NOTIFIER ACPS-610-E Addressable Charger-Power Supply Owner’s Manual

June 9, 2024
NOTIFIER

NOTIFIER ACPS-610-E Addressable Charger-Power Supply

NOTIFIER ACPS-610-E Addressable Charger-Power Supply

General

The ACPS-610(E) is an auxiliary power supply with a battery charging option and a host of special features. Selectable charging options allow the ACPS-610(E) to provide 6 amps of shared power to four outputs while charging batteries from 12 to 200 AH, or 10 amps of shared power when the unit is configured for use with an external battery charger. Four indi-vidually addressable outputs can be independently configured for auxiliary power or Notification Appliance Circuits (NAC). NAC outputs support notification appliance synchronization for devices manufactured by System Sensor®, Wheelock, and Gentex. An option to disable battery charging allows the sys-tem designer to use the four built-in circuits to distribute 10 amps of power for general purposes, excluding NAC appli-cations.The ACPS-610(E) is compatible with NOTIFIER intelligent fire alarm control panels using CLIP and FlashScan® protocol.

Features

  • Certified for seismic applications when used with the appro-priate seismic mounting kit.
  • Approved for Marine applications when used with listed compatible equipment (see DN-60688).
  • Provides 6.0 A of NAC power or 10 A of general purpose power.
  • Four Class B (Style Y) or four Class A (Style Z) outputs, individually addressable by the FACP.
  • When built-in outputs are configured for NAC operation, each circuit supports strobe synchronization with the follow-ing manufacturers’ audio/visual devices: System Sensor® (SpectrAlert® and SpectrAlert Advance Series) or Whee-lock or Gentex.
  • Each circuit can be software-selected for use as: a Notifica-tion Appliance Circuit, general purpose 24 VDC power, four-wire detector power, or door holder.
  • Steady, March Time (120 PPM), Two Stage, Temporal, or UZC Zone-Coded and Non-Coded devices – software-selectable by circuit.
  • Universal Zone Coder (UZC-256) option supports for pro-grammable coded outputs. Up to 256 different codes.
  • Auxiliary Outputs: 24V @ 0.5A and 5V @ 0.15A.
  • Charges 12 to 200 AH batteries with full supervision. The charger on the ACPS may be disabled via software. When disabled, a separate, external charger is required, for exam-ple a CHG-120.
  • May be used to provide battery backup for multiple ACPS supplies.
  • AC loss detection, brownout detection, and AC loss delay reporting.
  • Power-limited outputs.
  • Isolated Signaling Line Circuit (SLC) interface.
  • Selectable ground fault detection.
  • Canadian two stage operation.

Specifications

  • Primary (AC) power:
    • ACPS-610: 120 VAC, 50/60 Hz input, 5.0 A maximum.
    • ACPS-610E: 220/240 VAC, 50/60 Hz input, 2.5 A maxi-mum.
  • Output voltage: 24 VDC electrically regulated and power limited (under primary AC mains). Under secondary power, 20.4 to 26.4 VDC.
  • Output circuits – TB3, TB4, TB5, TB6 on Main Board: 1.5 A maximum for any NAC output circuit. 2.5 A maximum for any Power output with battery charger disabled.
  •  Secondary power (battery) charging circuit – lead-acid bat-tery charger which will charge 12 to 200 AH batteries. Max-imum charger current – 5.0 A.
  • Secondary power auxiliary outputs – TB2 on CPS-24 Board:
    • 24V @ 0.5A, power limited.
    • 5V @ 0.15A, power limited.
  • Wiring: utilizes wire sizes 12 to 18 AWG (3.1 to 0.78 mm²).
  • SLC specifications: Average SLC current is 1.287 mA. SLC data is transmitted between 24.0 VDC, 5 VDC, and 0 VDC at approximately 3.33 Kbaud.
  • Battery fuse (F2): 15A, Fast-acting.
  • Weight: 4.5 lb.

ACPS Programming

The ACPS-610(E) is programmable via the simple-to-use PK-PPS programming utility, which requires a Windows® PC with a USB port and cable. Programming may be performed during an on-line session with the ACPS-610(E), or previously saved programs may be downloaded to individual ACPS-610(E) units. The ACPS-610(E) requires the use of a minimum of 5 SLC address points, and will use up to 14 SLC address points to fulfill requirements for Canadian supervision and two stage operation.
NOTE: PK-PPS is available for download from www.magni- fire.com

NOTIFIER logo 1

Listings and Approvals

These listings and approvals apply to the modules specified in this document. In some cases, certain modules or applications may not be listed by certain approval agencies, or listing may be in process. Consult factory for latest listing status.

  • UL Listed: S635.
  • ULC Listed: S635.
  • FM Approved.
  • CSFM: 0028:0243.
  • MEA #30-08-E.
  • FDNY: COA #6085, #6098.

When used with the MARINE-EQ, appropriate seismic bracket, and marine approved devices, the ACPS-610(E) is approved by the following agencies:

  • US Coast Guard: 161.002/50/0 (Standard 46 CFR).
  • Lloyd’s Register: 11/600013 (ENV 3 category).
  • American Bureau of Shipping (ABS).

Product Line Information

  • ACPS-610: Addressable charger power supply, with selectable built-in synchronization, and four built-in control modules. Sev-eral mounting options available (see below).
  • ACPS-610E: Same as ACPS-610, but configured for 220/240 VAC operation.
  • CAB-PS1: The CAB-PS1 can house one ACPS-610(E) and two 12 AH batteries. Dimensions: 15.218″ (38.654 cm) high x 14.5″ (36.83 cm) wide x 3.562″ (9.048 cm) deep with door.
  • SEISKIT-PS/2/4: Seismic kit for mounting ACPS-610 in a CAB-PS1. Includes bracket for two 12 AH batteries.
  • DR-PS1: When installing an ACPS-610(E) into an older ver-sion of the CAB-PS1 used for an ACPS-2406(E), the new wider door must be ordered for use with the older version cabinet.
  • BB-25: The BB-25 can house one ACPS-610(E) and two 12 volt, 26 AH batteries.
  • BB-100: The BB-100 can house one ACPS-610(E) and two 12 volt, 55 AH or 100 AH AH batteries.
  • BB-200: The BB-200 can house one ACPS-610(E) and four 12 volt, 100 AH batteries.
  • CAB-4 Series: The ACPS-610(E) can mount in any of the CAB-4 Series cabinets with CHS-PS or CHS-BH. See DN-6857.
  • EQ Cabinet Series: The ACPS-610(E) can mount in any of the EQ Cabinet Series cabinets using CHS-6. See DN-60229.
  • MARINE-EQ System: Protects equipment in shipboard and waterfront applications. For a full list of required and optional equipment, see DN-60688.
  • CHS-PS/CHS-6: Chassis used to mount the ACPS-610(E) in row 1, 2, or 3 of the CAB-4 or EQ series enclosure.
  • CHS-BH: Battery mounting chassis that holds up to two 12AH batteries on a CHS-PS.
  • Batteries: ACPS-610(E) battery charging circuit range is 12 -200 AH. See DN-6933.

Notifier®, FlashScan®, System Sensor®, and SpectrAlert® are registered trademarks of Honeywell International Inc. Windows® is a registered trademark of Microsoft.
©2012 by Honeywell International Inc. All rights reserved. Unauthorized use of this document is strictly prohibited.

This document is not intended to be used for installation purposes. We try to keep our product information up-to-date and accurate. We cannot cover all specific applications or anticipate all requirements. All specifications are subject to change without notice. For more information, contact Notifier. Phone: 203-484-7161, FAX: 203-484-7118. www.notifier.com firealarmresources.com

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

NOTIFIER User Manuals

Related Manuals