General

The NFS2-3030 is an intelligent Fire Alarm Control Panel (FACP) designed for medium- to large-scale facilities. Fire emergency detection and evacuation are extremely critical to life safety, and the NFS2-3030 is ideally suited for these appli-cations. The NFS2-3030 is part of the ONYX® Series of prod-ucts from NOTIFIER. The NFS2-3030 is ideal for virtually any application because it features a modular design that is config-ured per project requirements. With one to ten Signaling Line Circuits (SLCs), the NFS2-3030 supports up to 3,180 intelli-gent addressable devices.
Information is critical to fire evacuation personnel, and the NFS2-3030’s large 640-character Liquid Crystal Display (LCD) presents vital information to operators concerning a fire situa-tion, fire progression, and evacuation details.
A host of other options are available, including single- or multi-channel voice; firefighter’s telephone; LED, LCD, or PC-based graphic annunciators; networking; advanced detection prod-ucts for challenging environments; wireless fire protection; and many additional options.

Features

  • Certified for seismic applications when used with the appro-priate seismic mounting kit.

  • Approved for Marine applications when a marine-listed ver-sion is used with marine-listed compatible equipment. See DN-60688.

  • Complies with UL 2572 Mass Notification Systems (NFS2-3030 version 20 or higher).

  • One to ten isolated intelligent Signaling Line Circuits (SLC) Style 4, 6 or 7.

  • Wireless fire protection using SWIFT Smart Wireless Inte-grated Fire Technology. See DN-60820.

  • Up to 159 detectors and 159 modules per SLC; 318 devices per loop/3,180 per FACP or network node.

    •  Detectors can be any mix of ion, photo, thermal, or multi-sensor; wireless detectors are available for use with the FWSG.
    • Modules include addressable pull stations, normally open contact devices, two-wire smoke detectors, notification, or relay; wireless modules are available for use with the FWSG.
  • Large 16 line, 640 character LCD backlit display or use display-less as a network node.

  •  Network options:

    • High-speed network for up to 200 nodes (NFS2-3030, NFS2-640, NFS-320(C), NFS-320SYS, NCA-2, DVC-EM, ONYXWorks, NFS-3030, NFS-640, and NCA).
    • Standard network for up to 103 nodes (NFS2-3030, NFS2-640, NFS-320(C), NFS-320SYS, NCA-2, DVC-EM, ONYXWorks, NCS, NFS-3030, NFS-640, NCA, AFP-200, AFP-300/400, AFP-1010, and AM2020). Up to 54 nodes when DVC-EM is used in network paging.
  • Built-in Alarm, Trouble, Security, and Supervisory relays.

  • VeriFire® Tools online/offline program option.

  • With built-in Degraded Mode operation, the system is capa-ble of general alarm if a fire alarm condition is present even if the central processing unit (CPU) fails.

  • Weekly Occupancy Schedules allow changing sensitivity by time of day and day of week.

  • EIA-485 annunciators, including custom graphics.

  • History file with 4000-event capacity in nonvolatile memory, plus separate 1000-event alarm-only file.

  • Advanced history filters allow sorting by event, time, date, or address.

  • Alarm Verification selection per point, with automatic counter.

  • Autoprogramming and Walk Test reports.

  • Multiple central station communication options:

    • Standard UDACT
    • Internet
    • Internet/GSM
  • Positive Alarm Sequence (PAS) Presignal.

  • Silence Inhibit and Auto Silence timer options.

  • Field-programmable on panel or on PC, with VeriFire Tools program, also check, compare.

  • Non-alarm points for lower priority functions.

  • Remote ACK/Signal Silence/System Reset/Drill via monitor modules.

  • Up to 1000 powerful Boolean logic equations.

  • Supports SCS Series smoke control system in both HVAC and FSCS modes.

  • FM6320 approved Gas Detection System with FMM-4-20 module and any FM listed gas detector.

  • EIA-232 printer port.

  • EIA-485 annunciator port.
    640-CHARACTER DISPLAY FEATURES

  • Backlit, 640-character display.

  • Program keypad: full QWERTY keypad.

  • Up to nine users, each with a password and selectable access levels.

  • 11 LED indicators: Power; Fire Alarm; Pre-Alarm; Secu-rity; Supervisory; System Trouble; Other Event; Signals Silenced; Point Disabled; CPU Failure; Controls Active.

  • Membrane Switch Controls: Acknowledge; Signal Silence; Drill; System Reset; Lamp Test.

  • LCD Display: 640 characters (16 lines x 40 characters) with long-life LED backlight.
    FLASHSCAN® INTELLIGENT FEATURES

  • Polls up to 318 devices on each loop in less than two seconds.

  • Activates up to 159 outputs in less than five seconds.

  • Multicolor LEDs blink device address during Walk Test.

  • Fully digital, high-precision protocol (U.S. Patent 5,539,389).

  • Manual sensitivity adjustment — up to nine levels.

  • Pre-alarm ONYX intelligent sensing — up to nine levels.

  • Sensitivity levels:

    • Ion – 0.5 to 2.5%/foot obscuration.
    • Photo – 0.5 to 2.35%/foot obscuration.
    • Laser (VIEW®) – 0.02 to 2.0%/foot obscuration.
    • Acclimate Plus™ – 0.5 to 4.0%/foot obscuration.
    • IntelliQuad – 1.0 to 4.0%/foot obscuration.
    • IntelliQuad™ PLUS – 1.0 to 4.0%/foot obscuration
  • Drift compensation (U.S. Patent 5,764,142).

  • Multi-detector algorithm involves nearby detectors in alarm decision (U.S. Patent 5,627,515).

  • Automatic detector sensitivity testing (NFPA-72 compliant).

  • Maintenance alert (two levels).

  • Self-optimizing pre-alarm.

  • Programmable activation of sounder/relay bases during alarm or pre-alarm.

  • Read Status displays the level of detector cleanliness.
    FSL-751 VIEW® (VERY INTELLIGENT EARLY WARNING) SMOKE DETECTION TECHNOLOGY

  • Advanced ONYX intelligent sensing algorithms differentiate between smoke and non-smoke signals (U.S. Patent 5,831,524).

  • Addressable operation pinpoints the fire location.

  • Early warning performance comparable to the best aspira-tion systems at a fraction of the lifetime cost.

Sample System Options

NOTIFIER NFS2-3030 Intelligent Addressable Fire Alarm System-
fig2

NOTE: CPU2-3030 firmware version 14.0 (and higher) can support LCD-160 on the RDP port, or LCD2-80 in terminal mode, but not both at the same time.

  • FAPT-851 ACCLIMATE PLUS™ LOW-PROFILE INTELLIGENT MULTI-SENSOR

    • Detector automatically adjusts sensitivity levels without operator intervention or programming. Sensitivity increases with heat.
    • Microprocessor-based technology; combination photo and thermal technology.
    • Low-temperature signal at 40°F ± 5°F (4.44°C ± 2.77°C).
  • FSC-851 INTELLIQUAD
    ADVANCED MULTI-CRITERIA DETECTOR

    • Detects all four major elements of a fire (smoke, heat, CO, and flame).
    • Automatic drift compensation of smoke sensor and CO cell.
    •  High nuisance-alarm immunity.
  • INTELLIGENT FAAST® DETECTORS FSA-5000, FSA-8000, FSA-20000 AND FSA-20000P

    • Connects directly to the SLC loop of compatible ONYX series panels.
    • Provides five event thresholds that can be individually pro-grammed with descriptive labels for control-by-event pro-gramming; uses five detector addresses.
    • Uses patented particle separator and field-replaceable filter to remove contaminants.
    • Advanced algorithms reject common nuisance conditions
    • SA-5000 covers 5,000 square feet through one pipe.
    • SA-8000 covers 8,000 square feet through one pipe.
    • FSA-20000 covers 28,800 square feet through one to four pipes.
    • FSA-20000P covers 28,800 square feet through one to four addressable pipes. Supports addressable pipes to pinpoint location of alarm events.
  • FCO-851 INTELLIQUAD™ PLUS
    ADVANCED MULTI-CRITERIA FIRE/CO DETECTOR

    • Detects all four major elements of a fire.
    • Separate signal for life-safety CO detection.
    • Optional addressable sounder base for Temp-3 (fire) or Temp-4(CO) tone.
    • Automatic drift compensation of smoke sensor and CO cell.
    • High nuisance-alarm immunity.
  • FMM-4-20 GAS DETECTION MODULE

    • Interface to industry-standard linear scale 4-20 mA sensors.
    • Five programmable thresholds.
    • FM Approved, Class 6320 (Stationary Gas Sensors/Detectors).
  • SWIFT WIRELESS

    • Self-healing mesh wireless protocol.
    • Each SWIFT Gateway supports up to 50 devices: 1 wireless gateway and up to 49 SWIFT devices.
    • Up to 4 wireless gateways can be installed with overlapping network coverage.
  • RELEASING FEATURES

    • Ten independent hazards.
    • Sophisticated cross-zone (three options).
    • Delay timer and Discharge timers (adjustable).
    • Abort (four options).
  • VOICE AND TELEPHONE FEATURES

    • Up to eight channels of digital audio.
    • 35 watt, 50 watt, 75 watt, and 100/125 watt digital amplifiers (DAA2/DAX series and DS series).
    • Solid state message generation.
    • Hard-wired voice control module options.
    • Firefighter telephone option.
    • 30- to 120-watt analog amplifiers (AA Series).
    • Backup tone generator and amplifier option.

FlashScan® Exclusive World-Leading Detector Protocol

At the heart of the NFS2-3030 is a set of detection devices and device protocol — FlashScan (U.S. Patent 5,539,389). FlashS-can is an all-digital protocol that gives superior precision and high noise immunity. As well as giving quick identification of an active input device, this protocol can also activate many output devices in a frac-tion of the time required by competitive protocols. This high speed also allows the NFS2-3030 to have the largest device per loop capacity in the industry — 318 points — yet every input and output device is sampled in less than two seconds. The microprocessor-based FlashScan® detectors have bicolor LEDs that can be coded to provide diagnostic information, such as device address during Walk Test.

ONYX Intelligent Sensing

ONYX Intelligent Sensing is a set of software algorithms that provide the NFS2-3030 with industry-leading smoke detection capability. These complex algorithms require many calcula-tions on each reading of each detector, and are made possible by the very high-speed microcomputer used by the NFS2-3030.

  • Drift Compensation and Smoothing. Drift compensation allows the detector to retain its original ability to detect actual smoke, and resist false alarms, even as dirt accumulates. It reduces maintenance requirements by allowing the system to automatically perform the periodic sensitivity measurements required by NFPA 72. Smoothing filters are also provided by software to remove transient noise signals, usually caused by electrical interference.
  • Maintenance Warnings. When the drift compensation per-formed for a detector reaches a certain level, the performance of the detector may be compromised, and special warnings are given. There are three warning levels: (1) Low Chamber value; (2) Maintenance Alert, indicative of dust accumulation that is near but below the allowed limit; (3) Maintenance Urgent, indicative of dust accumulation above the allowed limit.
  • Sensitivity Adjust. Nine sensitivity levels are provided for alarm detection. These levels can be set manually, or can change automatically between day and night. Nine levels of pre-alarm sensitivity can also be selected, based on predeter-mined levels of alarm. Pre-alarm operation can be latching or self-restoring, and can be used to activate special control func-tions.
  • Self-Optimizing Pre-Alarm. Each detector may be set for “Self-Optimizing” pre-alarm. In this special mode, the detector “learns” its normal environment, measuring the peak analog readings over a long period of time, and setting the pre-alarm level just above these normal peaks.
  • Cooperating Multi-Detector Sensing. A patented feature of ONYX Intelligent Sensing is the ability of a smoke sensor to consider readings from nearby sensors in making alarm or pre-alarm decisions. Without statistical sacrifice in the ability to resist false alarms, it allows a sensor to increase its sensitivity to actual smoke by a factor of almost two to one.

Field Programming Options

  • Autoprogram is a timesaving feature. The FACP “learns” what devices are physically connected and automatically loads them in the program with default values for all parameters. Requiring less than one minute to run, this routine allows the user to have almost immediate fire protection in a new installa-tion, even if only a portion of the detectors are installed.
  • Keypad Program Edit. The NFS2-3030, like all NOTIFIER intelligent panels, has the exclusive feature of program cre-ation and editing capability from the front panel keypad, while continuing to provide fire protection. The architecture of the NFS2-3030 software is such that each point entry carries its own program, including control-by-event links to other points. This allows the program to be entered with independent per-point segments, while the NFS2-3030 simultaneously monitors other (already installed) points for alarm conditions.
  • VERIFIRE® TOOLS
    VeriFire® Tools is an offline programming and test utility that can greatly reduce installation programming time, and increase confidence in the site- specific software. It is Win-dows® based and provides technologically advanced capabili-ties to aid the installer. The installer may create the entire program for the NFS2-3030 in the comfort of the office, test it, store a backup file, then bring it to the site and download from a laptop into the panel.

Product Line Information

  • “Configuration Guidelines” on page 4
  • “Main System Components” on page 4
  • “Networking Options” on page 4
  • “Auxiliary Power Supplies and Batteries” on page 4
  • “Audio Options” on page 5
  • “Compatible Devices, EIA-232 Ports” on page 5
  • “Compatible Devices, EIA-485 Ports” on page 5
  • “Compatible Intelligent Devices” on page 5
  • “Enclosures, Chassis, and Dress Plates” on page 6
  • “Other Options” on page 7

CONFIGURATION GUIDELINES

Stand-alone and network systems require a main display. On single-FACP systems (one NFS2-3030D), the display option is the CPU2-3030D. On network systems (two or more net-worked fire panel nodes), at least one NCA-2, NCS, or ONYX- Works annunciation device is required. Options listed as follows.

MAIN SYSTEM COMPONENTS

CPU2-3030D: NFS2-3030 Primary Display. CPU2-3030D ships with keypad/display installed; includes 640-character backlit LCD display, QWERTY programming and control key-pad. CPU2-3030 is a central processing unit and requires an AMPS-24(E) power supply. For English ULC applications, use CPU2-3030DC. Non- English versions are available: CPU2-3030D-FR, CPU2-3030D-HE, CPU2-3030D-KO, CPU2-3030D-PO, CPU2-3030D-SC, CPU2-3030D-SP, CPU2-3030D-TC, and CPU2-3030D-TH. For English Marine applica-tions order CPU2-3030D-M; for non-English Marine applica-tions order CPU2-3030D-M and the appropriate KP-KIT-XX.(See DN-60688.)
CPU2-3030ND: CPU2-3030 without display. Non-English ver-sions are available: CPU2-3030ND-FR, CPU2-3030ND-HE, CPU2-3030ND-KO, CPU2-3030ND-PO, CPU2-3030ND- SC, CPU2-3030ND-SP, CPU2-3030ND-TC.

  • LCM-320: Loop Control Module. Provides one SLC. NFS2-3030 supports up to five LCM-320s and five LEM-320 expand-ers for a total of ten SLCs. See DN-6881.
  • LEM-320: Loop Expander Module. Expands an LCM-320. See DN-6881.
  • SAMPLE SYSTEM: Four-loop NFS2-3030 with display: CPU2-3030D, DP-DISP, two BMP-1s, CHS-M3, two LCM-320s, two LEM-320s, AMPS-24, SBB-A4, DR-A4, BP2-4, BB-100, batteries.

NETWORKING OPTIONS

  • NCA-2: Network Control Annunciator, 640 characters. An alternate primary display for CPU2-3030 can be provided by the NCA-2, NCS, or ONYXWorks. Using NCA-2 as primary display enables non-English languages. On network systems (two or more networked fire panel nodes), one network display (either NCA-2, NCS, or ONYXWorks) is required for every sys-tem. On network systems, the NCA-2 connects (and requires) a standard Network Communication Module or High-Speed Network Communication Module. Mounts in a row of FACP node or in two annunciator positions. Mounting options include the DP-DISP, ADP-4B, or in an annunciator box, such as the ABS-2D. In CAB-4 top-row applications, a DP-DISP and two BMP-1 blank modules are required for mounting. Non-English versions are available: NCA-2-FR, NCA-2-HE, NCA-2-KO, NCA-2-PO, NCA-2-SC, NCA-2-SP, NCA-2-TC, NCA-2-TH. For English ULC applications, order NCA-2C; for marine applica-tions, order NCA-2-M; for non-English marine applications order NCA-2-M and appropriate KP-KIT-XX. See DN-7047.

  • NCM-W, NCM-F: Standard Network Communications Mod-ules. Wire and multi-mode fiber versions available. See DN-6861.
    HS-NCM-W/MF/SF/WMF/WSF/MFSF: High-speed Network Communications Modules that can connect to two nodes. Wire, single-mode fiber, multi-mode fiber, and media conver-sion models are available. See DN-60454.

  • RPT-W, RPT-F, RPT-WF: Standard-network repeater board with wire connection (RPT-W), multi-mode fiber connection (RPT-F), or allowing a change in media type between wire and fiber (RPT-WF). Not used with high-speed networks. See DN-6971.

  • ONYXWorks: UL-listed graphics PC workstation, ONYXWorks GUI software, and computer hardware. See DN-7048 for spe-cific part numbers.

  • NFN-GW-EM-3: NFN Gateway, embedded. (Replaces NFN-GW-EM.) See DN-60499.

  • NWS-3 : NOTIFIRENET™ Web Server. See DN-6928.

  • CAP-GW: Common Alerting Protocol Gateway. See DN-60756.

  • VESDA-HLI-GW: VESDAnet high-level interface gateway. See DN-60753.

  • LEDSIGN-GW: UL-listed sign gateway. Interfaces with classic and high-speed NOTIFIRENET networks through the NFN Gateway. See DN-60679.

  • OAX2-24V: UL-listed LED sign, used with LEDSIGN-GW. See DN-60679.

AUXILIARY POWER SUPPLIES AND BATTERIES

  • AMPS-24(E): One required for each NFS2-3030. Addressable power supply and battery charger with two 24 VDC outputs. Addressable by any FlashScan® or CLIP mode FACP. Charges 7 to 200 AH batteries. Occupies up to five addresses on an SLC, depending on configuration. Primary input power for panel. See DN-6883.
  • APS2-6R: Auxiliary Power Supply. Provides up to 6.0 amperes of power for peripheral devices. Includes battery input and transfer relay, and overcurrent protection. Mounts on two of four positions on a CHS-4L or CHS-4 chassis. See DN-5952.
  • ACPS-610: 6.0 A or 10.0 A addressable charging power sup-ply. See DN-60244.
  • FCPS-24S6/-24S8: Remote 6 A and 8 A power supplies with battery charger. See DN-6927.
  • BAT Series: Batteries. AMPS-24 uses two 12 volt, 7 to 200 AH batteries. See DN-6933.

AUDIO OPTIONS

NOTE: See “Enclosures, Chassis, and Dress Plates” on page 6 for mounting hardware.

  • DVC-EM: Digital Voice Command, digital audio processor with message storage for up to 32 minutes of standard quality (4 minutes at high quality) digital audio. See DN-7045.
  • DVC-RPU: Digital Voice Command Remote Paging Unit for use with DVC-EM. Includes the keypad/display. See DN-60726.
  • DS-DB: Digital Series Distribution Board, provides bulk ampli-fication capabilities to the DVC-EM while retaining digital audio distribuition capabilities. Can be configured with up to four DS-AMPs, supplying high-level risers spread throughout an instal-lation. See DN-60565.
  • DVC-KD: DVC-EM keypad for local annunciation and controls; status LEDs and 24 user-programmable buttons. See DN-7045.
  • DS-AMP/E: 125W, 25 VRMS, or 100W, 70VRMS. 70VRMS requires DS-XF70V step-up transformer. Digital Series Ampli-fier, part of the DS-DB system. See DN-60663.
  • DS-RFM, DS-FM, DS-SFM: Fiber conversion modules for DVC-EM, DS-DB distribution board, and DAA2/DAX Series amplifiers. See DN-60633.
  • DAA2-5025(E): 50W, 25 Vrms Digital Audio Amplifier assem-bly with power supply; includes chassis. See DN-60556.
  • DAA2-5070(E): 50W, 70.7 Vrms Digital Audio Amplifier assembly with power supply; includes chassis. See DN-60556.
  • DAA2-7525(E): 75W, 25 Vrms digital audio amplifier assembly with power supply; includes chassis. See DN-60556.
  • DAX-3525(E): 35W, 25 Vrms Digital Audio Amplifier assembly with power supply, includes chassis. See DN-60561.
  • DAX-3570(E) : 35W, 70.7 Vrms Digital Audio Amplifier assem-bly with power supply, includes chassis. See DN-60561.
  • DAX-5025(E): 50W, 25 Vrms Digital Audio Amplifier assembly with power supply, includes chassis. See DN-60561.
  • DAX-5070(E): 50W, 70.7 Vrms Digital Audio Amplifier assem-bly with power supply, includes chassis. See DN-60561.
  • TELH-1: Firefighter’s Telephone Handset for use with the DVC-EM when mounted in the CA-2 chassis. See DN-7045.
  • CMIC-1: Microphone used with DVC/DVC-EM. Included with CA-2 chassis assembly. See DN-7045.
  • RM-1/RM-1SA : Remote microphone assemblies, mount on ADP-4 (RM-1) dress panel or CAB-RM/-RMR (RM-1SA) stand-alone cabinets. See DN-6728.
  • AA-30: Audio Amplifier, 30 watts, 25 Vrms. Includes amplifier and audio input supervision, backup input, and automatic swi-tchover, power supply, cables. See DN-3224.
  • AA-120/AA-100: Audio Amplifier. AA-120 is 120 watts, 25 Vrms. AA-100 is 100 watts, 70.7 Vrms. The amplifier contains an integral chassis for mounting to a CAB-B4, -C4, or -D4 backbox (consumes one row). Includes audio input and ampli-fied output supervision, backup input, and automatic switcho-ver to backup tone. See DN-3224.
  • DAA Series Digital Audio Amplifiers: Legacy DAA Series amplifiers are compatible with DVC systems running SR4.0. For specific information on DAA-50 series amplifiers, refer to DN-7046. For information on DAA-7525 Series, refer to DN-60257.

COMPATIBLE DEVICES, EIA-232 PORTS

  • PRN-7: 80-column printer. See DN-60897
  • VS4095/5: Printer, 40-column, 24 V. Order from Keltron, Inc. See DN-3260.
  • DPI-232: Direct Panel Interface, specialized modem for extending serial data links to remotely located FACPs and/or peripherals. See DN-6870.

COMPATIBLE DEVICES, EIA-485 PORTS

  • ACM-24AT: ONYX® Series ACS annunciator – up to 96 points of annunciation with Alarm or Active LED, Trouble LED, and switch per circuit. Active/Alarm LEDs can be programmed (by powered-up switch selection) by point to be red, green, or yel-low; the Trouble LED is always yellow. See DN-6862.
  • AEM-24AT: Same LED and switch capabilities as ACM-24AT; expands the ACM-24AT to 48, 72, or 96 points. See DN-6862.
  • ACM-48A : ONYX® Series ACS annunciator – up to 96 points of annunciation with Alarm or Active LED per circuit. Active/Alarm LEDs can be programmed (by powered-up switch selec-tion) in groups of 24 to be red, green, or yellow. Expandable to 96 points with one AEM-48A. See DN-6862.
  • AEM-48A: Same LED capabilities as ACM-48A; expands the ACM-48A to 96 points. See DN-6862.
  • ACM-8R: Remote Relay Module with eight Form-C contacts. Can be located up to 6,000 ft. (1828.8 m) from panel on four wires. See DN-3558.
  • LCD-160: Liquid Crystal Display annunciator, 160-character backlit. Can store character sets for multiple languages. LCD-160C is used for ULC applications. See DN-6940.
  • LCD2-80: Terminal and ACS mode. 80-character, backlit LCD display. Mounts up to 6,000 ft. (1828.8 m) from panel. Up to 32 per FACP. See LCD2-80 (DN-60548).
  • SCS Series: Smoke control station; eight (expandable to 16) circuits. See DN-4818.
  • TM-4: Transmitter Module. Includes three reverse-polarity cir-cuits and one municipal box circuit. Mounts in panel module position (as in single-address mode applications) or in CHS-M3 position. See DN-6860.
  • UDACT-2: Universal Digital Alarm Communicator Transmitter, 636 channel. See DN-60686.
  • UZC-256: Programmable Universal Zone Coder provides pos-itive non-interfering successive zone coding. Microprocessor-controlled, field-programmable from IBM®-compatible PCs (requires optional programming kit). Mounts on a CHS-4 series chassis within NFS2-3030.

COMPATIBLE INTELLIGENT DEVICES

NOTE: “A” suffix indicates ULC-Listed model.

  • FWSG Wireless SWIFT Gateway: Addressable gateway sup-ports wireless SLC devices. Not appropriate for ULC applica-tions. See DN-60820.
  • FSA-5000: Intelligent FAAST® XS Fire Alarm Aspiration Sens-ing Technology. Intelligent aspirating smoke detector for appli-cations up to 5,000 sq.ft. For Canadian applications, order FSA-5000A.
  • FSA-8000: Intelligent FAAST® XM Fire Alarm Aspiration Sensing Technology. Intelligent aspirating smoke detector for applications up to 8,000 sq.ft. For Canadian applications, order FSA-8000A. See DN-60792.
  • FSA-20000: Intelligent FAAST® XT Fire Alarm Aspiration Sensing Technology. Intelligent aspirating smoke detector for applications up to 28,800 sq.ft. For Canadian applications, order FSA-20000A. See DN-60849.
  • FSA-20000P FAAST ® XT PRO Intelligent Aspiration Detector For applications up to 28,800 sq. ft. (2601 sq. m.) through one to four addressable pipes. See DN-60792
  • FSB-200(A): Intelligent beam smoke detector. See DN-6985.
  • FSB-200S(A): Intelligent beam smoke detector with integral sensitivity test. See DN-6985.
  • FSC-851(A): FlashScan IntelliQuad Advanced Multi-Criteria Detector. See DN-60412.
  • FCO-851(A): FlashScan IntelliQuad PLUS Advanced Multi-Cri-teria Fire/CO Detector. See DN-60689.
  • FSI-851(A): Low-profile FlashScan ionization detector. See DN-6985.
  • FSP-851(A): Low-profile FlashScan photoelectric detector. See DN-6935.
  • FSP-851R(A): Low-profile intelligent photoelectric sensor, remote test capable. For use with DNR(W). See DN-6935.
  • FSP-851T(A) : Low-profile FlashScan photoelectric detector with 135°F (57°C) thermal. See DN-6935.
  • FST-851(A):: FlashScan thermal detector 135°F (57°C). See DN-6936.
  • FST-851R(A): FlashScan thermal detector 135°F (57°C) with rate-of-rise. See DN-6936.
  • FST-851H(A) : FlashScan 190°F (88°C) high-temperature ther-mal detector. See DN-6936.
  • FAPT-851(A): FlashScan Acclimate Plus™ low-profile multi-sensor detector. See DN-6937.
  • FSL-751(A): FlashScan VIEW® laser photo detector. See DN-6886.
  • DNR(A): InnovairFlex low-flow non-relay duct-detector housing (order FSP-851 separately). Replaces FSD-751PL/FSD-751RPL. See DN-60429.
  • DNRW(A): Same as above with NEMA-4 rating, watertight. See DN-60429.
  • B224RB: Low-profile relay base. See DN-60054.
  • B224BI: Isolator base for low-profile detectors. See DN-60054.
  • B210LP: Low-profile base. Standard U.S. style. Replaces B710LP. See DN-60054.
  • B501(A): European-style, 4″ (10.16 cm) base. See DN-60054.
  • B200S: Intelligent programmable sounder base, capable of producing a variety of tone patterns including ANSI Temporal 3. Compatible with sychronization protocol. See DN-60054.
  • B200S-LF: Low-frequency version of B200S. See DN-60054.
  • B200SCOA: Based on B200SA, with added CO detector markings in English/French. For Canadian applications only.
  • B200SR: Sounder base, Temporal 3 or Continuous tone. See DN-60054.
  • B200SR-LF: Low-frequency version of B200SR. See DN-60054.
  • FMM-1(A):: FlashScan monitor module. See DN-6720.
  • FDM-1(A): FlashScan dual monitor module. See DN-6720.
  • FZM-1(A): FlashScan two-wire detector monitor module. See DN-6720.
  • FMM-101(A): FlashScan miniature monitor module. See DN-6720.
  • FMM-4-20: FlashScan 4-20 mA protocol monitor module. See DN-60411.
  • FCM-1(A): FlashScan control module. See DN-6724.
  • FCM-1-REL(A): FlashScan releasing control module. See DN-60390.
  • FTM-1(A): Firephone Telephone Module connects a remote firefighter telephone to a centralized telephone console. Reports status to panel. Wiring to jacks and handsets is super-vised. See DN-6989.
  • FRM-1(A): FlashScan relay module. See DN-6724.
  • FDRM-1(A) : FlashScan dual monitor/dual relay module. See DN-60709.
  • NBG-12LX: Manual pull station, addressable. See DN-6726.
  • ISO-X: Isolator module. See DN-2243.
  • ISO-6: Six Fault isolator module. For Canadian applications order ISO-6A. See DN-60844.
  • XP6-C(A): FlashScan six-circuit supervised control module. See DN-6924.
  • XP6-MA(A): FlashScan six-zone interface module; connects intelligent alarm system to two-wire conventional detection zone. See DN-6925.
  • XP6-R(A): FlashScan six-relay (Form-C) control module. See DN-6926.
  • XP10-M(A): FlashScan ten-input monitor module. See DN-6923.
  • SLC-IM : SLC integration module, for VESDAnet detectors. See DN-60755.

ENCLOSURES, CHASSIS, AND DRESS PLATES

  • CAB-4 Series Enclosure : NFS2-3030 mounts in a standard CAB-4 Series enclosure (available in four sizes, “A” through “D”). Backbox and door ordered separately; requires BP2-4 battery plate. A trim ring option is available for semi-flush mounting. See DN-6857.
  • EQ Series Cabinets: EQ series cabinets will house amplifiers, power supplies, battery chargers and control modules. EQ cabinets are available in three sizes, “B” through “D”. See DN-60229.
  • CAB-BM Marine System: Protects equipment in shipboard and waterfront applications. Order CPU2-3030D-M; for non-English marine applications order CPU2-3030D and appropri-ate KP-KIT-XX. Also order BB-MB for systems using 100 AH batteries. For a full list of required and optional equipment, see DN-60688.
  • CHS-M3: Mounting chassis for CPU2-3030. One required for each CPU2-3030D/3030ND.
  • CA-2: Chassis for FACP control panel when DVC-EM is used with firefighter’s telephone. Mounts in the top two rows of a CAB-4 series enclosure.
  • DP-DISP: Dress panel for top row in cabinet with CPU2-3030D installed.
  • DP-1B: Blank dress panel. Provides dead-front panel for unused tiers; covers DAA2/DAX series or AA-series amplifier. See DN-7046.
  • CHS-BH1: Battery chassis; holds two 12.0 AH batteries. Mounts on the left side of DAA2 chassis. See DN-7046.
  • CA-1: Chassis, occupies one tier of a CAB-4 Series enclosure. The left side accommodates one DVC-EM and a DVC-KD (optional); and the right side houses a CMIC-1 microphone and its well (optional). See DN-7045.
  • CA-2: Chassis assembly, occupies two tiers of a CAB-4 Series enclosure. The left side accommodates one DVC-EM mounted on a half-chassis and one NFS2-3030 or NCA-2 mounted on a half-chassis. The right side houses a microphone/handset well. The CA-2 assembly includes CMIC-1 microphone. ADDR Series doors with two-tier visibility are available for use with the CA-2 configuration: ADDR-B4, ADDR-C4, ADDR-D4 (below).
  • ADDR-B4: Two-tier-sized door designed for use with the CA-2 chassis configuration. ADDR Series doors are similar to CAB-4 Series “DR” doors, but a clear window space exposes the top two tiers of the CAB-4 enclosure. Use an SBB-B4 backbox with the ADDR-B4. See DN-7045, DN-6857.
  • ADDR-C4: Three-tier-sized door designed for use with the CA-2 chassis configuration. ADDR Series doors are similar to CAB-4 Series “DR” doors, but a clear window space exposes the top two tiers of the CAB-4 enclosure. Use an SBB-C4 backbox with the ADDR-C4. See DN-7045, DN-6857.
  • ADDR-D4: Four-tier-sized door designed for use with the CA-2 chassis configuration. ADDR Series doors are similar to CAB-4 Series “DR” doors, but a clear window space exposes the top two tiers of the CAB-4 enclosure. Use an SBB-D4 backbox with the ADDR-D4. See DN-7045, DN-6857.
  • DPA-1: Dress panel, used with the CA-1 chassis when config-ured with a DVC-EM, DVC-KD, and CMIC-1. See DN-7045.
  • DPA-2: Dress Panel used with the CA-2 chassis assembly.
  • DPA-1A4: Dress panel, used with the CA-1 chassis when the CMIC-1 is not used. Provides mounting options on right two bays for two ACS annunciators, or for blank plates. See DN-7045.
  • ADP-4B: Annunciator dress plate. Mounts in rows 2, 3 or 4 of a CAB-4 series enclosure. Used with ACS series annuncia-tors.
  • BMP-1: Blank module for unused module positions.
  • DP-1B: Blank dress panel. Provides dead-front panel for unused tiers; covers DAA2/DAX series or AA-series amplifier.
  • BP2-4: Battery plate, required.
  • CHS-4L: Low-profile four-position Chassis. Mounts two AA-30 amplifiers.
  • CHS-4N: Chassis for mounting up to four APS-6Rs.
  • CHS-6: Chassis used with the XP6 and XP10 Multi-Modules. Mounts up to six modules in any CAB-4 series row.
  • NFS-LBB: Battery Box. The NFS-LBB is used to mount up to two 55 AH batteries. Dimensions: Box: 24″ (610 mm) wide x 14″ (356 mm) high x 7.75″ (197 mm) deep.
  • Door: 24.125″ (613 mm) wide x 14.25″ (362 mm) high; door adds 0.0625″ (approx. 1.6 mm) to depth.

BACKBOXES

NOTE: “C” suffix indicates ULC-Listed model.

  • BB-100: Backbox for batteries and power supplies. The BB-100 is used to mount up to two 100 AH batteries and power supply, if needed. 30″ (76.20 cm) wide x 25″ (63.50 cm) high x 7.5″ (19.05 cm) deep; depth includes door.
  • BB-200: Backbox for batteries and power supplies. Holds up to four 100 AH batteries (200 AH capacity) and power supply. 30″ (76.20 cm) wide x 36″ (91.44 cm) high x 7.5″ (19.05 cm) deep; depth includes door.
  • BB-UZC: Backbox for housing the UZC-256 for applications where the UZC will not fit in panel enclosure. Black; for red, order BB-UZC-R. See DN-3404.
  • ABF-1B(C) Annunciator Flush Box
  • ABF-1DB(C) Annunciator Flush Box with Door. UL/ULC Listed.
  • ABF-2B Annunciator Flush Box
  • ABF-2DB(C) Annunciator Flush Box with Door
  • ABF-4B Annunciator Flush Box
  • ABS-1TB(C) Annunciator Surface Box
  • ABS-1B(C) Annunciator Surface Box
  • ABS-2B Annunciator Surface Box
  • ABS-2D(C) Annunciator Surface Box
  • ABS-4D(C) Annunciator Surface Box
  • SEISKIT-CAB: Seismic mounting kit. Required for seismic-certified applications with NFS2-3030 and other equipment mounted in CAB-4 Series Enclosures. Includes battery bracket for two 26 AH batteries.
  • SEISKIT-LBB: Seismic kit for the NFS-LBB. Includes battery bracket for two 55 AH batteries.

OTHER OPTIONS

Slave digital alarm communicator. See DN-6619.
UDAC: Digital alarm communicator. See DN-6746.

  • IPDACT-2, IPDACT Internet Monitoring Module: Connects to primary and secondary DACT telephone output ports for internet communications over customer-provided Ethernet connection. Requires compatible Teldat VisorALARM Central Station Receiver. Can use DHCP or static IP. See DN-60408.
  • IPCHSKIT: IP Communicator Chassis Mounting Kit. For mounting an IPDACT-2/2UD onto the panel chassis or CHS-4 series chassis. Use IPENC for external mounting applications.
  • IPSPLT: Y-adapter option allow connection of both panel dialer outputs to one IPDACT-2/2UD cable input.
  • IPENC: External enclosure for IPDACT, includes IPBRKT mounting bracket; Red; for black, order IPENC-B.
  • IPGSM-4G: Internet and Digital Cellular Fire Alarm Communica-tor. Provides selectable configurable paths: cellular only, IP only, or IP primary with cellular backup. Connects to the primary and secondary ports of a DACT. For Canadian applications order IPGSM-4GC. See DH-60769.
    NOTE: For other options including compatibility with retrofit equip-ment, refer to the panel’s installation manual, the SLC manual, and the Device Compatibility Document.

System Specifications

SYSTEM CAPACITY

  • Intelligent Signaling Line Circuits ………..1 expandable to 10
  • Intelligent detectors …………………………………… 159 per loop
  • Addressable monitor/control modules ………….. 159 per loop
  • Programmable software zones……………………….. over 2000
  • ACS annunciators per CPU2-3030 …………………..32 address x 64 or 96 points
    NOTE: The CPU2-3030 can support up to 96 annunciator address points per ACM- 24AT/-48A.

SPECIFICATIONS

  • Primary Input Power:

    • AMPS-24: 110-120 VAC, 50/60 Hz, 4.5 A maximum.
    • AMPS-24E: 240 VAC, 50/60 Hz, 2.25 A maximum.
  • DC Output:

    • Main 24 VDC: Up to 5.0 A
    • Aux 24 VDC: Up to 5.0 A
    • 5 VDC: Up to 0.15 A.
  • Current draw (Standby/Alarm):

    • CPU2-3030D board: 0.340 A.
    • CPU2-3030ND board: 0.120 A.
    • LCM-320: 0.130 A.
    • LEM-320: 0.100 A.
    • – AMPS-24(E)*: 0.13 A.
      (Draws power from secondary power source only.)
      NOTE: See AMPS-24(E) Manual 51907 for a complete current draw calculation sheet and details of input and output values.
  • Battery charger range: 7 AH – 200 AH. Use separate cabinet for batteries over 26 AH.

  • Float Rate: 27.6 V.

  • SHIPPING WEIGHT

    • CPU2-3030D: 5.95 lb (2.70 kg).
    • CPU2-3030ND: 2.90 lb (1.32 kg).

TEMPERATURE AND HUMIDITY RANGES

This system meets NFPA requirements for operation at 0 –49°C/32 – 120°F and at a relative humidity 93% ± 2% RH (noncondensing) at 32°C ± 2°C (90°F ± 3°F). However, the useful life of the system’s standby batteries and the electronic components may be adversely affected by extreme tempera-ture ranges and humidity. Therefore, it is recommended that this system and its peripherals be installed in an environment with a normal room temperature of 15 – 27°C/60 – 80°F.

AGENCY LISTINGS AND APPROVALS

These listings and approvals apply to the modules specified in this document. In some cases, certain modules or applications may not be listed by certain approval agencies, or listing may be in process. Consult factory for latest listing status.

  • UL Listed: S635.
  • ULC Listed: S527-11.
  • MEA: 232-06-E.
  • Fire Dept. of New York: COA#6211.
  • CSFM: 7165-0028:0224 (Commercial).
  • FM Approved.
  • FM6320 Approved. Class 6320 for Gas Detection.
  • City of Chicago.
  • City of Denver.
  • Singapore Productivity and Standards Board (PSB).
  •  CCCF listed.
  •  Fire Services Department (Hong Kong).

Marine Applications: Marine approved systems must be con-figured using components itemized in this document. (See Main System Components, in “Product Line Information.) Spe-cific connections and requirements for those components are described in the installation document, PN 54756. When these requirements are followed, systems are approved by the fol-lowing agencies:

  • US Coast Guard 161.002/55/0 (Standard 46 CFR and 161.002).
  • Lloyd’s Register 11/600013 (ENV 3 category).
  • American Bureau of Shipping (ABS) Type Approval. NOTE: For information on marine applications, see DN-60688.

STANDARDS

The NFS2-3030 complies with the following UL Standards and NFPA 72, International Building Code (IBC), and California Building Code (CBC) Fire Alarm Systems requirements:

  • UL 864 (Fire).
  • UL 1076 (Burglary).
  • UL 2572 (Mass Notification Systems). (NFS2-3030 version 20 or higher)
  • ULC-S527-11 Standard for the Installation of Fire Alarm Sys-tems.
  • LOCAL (Automatic, Manual, Waterflow and Sprinkler Supervisory).
  • AUXILIARY (Automatic, Manual and Waterflow) (requires TM-4).
  • REMOTE STATION (Automatic, Manual, Waterflow and Sprinkler Supervisory) (requires TM-4).
  • PROPRIETARY (Automatic, Manual, Waterflow and Sprin-kler Supervisory). Not applicable for FM.
  • EMERGENCY VOICE/ALARM.
  • OT, PSDN (Other Technologies, Packet-switched Data Net-work).
  • IBC 2012, IBC 2009, IBC 2006, IBC 2003, IBC 2000 (Seis-mic).
  • CBC 2007 (Seismic).

IntelliQuad™, NOTIFIRENET™, ONYXWorks™, and SWIFT™ are all trademarks; and Acclimate® Plus™, FlashScan®, Intelligent FAAST®, NOTIFIER®, ONYX®, VeriFire® Tools, and VIEW® are all registered trademarks of Honeywell International Inc.
©2017 by Honeywell International Inc. All rights reserved. Unauthorized use of this document is strictly prohibited.

This document is not intended to be used for installation purposes.
We try to keep our product information up-to-date and accurate.
We cannot cover all specific applications or anticipate all requirements.
All specifications are subject to change without notice.