Honeywell WFDN Series Waterflow Detector Instruction Manual
- June 9, 2024
- Honeywell
Table of Contents
Honeywell WFDN Series Waterflow Detector
GENERAL
WFDN SERIES
The WFDN Series Waterflow Detectors are compatible with Schedule 7 through 40
steel pipe, sizes 2″ through 4″ (50.8 mm through 101.6 mm), and are compatible
with Schedule 10 through 40 steel pipes, sizes 5” through 8” (127 mm through
203.2 mm). They can be mounted in a vertical or horizontal position. WFDN
Series detectors are contained in a rugged, NEMA 4-rated enclosure. Designed
for both indoor and outdoor use, the WFDN Series operates across a wide
temperature range: 32°F to 150°F (0°C to 66°C). UL-Listed models are equipped
with tamper-resistant cover switch to prevent unauthorized entry. Inside, two
sets of SPDT (Form-C) synchronized switches are enclosed in a durable terminal
block with a new layout designed to make wiring easy with wire ready
terminals. COM terminals are on a different elevation. There is a large
barrier between switches and raised textured lettering make it easy to read.
An optional cover tam-per switch is available which securely snaps into place,
no tools required.
WFDN Series detectors incorporate a mechanical time delay feature, which
minimizes the risk of false alarm due to pres-sure surges or air trapped in
the sprinkler system. The larger and easy to turn timer dial makes setting the
waterflow detec-tor easy. The WFDN Series is designed for accuracy and
repeatability. The detector also offers improved performance during vibration
in riser applications where detectors are exposed to a large rush of water.
FEATURES
- New directional cover allows installers and inspectors to easily see the direction of flow.
- UL-Listed models are NEMA 4 rated.
- Sealed retard mechanism immune to dust and other con-taminants
- Less exposed metal reduces shock hazard. Plastic cover acts as an insulator and is resistant to arcing.
- Visual switch activation
- Audible switch activation (73 dBA).
- Field-replaceable timer/switch assembly.
- Accommodates up to 12 AWG wire.
- Switch synchronization activates both alarm panel and local bell or horn strobe.
- Tamper-resistant cover screws.
- Improved water sealing.
- Reduced product weight.
- Wire-ready terminals.
- Improved wiring with new terminal block layout.
- Snap-in optional cover tamper switch.
- Improved timer repeatability and accuracy.
SPECIFICATIONS
WFDN SERIES
Static Pressure Rating: 450 PSI.
Triggering Threshold Bandwidth (flow rate): 4 to 10 GPM.
Maximum Surge: 18 feet per second (FPS) (5.4864 m/sec).
Compatible Pipe: steel water pipe, 2” – 4” (50.8 mm through 101.6 mm) rated for use with Schedule 7 through 40 pipe, 5” -8” (127 mm through 203.2 mm) rated for use with Schedule 10 through 40 pipe.
Contact Ratings: two sets of SPDT (Form-C) contacts; 10.0 A @ 1/2 HP @125/250 VAC; 2.5 A @ 6/12/24 VDC.
Conduit Entrances: two openings for 0.5″ (12.7 mm) con-duit. One open, one knock-out type. NEMA 4 rated plugs
Operating Temperature Range: 32°F to 150°F (0°C to 66°C).
Enclosure Rating: NEMA 4, suitable for indoor/outdoor use.
Cover Tamper Switch: standard for ULC models; optional for UL models (P/N CTS).
Service Use: NFPA 13 for Automatic Sprinkler; NFPA 13D for One- or Two- Family Dwelling; NFPA 13R for Residential Occu-pancies up to Four Stories; NFPA 72 for National Fire Alarm Code.
Warranty: 3 years.
ENGINEERING SPECIFICATIONS
WFDN SERIES
Vane-type waterflow detectors shall be installed on system piping as
designated on the drawing and/or as specified herein. Detectors shall mount on
any clear pipe span of the appropriate nominal size, either a vertical upflow
or horizontal run, at least 6″ (152.4 mm) from any fittings which may change
water direction, flow rate, or pipe diameter; or no closer than 24″ (0.6096 m)
from a valve or drain. Detectors shall have a sensitivity in the range of 4 to
10 gallons per minute and a static pressure rating of 450 psi for 2″ (50.8 mm)
to 8″ (203.2 mm) pipes. The detector shall respond to waterflow in the
specified direction after a preset time delay which is field-adjustable. The
delay mechanism shall be a sealed mechanical pneumatic unit with visual
indication of actuation. The actu-ation mechanism shall include a polyethylene
vane inserted through a hole in the pipe and connected by a mechanical link-
age to the delay mechanism. Outputs shall consist of dual SPDT switches
(Form-C contacts). Two conduit entrances for standard fittings of commonly
used electrical conduit shall be provided on the detectors. A grounding
provision is provided. Unless noted, enclosures shall be NEMA 4 Listed by
Under-writers Laboratories Inc. All detectors shall be Listed by Underwriters
Laboratories Inc. for indoor or outdoor use.
Agency Listings and Approvals
These listings and approvals apply to the modules specified in this document.
In some cases, certain modules or applications may not be listed by certain
approval agencies, or listing may be in process. Consult factory for latest
listing status.
- UL Listed: S739
- ULC Listed: S739
- MEA Listed: 167-93-E
- CSFM: 7770-1653:114
- FM Approved
Ordering Information
WFDN Series Detectors
UL Models| ULC Models| Pipe Size| Hole Size| Shipping
Weight
WFD20N| WFD20NA| 2.0” (50.8 mm)| 1.25” (31.75 mm)| 2.6 lbs
WFD25N| WFD25NA| 2.5” (63.5 mm)| 1.25” (31.75 mm)| 2.6 lbs
WFD30N| WFD30NA| 3.0” (76.2 mm)| 2.00” (50.8 mm)| 3.1 lbs
WFD40N| WFD40NA| 4.0” (101.6 mm)| 2.00” (50.8 mm)| 4.0 lbs
WFD50N| WFD50NA| 5.0” (127 mm)| 2.00” (50.8 mm)| 4.9 lbs
WFD60N| WFD60NA| 6.0” (152.4 mm)| 2.00” (50.8 mm)| 5.6 lbs
WFD80N| WFD80NA| 8.0” (203.2 mm)| 2.00” (50.8 mm)| 7.3 lbs
Accessories and Replacement Parts
Model Number| Description
WFDW| Tamper-proof wrench for metal cover
CTS| Tamper-proof switch kit
FS-RT| Delay mechanism and switch assembly
WFDN Field Wiring Diagram Overall Dimensions Installed
Spears® is a registered trademark of Spears Manufacturing Company. Victaulic®
is a registered trademark of Victaulic Company of America.
©2007 by Honeywell International Inc. All rights reserved. Unauthorized use of
this document is strictly prohibited.
This document is not intended to be used for installation purposes. We try to
keep our product information up-to-date and accurate. We cannot cover all
specific applications or anticipate all requirements. All specifications are
subject to change without notice.
For more information, contact Notifier.