SIEMENS DB-11 Base Seal Instruction Manual
- June 9, 2024
- SIEMENS
Table of Contents
DB-11 Base Seal
Instruction Manual
DB-11 Base Seal
for use with FP-11, FPO-11, FPT-11, HFP-11, HFPO-11, HFPT-11 and FDOT421/OH921
Detectors
After mounting and wiring the DB-11 base according to the appropriate
installation instructions, follow the steps listed below to install the DB-11
Base Seal.
- Place the base seal (1/4″ white foam) firmly into the bottom of the base. Do not cover the contact springs (See Figure 1.)
- Rotate the detector counterclockwise while pressing on it until the detector drops into the base.
- Rotate the detector clockwise until it stops and locks in place.
Figure 1 Installing the DB-11 Base Seal in the DB-11 Base
Siemens Industry, Inc.
Building Technologies Division
Florham Park, NJ
P/N 315-096054-3