NOTIFIER AMPS-24/E Addressable Power Supply Owner’s Manual

June 9, 2024
NOTIFIER

NOTIFIER logo AMPS-24/E
Power Supply
for the NFS-3030, NFS2-3030 and NCA-2
Owner’s Manual
NOTIFIER AMPS-24 E Addressable Power Supply -

General

NOTIFIER’s AMPS-24/E is an addressable power supply and battery charger with up to three 24 VDC outputs. It operates in either FlashScan® or CLIP (Classic Loop Interface Protocol) mode with the NFS-3030/NFS2-3030 Fire Alarm Control Panel (FACP). It can also be used as the primary power supply for the NCA-2 Network Control Annunciator.

Features

  • Addressable by NFS-3030/NFS2-3030 FACP.
  • Selectable charging current charges 7 AH to 200 AH batteries.
  • Isolated Signaling Line Circuit (SLC) interface.
  • Trouble bus input for use with normally-open dry contacts or open-collector circuit.
  • USB Type B connector for programming installation parameters.
  • Brownout detection.
  • Battery/battery charger supervision.
  • Secondary Power Auxiliary Outputs: 24V @ 0.5A and 5V @ 0.15A.
  • AC loss detection and AC loss delay reporting.
  • Mounts in a CAB-4 Series enclosure, EQ Cabinet Series enclosure, BB-25, BB-100, or BB-200 Battery Backbox.

Specifications

  • Primary (AC) power:
    AMPS24: 110-120 VAC 50/60 Hz input, 5 A maximum;
    AMPS24E: 220-240 VAC 50/60 Hz input, 2.5 A maximum.

  • MAIN 24V Output – filtered power-limited power. Refer to table for configuration/current information.

Charger Setting/Battery Size| Main 24V (TB 1 on
Main Control Unit)
Max. Current| *Total AUX 24V (TB3 on Main
Control Unit with TB2 on CPS-24) Max. Current
---|---|---
1 A/7-26AH Bat-teries| 5A| 3A
2A/12-60AH Bat-teries| 5A| 3A
5A/55-200AH
Configuration 1
Configuration 2| 5A
3A| OA
1A
Disabled| 5A| 5A

  • Maximum current for all AUX 24 volt outputs. Note that TB2 on CPS-24 is limited to 0.5A.

    • AUX 24V – provides filtered power-limited power for additional components.
      Refer to table above for configuration/current information.

    • Secondary power (battery) charging circuit: Current-limited, sealed lead-acid battery charger which will charge 7 to 200 AH batteries.
      Selectable charging current: 1.0 A, 2.0 A or 5.0 A.

    • Secondary power auxiliary outputs.

    • Wire sizes: 10 AWG (5.26 mm²) to 22 AWG (0.326 mm²).

    • Battery fuse (F2): 15 A, fast-acting.

    • Shipping Weight: 4.25 lb

Agency Listings and Approvals

These listings and approvals apply to the AMPS-24/E power supply. In some cases, certain modules may not be listed by certain approval agencies, or listing may be in process. Consult factory for latest listing status.

  • UL: S635
  • ULC: CS118
  • City of Chicago
  • City of Denver
  • MEA: 345-02-E
  • CSFM: 7165-0028:224
  • FM: Approved
  • FDNY: #6026

Product Line Information

AMPS-24: Addressable power supply/battery charger
AMPS-24E: Same as AMPS-24: 220-240VAC operation

This document is not intended to be used for installation purposes.
We try to keep our product information up-to-date and accurate.
We cannot cover all specific applications or anticipate all requirements.
All specifications are subject to change without notice.
For more information, contact Notifier. Phone: 203-484-7161, FAX: 203-484-7118.
www.notifier.com
FlashScan® is a registered trademark of Honeywell International Inc.
©2009 by Honeywell International Inc. All rights reserved. Unauthorized use of this document is strictly prohibited.