NOTIFIER AFP-200 ROM Field Software Change Procedure

NOTIFIER-AFP-200-ROM-Field-Software-Change-Procedure-prodfuct-
image

Field Software Change Procedure

Document #15632 Rev. B 5/20/93 ECN 93-119 P/N 15632:B

NOTIFIER-AFP-200-ROM-Field-Software-Change-
Procedure-01

Firmware Change

This procedure outlines the mechanical installation steps required to install EPROMs in the AFP-200.

Handling precautions for integrated circuits
Static electricity can destroy integrated circuits (ICs)! To prevent damage to the EPROM, a wrist strap and a static-free IC insertion/extraction tool is highly recommended. The manufacturer cannot be responsible for damage to the EPROM as a result of improper handling.

System Power Sources
Always remove primary and secondary power before working on the system!

  1. Disconnect battery backup power before working on the system!
  2. Proceed by disconnecting AC power to the panel at the main service circuit breaker (not the circuit breaker at the alarm control panel’s power supply).
  3. Wait 60 seconds to allow for capacitive discharge before touching any of the system’s components.
  4. Reverse the procedure for powering up the system – AC first – then batteries.

Integrated Circuit Pin Conversion
Observe proper orientation of any IC removed or installed! Note location of Pin 1 with respect to the notch in the body of the IC. The replacement EPROM must be installed in the same manner as the EPROM removed. Failure to observe this orientation will result in destruction of the EPROM. NOTE: Some ICs may have a small dot instead of a notch for orientation purposes.

EPROM # Release # Summary of Changes
73354 1.0 Initial Release
73397 1.1 Increases 4-wire smoke detector reset time and changes the

operation of releasing zones 93-94
73441| 1.2| Changed AFP-200 operation to: 1) limit maximum alarm verification time setting to 30 seconds (CSFM requirements) and 2) delay “loss of AC” for DACTs (new UL/NFPA requirements). Add: 1) global acknowledge for ACS annunciators, 2) trouble tone for terminal mode LCD-80s and 3) style D operation for MMX-1 and MMX-2 modules. Software refinements were made in Auto programming, Up load/down-load, detector sensitive programming, obscuration display, detector testing, default setting,

EPROM Replacement
Observe proper orientation of any IC removed or installed! To replace the EPROM, complete the following steps:

  1. Once all power has been removed, disconnect any optional modules (if installed).
  2. Locate U9 (bottom right of the board).
  3. Gently loosen and remove U9 from board.
  4. Install replacement EPROM in location U9. Observe proper orientation! The notch or dot should be on the right-hand side of the IC. Use care to insure that the EPROM’s pins are not bent or broken during insertion.
  5. Reconnect power supplies.

NOTIFIER-AFP-200-ROM-Field-Software-Change-
Procedure-03 Programming and Testing
Reprogram and test the AFP-200 after EPROM replacement.