.
FireWarden®, FlashScan®, NOTIFIER®, and System Sensor® have registered
trademarks of Honeywell International, Inc. ©2019by Honeywell International
Inc. All rights reserved. The unauthorized use of this document is strictly
prohibited.
NOTIFIER
12 Clintonville Road
Northford, CT 06472
203.484.7161
www.notifier.com
References
- Fire Alarm Resources | Download fire alarm documents
- Home (USA) | NOTIFIER by Honeywell | Engineered Fire Alarm System.
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>