SIEMENS DB-11 Base Seal Instruction Manual

June 9, 2024
SIEMENS

DB-11 Base Seal
Instruction Manual

DB-11 Base Seal

for use with FP-11, FPO-11, FPT-11, HFP-11, HFPO-11, HFPT-11 and FDOT421/OH921 Detectors
After mounting and wiring the DB-11 base according to the appropriate installation instructions, follow the steps listed below to install the DB-11 Base Seal.

  1. Place the base seal (1/4″ white foam) firmly into the bottom of the base. Do not cover the contact springs (See Figure 1.)
  2. Rotate the detector counterclockwise while pressing on it until the detector drops into the base.
  3. Rotate the detector clockwise until it stops and locks in place.

Figure 1 Installing the DB-11 Base Seal in the DB-11 Base

Siemens Industry, Inc.
Building Technologies Division
Florham Park, NJ
P/N 315-096054-3