NOTIFIER AFM-16AT Annunciator Fixed Module Instruction Manual
- June 9, 2024
- NOTIFIER
Table of Contents
A Pittway Company
Installation Manual for the
AFM-16AT and AFM-32A
Annunciator Modules
THE ANNUNCIATOR FIXED MODULE
AFM-16AT Annunciator Fixed Module
Document 15048
07/16/97 Revision: D1
ECN 97-294
Installation Precautions
WARNING – Several different sources of power can be connected to the fire
alarm control panel. Disconnect all sources of power before servicing. Control
unit and associated equipment may be damaged by removing and/ or inserting
cards, modules, or interconnecting cables while the unit is energized. Do not
attempt to install, service, or operate this unit until this manual is read
and understood.
CAUTION – System Reacceptance Test after Software Changes: To ensure
proper system operation, this product must be tested in accordance with NFPA
72-1993 Chapter 7 after any programming operation or change in site-specific
software. Reacceptance testing is required after any change, addition or
deletion of system components, or after any modification, repair or adjustment
to system hardware or wiring.
All components, circuits, system operations, or software functions known to be
affected by a change must be 100% tested. In addition, to ensure that other
operations are not inadvertently affected, at least 10% of initiating devices
that are not directly affected by the change, up to a maximum of 50 devices,
must be tested and proper system operation verified.
This system meets NFPA requirements for operation at 0-49º C/32-120 ºF and at
a relative humidity of 85% RH (non-condensing) at 30º C/86 ºF. However, the
useful life of the system’s standby batteries and the electronic components
may be adversely affected by extreme temperature ranges and humidity.
Therefore, it is recommended that this system and its peripherals be installed
in an environment with a nominal room temperature of 1527º C/60-80º F.
Verify that wire sizes are adequate for all initiating and indicating
device loops. Most devices cannot tolerate more than a 10% I.R. drop from the
specified device voltage.
Adherence to the following will aid in problem-free installation with long-
term reliability:
Like all solid state electronic devices, this system may operate
erratically or can be damaged when subjected to lightning induced transients.
Although no system is completely immune from lightning transients and
interferences, proper grounding will reduce susceptibility. Overhead or
outside aerial wiring is not recommended, due to an increased susceptibility
to nearby lightning strikes. Consult with the Technical Services Department if
any problems are anticipated or encountered.
Disconnect AC power and batterie s prior to removing or inserting circuit
boards. Failure to do so can damage circuits.
Remove all electronic assemblies prior to any drilling, filing, reaming, or
punching of the enclosure. When possible, make all cable entries from the
sides or rear. Before making modifications, verify that they will not
interfere with battery, transformer, and printed circuit board location.
Do not tighten screw terminals more than 9 in-lbs. Over tightening may
damage threads, resulting in reduced terminal contact pressure and difficulty
with screw terminal removal.
This system contains static-sensitive components. Always ground yourself
with a proper wrist strap before handling any circuits so that static charges
are removed from the body. Use static suppressive packaging to protect
electronic assemblies removed from the unit.
Follow the instructions in the installation, operating, and programming
manuals. These instructions must be followed to avoid damage to the control
panel and associated equipment. FACP operation and reliability depend upon
proper installation.
Fire Alarm System Limitations
An automatic fire alarm system – typically made up of smoke detectors, heat
detectors, manual pull stations, audible warning devices, and a fire alarm
control with remote notification capability can provide early warning of a
developing fire. Such a system, however, does not assure protection against
property damage or loss of life resulting from a fire.
Any fire alarm system may fail for a variety of reasons:
Smoke detectors may not sense fire where smoke cannot reach the detectors
such as in chimneys, in walls, or roofs, or on the other side of closed doors.
Smoke detectors also may not sense a fire on another level or floor of a
building. A second floor detector, for example, may not sense a first floor or
basement fire. Furthermore, all types of smoke detectors – both ionization and
photoelectric types, have sensing limitations. No type of smoke detector can
sense every kind of fire caused by carelessness and safety hazards like
smoking in bed, violent explosions, escaping gas, improper storage of
flammable materials, overloaded electrical circuits, children playing with
matches, or arson.
IMPORTANT! Smoke detectors must be installed in the same room as the
control panel and in rooms used by the system for the connection of alarm
transmission wiring, communications, signaling, and/or power. If detectors are
not so located, a developing fire may damage the alarm system, crippling its
ability to report a fire.
While installing a fire alarm system may make lower insurance rates possible,
it is not a substitute for fire insurance!
Audible warning devices such as bells may not alert people if these
devices are located on the other side of closed or partly open doors or are
located on another floor of a building.
A fire alarm system will not operate without any electrical power. If AC
power fails, the system will operate from standby batteries only for a
specified time.
Rate-of-Rise heat detectors may be subject to reduced sensitivity over
time. For this reason, the rate-of-rise feature of each detector should be
tested at least once per year by a qualified fire protection specialist.
Equipment used in the system may not be technically compatible with the
control. It is essential to use only equipment listed for service with your
control panel.
Telephone lines needed to transmit alarm signals from a premise to a
central monitoring station may be out of service or temporarily disabled.
The most common cause of fire alarm malfunctions, however, is inadequate
maintenance. All devices and system wiring should be tested and maintained by
professional fire alarm installers following written procedures supplied with
each device. System inspection and testing should be scheduled monthly or as
required by National and/or local fire codes. Adequate written records of all
inspections should be kept.
Section One: The AFM
Annunciator Fixed Modules provide the control panel with discrete display and
control points. These annunciators turn their LEDs ON and OFF as commanded by
the system’s CPU. In addition, they report selected switch activations to the
CPU for action.
Limits
The AFM-16AT is intended for use in systems that require 16 annunciation
points or less.
The AFM-32A is intended for use in systems that require 32 annunciation points
(alarm only) or less. Only one annunciator may be used in a system. Each
annunciator’s address is internally fixed at “1.”
Capabilities
The AFM-16AT can annunciate the following:
Circuits: IZ-4, IZ-8 and IZM-8 Initiating Device Circuits (alarm and
trouble)
AIM-200 Software Zones (alarm and trouble)
IC-4, ICM-4 and ICE-4 Notification Appliance Circuits (trouble)
CR-4, CRM-4 and CRE-4 Control Relays (trouble)
TC-2, TC-4, TCM-2, and TCM-4 circuits (trouble)
CPU Controls: Acknowledge, Signal-Silence and System Reset. If desired,
the Alarm Relay, Indicating Circuits 1 and 2, and the Remote Station Municipal
Tie may be controlled from the AFM-16AT.
The AFM-32A can annunciate the following:
Circuits: IZ-4, IZ-8 and IZM-8 Initiating Device Circuits (alarm and trouble)
AIM-200 Software Zones (alarm and trouble)
CPU Controls: System Alarm, and the activation of Indicating Circuits 1 and 2,
the Remote Station Municipal Tie and the Alarm Relay.
Controls: Local Silence/Acknowledge and Lamp Test.
Software Required
The AFM is fully compatible with the System 500 (CPU–500). To operate the AFM
with a System 5000 FACP, the CPU-5000 must be operating under software with
ROM U4 software numbered 73085 or greater.
Electrical Ratings
Input Voltage: 24 volts DC (must be power-limited).
Current Draw from 24 volt DC Input: 0.040 Amps in Standby; 0.056 Amps in Alarm
Data Communications Port: EIA-485 operating at 20.833 Kbaud (must be power-
limited).
Wiring
Communication between the control panel and the AFM is accomplished over a
two-wire power-limited EIA-485 serial interface (formerly referred to as
RS-485). This communication, to include the wiring, is supervised by the
control panel’s CPU. Loss of communication results in “System Trouble” and
“Module Failure” indications at the CPU. Power for the AFM must be power-
limited and is provided via a separate power loop from the control panel which
is inherently supervised (loss of power also results in a communication
failure at the control panel). No End-Of-Line Resistor needs to be installed
because the EIA-485 circuit is internally terminated on the annunciator.
Wiring Specifications
The EIA-485 circuit cannot be T-Tapped; it must be wired in a continuous
fashion from the control panel to the AFM. The maximum wiring distance between
the panel and annunciator is 6000 feet. The wiring size should be a 18 AWG to
14 AWG twisted-pair cable having a Characteristic Impedance of approximately
120 ohms. Limit the total wire resistance to 100 ohms on the EIA-485 circuit,
and to 10 ohms on the power run to the annunciator. Do not run cable adjacent
to, or in the same conduit as, 120 volts AC service, noisy electrical circuits
that are powering mechanical bells or horns, audio circuits above 25 volts
RMS , motor control circuits, or SCR power circuits.
Twisted-shielded wiring should be used for EIA-485 circuits that are not
contained entirely in conduit.
Functions
The fire alarm control panel automatically assigns annunciator points to the
modules directly to the right of the CPU and outward. Therefore, when
installing the system modules, Initiating Zone Modules (IZ-4, IZ-8, or IZM-8)
should be installed in ribbon cable positions immediately next to the CPU (and
outward) to permit full annunciation of initiating circuits.
Section Two: Inventory
AFM-16AT
(H = 8-3/8″ W = 4-3/8″ D = 1-3/8″)
The Annunciator Fixed Module-16AT contains 16 red alarm and 16 yellow trouble
LEDs, 16 momentary touch-pad switches, a system trouble LED, an ON LINE/POWER
LED, and a local piezo sounder with a silence/acknowledge switch for audible
indication of alarm and trouble conditions. The AFM-16AT can be mounted in two
types of backboxes – the ABS-1 or ABF-1.
AFM-32A
(H = 8-3/8″ W = 4-3/8″ D = 1-3/8″)
The Annunciator Fixed Module-32A contains 32 red alarm LEDs, a System Trouble
LED, an ON LINE/POWER LED, and a piezo sounder with a Local Silence/
Acknowledge switch for audible indication of alarm and trouble conditions. The
AFM-32A can be mounted in two types of backboxes – the ABS-1 or
ABF-1.
ABF-1
(H = 9-15/16″ W = 4-5/8″ D = 2-1/2″)
The Annunciator Flush Box-1 provides for the remote mounting of the AFM
annunciator in a flush-mount enclosure . The ABF-1 includes a trim plate
(height=11″ idth=6-1/4″), mounting hardware, and an adhesive-backed
annunciator label.
ABS-1
(H = 8-1/2″ W = 4-1/2″ D = 1-3/8″)
The Annunciator Surface Box-1 provides for the remote mounting of the AFM
annunciator in a surface-mount enclosure. Knockouts are provided for use with
1-2″ conduit. The annunciator mounts directly to the ABS-1 without a dress
plate.
Note: The ABS-1 will not support the installation of the AKS-1 or APJ-1.
AKS-1
The Annunciator Key Switch provides access security for the control switches
on the AFM16AT. Includes a key, mounting hardware and an adhesive backed
annunciator label. The AKS-1 can only be employed with a flush-mount type
backbox.
APJ-1
The Annunciator Phone Jack provides a fireman’s telephone jack that mounts to
the ABF-1 dress plate. Includes mounting hardware and an adhesive-backed
annunciator label. The APJ-1 can only be employed with a flush-mount type
backbox.
Section Three: Installation
AFM Installation Summary
- Run the EIA-485 and power circuits out to the location of the annunciator.
- Select an appropriate knockout on the backbox and mount the backbox.
- Connect the backbox to a solid ground, such as a properly grounded metallic cold water pipe.
- Draw all annunciator and power wiring into the enclosure. Do not terminate the shield (if employed) to the backbox (see Figure 3-2).
- Insert the custom display labels into the annunciator (see Figure 3-3).
- As appropriate, cut jumper options on the annunciator as outlined in Figure 3-4.
- ABF-1 Only – Turn the ABF-1 Dress Plate face down on a surface with the screw studs facing up. Position the AFM-16AT over the screw studs and secure to the dress plate with the two nuts and lock washers provided (see Figure 3-5).
- ABF-1 Only – Remove the backing from the Annunciator Label and affix to the dress plate as illustrated in Figure 3-6.
- ABF-1 Only – If employing an Annunciator Key Switch (AKS-1), mount the switch to the dress plate. Plug the switch leads to Connector J4 on the Annunciator (see Figure 3-7).
- ABF-1 Only – If employing an Annunciator Phone Jack (APJ-1), mount the jack to the ABF-1 Dress Plate. Connect the telephone circuit to the leads of the APJ-1(see Figure 3-7).
- Connect power-limited EIA-485 circuit and power-limited power wiring to the Annunciator Terminal Blocks as illustrated in Figure 3-8.
- Place the annunciator/dress plate assembly into the backbox and secure with two screws.
- Connect the EIA-485 circuit to the CPU as illustrated in Figure 3-9.
- Connect the power loop for the annunciator to the Main Power Supply as illustrated in Figure 3-10.
Installation of the AFM Annunciator is complete. Program the AFM into the respective CPU and full test the system.
Figure 3-1: Mounting the Backbox
Select a knockout on the backbox. Mount the backbox and draw all annunciator, power, and telephone wiring (if employing an APJ-1) into the enclosure. Connect the backbox to a solid ground such as a metallic cold water pipe.
The EIA-485 circuit should be wired using a twisted-pair cable having a Characteristic Impedance of approximately 120 ohms. Do not run cable adjacent to, or in the same conduit as, 120-volt AC service, noisy electrical circuits that are powering mechanical bells or horns, audio circuits above 25 volts (RMS), motor control circuits, or SCR power circuits. Twisted shielded wiring should be used for EIA-485 circuits that are not contained entirely in conduit. Do not allow the shield to enter or touch the annunciator enclosure, as illustrated above. The shield should only be terminated at the fire alarm control panel. Wire-nut multiple shields together outside of the cabinet.
AFM-16AT Slide-In Labels
Slide-in labels for the AFM-16AT Annunciator are contained on the following
pages. Two labels are required for the AFM– 16AT – one for the left-hand side
and one for the right-hand side of the faceplate. Each label has a distinctive
format.
Three types of labels are offered:
Set A: Factory-printed zone labels:
These provide labels for alarm zones 1 through 16.
Set B: Factory-printed system/zone labels:
These provide labels for Acknowledge, Signal Silence, System Reset, and other
CPU control functions, as well as alarm zones 1 through 8.
Set C: Custom User Labels:
These blank labels can be customized by the user. If information is to be
typed onto these labels, they should be reproduced on a copy machine so that
the entire page can be
inserted into a typewriter. Two sets of custom user labels are provided so
that one set may be used as a work sheet.
Effective Window Size
The size of the visible portion of an AFM-16AT label window is 9/16″ high by
1″ across. Using a pitch of 10 characters per inch at six lines per inch, up
to three lines of 10 characters each may be typed within this window space. If
information is to be typed onto these labels, make a reproduction on a copy
machine to use as a practice copy.
AFM-32A Slide-In Labels
Slide-in labels for the AFM-32A Annunciator are contained on the following
pages. Two labels are required for the AFM–32A – one for the left-hand side
and one for the right-hand side of the faceplate. Each label has a distinctive
format.
Three types of labels are offered:
Set D: Factory-printed zone labels:
These provide labels for alarm zones 1 through 32.
Set E: Factory-printed system/zone labels:
These provide labels for System Alarm, Supervisory condition, and alarm zones
1 through 24.
Set F: Custom User Labels:
These blank labels can be customized by the user. If information is to be
typed onto these labels, they should be reproduced on a copy machine so that
the entire page can be inserted into a typewriter.
Effective Window Size
The size of the visible portion of an AFM-32A label window is 1/2″ high by
1-3/8″ across. If information is to be typed onto these labels, make a
reproduction on a copy machine to use as a practice copy.
Figure 3-3: Inserting Display Labels
Remove the center pages of this manual. If using the custom user display
labels, type the appropriate information on the labels. Carefully cut out the
labels and insert them into the AFM by slipping them into the label slots on
the back side of the annunciator face plate.
Note: To ensure the best fit, cut directly along the dotted line
surrounding each label.
Figure 3-4: Annunciator Jumper Options
Figure 3-5: Mounting the Dress Plate
Position the annunciator over the screw studs on the dress plate and secure
with two nuts and lock washers provided.
Figure 3-6: Applying the Annunciator Label
Remove backing from adhesive-backed Annunciator Label and affix the label to
the bottom of the ABF-1 Dress Plate as illustrated.
Note: If an AKS-1 is to be installed, use the label supplied with the
appropriate kit and discard the other label.
Figure 3-7: Installing AFM Options
If employing an Annunciator Key Switch (AKS-1), mount the switch to the ABF-1 Dress Plate. Plug the switch leads from the AKS-1 into Connector J4 on the annunciator.
If employing an Annunciator Phone Jack (APJ-1), mount the jack to the ABF-1 Dress Plate. Connect the telephone circuit to the leads of the APJ-1 as shown below.
Figure 3-8: AFM Field Connections
Connect the annunciator and power wiring to the terminal blocks on the back of
the AFM as illustrated below.
Caution! Failure to observe proper polarity on these connections may
result in damage to the annunciator.
Installation Requirements
The EIA-485 circuit that drives the AFM must be connected to the CPU as
illustrated below.
Connect the EIA-485 (+) and (-) lines to the CPU terminals. On a System 5000,
ensure that the CPU U4 ROM software is Part Number 73085 or greater.
Figure 3-9: Connecting the EIA-485 Loop
Figure 3-10: Main Power Supply Connections
The AFM annunciator can be powered by an MPS-24A or an MPS-24B. This power run
to the annunciator need not contain a Power Supervision Relay since loss of
power is
inherently supervised through communication loss.
MPS-24A Main Power Supply:
Connect the power run for the AFM to MPS-24A TB3 Terminals 1 (+) and 2 (-) (1
amp max) or Terminals 3 (+) and 4 (-) (3 amps max). The total amount of
current drawn from these terminals cannot exceed the above ratings in standby
or in alarm.
MPS-24B Main Power Supply:
Connect the power run for the AFM to MPS-24B TB2 Terminals 1 (+) and 2 (-). No
more than 200 mA current can be drawn from these terminals in standby or
alarm.
Section Four: Operation
Figure 4-1: AFM-16AT Operation
If the Annunciator loses communication with the control panel, all the
yellow LEDs will flash.
Figure 4-2: AFM-32A Operation
If the Annunciator loses communication with the control panel, the yellow
System Trouble LED will flash.
Annunciator Operation
Annunciator points “track” or follow those control panel points they are
programmed to annunciate; they do not latch. The table below outlines the
annunciation of various circuits and functions.
Note: Control Switches marked “not used” will still function as local
LAMP TEST or local ACKNOWLEDGE switches for their respective points.
Table 4-1: Annunciator Point Functions
- If Jumper JP1 has not been cut, the eight CPU functions will not be active.
- These control switches will function only if Jumper JP3 has been cut.
- These Status LEDs are active only when the CPU has been programmed for “Output Status.”
- These control switches require that the CPU be programmed for “Output Control.”
- The AFM annunciates the eight AIM-200 software zones only, not each addressable point on the AIM.
- If an IZ-4, IZ-8 or IZM-8 circuit has been programmed as a supervisory point, both the red and yellow LEDs will be illuminated for a supervisory condition. Illumination of the yellow LED alone indicates a trouble condition (open circuit) on a supervisory zone.
Limited Warranty
NOTIFIER® warrants its products to be free from defects in materials and
workmanship for eighteen (18) months from the date of manufacture, under
normal use and service. Products are date stamped at time of manufacture. The
sole and exclusive obligation of NOTIFIER® is to repair or replace, at its
option, free of charge for parts and labor, any part which is defective in
materials or workmanship under normal use and service. For products not under
NOTIFIER® manufacturing date stamp control, the warranty is eighteen (18)
months from date of original purchase by NOTIFIER® ‘s distributor unless the
installation instructions or catalog sets forth a shorter period, in which
case the shorter period shall apply. This warranty is void if the product is
altered, repaired or serviced by anyone other than NOTIFIER® or its authorized
distributors or if there is a failure to maintain the products and systems in
which they operate in a proper and workable manner. In case of defect, secure
a Return Material Authorization form from our customer service department.
Return product, transportation prepaid, to NOTIFIER® , 12 Clintonville Road,
Northford, Connecticut 06472-1653.
This writing constitutes the only warranty made by NOTIFIER® with respect to
its products. NOTIFIER® does not represent that its products will prevent any
loss by fire or otherwise, or that its products will in all cases provide the
protection for which they are installed or intended. Buyer acknowledges that
NOTIFIER® is not an insurer and assumes no risk for loss or damages or the
cost of any inconvenience, transportation, damage, misuse, abuse, accident or
similar incident.
NOTIFIER® GIVES NO WARRANTY, EXPRESSED OR IMPLIED, OF MERCHANTABILITY, FITNESS
FOR ANY PARTICULAR PURPOSE, OR OTHERWISE WHICH EXTEND BEYOND THE DESCRIPTION
ON THE FACE HEREOF. UNDER NO CIRCUMSTANCES SHALL NOTIFIER® BE LIABLE FOR ANY
LOSS OF OR DAMAGE TO PROPERTY, DIRECT, INCIDENTAL OR CONSEQUENTIAL, ARISING
OUT OF THE USE OF, OR INABILITY TO USE NOTIFIER® PRODUCTS. FURTHERMORE,
NOTIFIER® SHALL NOT BE LIABLE FOR ANY PERSONAL INJURY OR DEATH WHICH MAY ARISE
IN THE COURSE OF, OR AS A RESULT OF, PERSONAL, COMMERCIAL OR INDUSTRIAL USE OF
ITS PRODUCTS.
This warranty replaces all previous warranties and is the only warranty made
by NOTIFIER®. No increase or alteration, written or verbal, of the obligation
of this warranty is authorized.
“NOTIFIER” is a registered trademark.
Set A
Zone Label #1
LOCAL SILENCE AND ACKNOWLEDGE →
SYSTEM TROUBLE →
Cut out along dotted line and insert into the left- hand side of AFM-16AT|
Set A
Zone Label #1
← ON-LINE
Cut out along dotted line and insert into the right- hand side of AFM-16AT| |
Set B
System/Zone
Label #1
LOCAL SILENCE AND ACKNOWLEDGE →
SYSTEM TROUBLE →
Cut out along dotted line and insert into the left- hand side of AFM-16AT|
Set B
System/Zone
Label #2
← ON-LINE
Cut out along dotted line and insert into the right-hand side of AFM-16AT
---|---|---|---|---
ALARM ZONE
1| ALARM ZONE
9| ACKNOWLEDGE
System Alarm/Trouble| ALARM ZONE
1
ALARM ZONE
2| ALARM ZONE
10| SIGNAL
SILENCE| ALARM ZONE
2
ALARM ZONE
3| ALARM ZONE
11| SYSTEM RESET| ALARM ZONE
3
ALARM ZONE
4| ALARM ZONE
12| SUPERVISORY
SIGNAL| ALARM ZONE
4
ALARM ZONE
5| ALARM ZONE
13| INDICATING CIRCUIT 1| ALARM ZONE
5
ALARM ZONE
6| ALARM ZONE
14| INDICATING CIRCUIT 2| ALARM ZONE
6
ALARM ZONE
7| ALARM ZONE
15| MUNICIPAL
STATION| ALARM ZONE
7
ALARM ZONE
8| ALARM ZONE
16| ALARM RELAY
PANEL TROUBLE| ALARM ZONE
8
Set D
Zone Label #1
LOCAL SILENCE AND
ACKNOWLEDGE →
SYSTEM TROUBLE →
Cut out along dotted line and insert into the left-
hand side of AFM-32A| | Set D
Zone Label #2
← ON-LINE
Cut out along dotted line and insert into the right- hand side of AFM-32A| |
Set E
Custom User Label #1
LOCAL SILENCE AND
ACKNOWLEDGE →
SYSTEM TROUBLE →
Cut out along dotted line and insert into the left-hand side of AFM-32A
---|---|---|---|---
ALARM ZONE 1| ALARM ZONE 17|
ALARM ZONE 2| ALARM ZONE 18|
ALARM ZONE 3| ALARM ZONE 19|
ALARM ZONE 4| ALARM ZONE 20|
ALARM ZONE 5| ALARM ZONE 21|
ALARM ZONE 6| ALARM ZONE 22| |
ALARM ZONE 7| ALARM ZONE 23|
ALARM ZONE 8| ALARM ZONE 24|
ALARM ZONE 9| ALARM ZONE 25|
ALARM ZONE 10| ALARM ZONE 26|
ALARM ZONE 11| ALARM ZONE 27|
ALARM ZONE 12| ALARM ZONE 28|
ALARM ZONE 13| ALARM ZONE 29|
ALARM ZONE 14| ALARM ZONE 30|
ALARM ZONE 15| ALARM ZONE 31|
I ALARM ZONE 16| ALARM ZONE 32|
Set C
Custom User
Label #1
LOCAL SILENCE AND ACKNOWLEDGE →
SYSTEM TROUBLE →
Cut out along dotted line and insert into the lefthand side of AFM-16AT|
Set C
Custom User
Label #2
ON-LINE →
Cut out along dotted line
and insert into the righthand side of AFM-16AT| Set C
Custom User
Label #1
LOCAL SILENCE AND ACKNOWLEDGE →
SYSTEM TROUBLE →
Cut out along dotted line and insert into the lefthand side of AFM-16AT|
Set C
Custom User
Label #2
← ON-LINE
Cut out along dotted line
and insert into the righthand side of AFM-16AT
---|---|---|---
Set E
System/Zone Label #1
LOCAL SILENCE AND ACKNOWLEDGE →
SYSTEM TROUBLE →
Cut out along dotted line and insert into the left- hand side of AFM-32A| |
Set E
System/Zone Label #2
← ON-LINE
Cut out along dotted line and insert into the right- hand side of AFM-32A| |
Set F
Custom User Label #2
← ON-LINE
Cut out along dotted line and insert into the right-hand side of AFM-32A
---|---|---|---|---
SYSTEM ALARM| ALARM ZONE 9|
| ALARM ZONE 10|
| ALARM ZONE 11|
| ALARM ZONE 12|
IND. CIRCUIT 1| ALARM ZONE 13|
IND. CIRCUIT 2| ALARM ZONE 14|
MUNICIPAL TIE| ALARM ZONE 15|
ALARM RELAY| ALARM ZONE 16|
ALARM ZONE 1| ALARM ZONE 17|
ALARM ZONE 2| ALARM ZONE 18|
ALARM ZONE 3| ALARM ZONE 19|
ALARM ZONE 4| ALARM ZONE 20|
ALARM ZONE 5| ALARM ZONE 21|
ALARM ZONE 6| ALARM ZONE 22|
ALARM ZONE 7| ALARM ZONE 23|
ALARM ZONE 8| ALARM ZONE 24|
www.PDF-Zoo.com
firealarmresources.com
Documents / Resources
|
NOTIFIER AFM-16AT Annunciator Fixed
Module
[pdf] Instruction Manual
AFM-32A, AFM-16AT, AFM-16AT Annunciator Fixed Module, Annunciator Fixed
Module, Fixed Module, Module
---|---
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>