HEIKO R417 DC Inverter Air to Water Heat Pump User Manual
- June 9, 2024
- HEIKO
Table of Contents
R417 DC Inverter Air to Water Heat Pump
Thermal 6 Thermal 9 Thermal 12
DC Inverter Air to Water Heat Pump
User’s manual
Before operating this product, please read the instructions carefully and keep
this manual for future use.
This product may only be installed or serviced by qualified personnel.
This appliance is filled with R32 refrigerant.
Catalogue
1. Before use
4
1.1 Safety precautions
10
1.2 Working principle
12
1.3 Main components
13
1.4 Specifications
15
2. Assembly Configurations
16
1. Flowchart
16
2. Drawing 1
17
3. Drawing 2
19
4. Drawing 3
22
5. Drawing 4
25
6. Drawing 5
28
7. Drawing 6
31
8. Drawing 7
34
9. Drawing 8
37
10. Drawing 9
40
11. Drawing 10
43
3. Installation
46
3.1 General application system introduction
46
3.2 Tools needed
53
3.3 Installation of the indoor control unit
53
3.4 Installation of the monoblock unit
55
3.5 Accessories
57
3.6 Wiring
58
3.7 Installation of safety valve kit
71
3.8 Water pipe connection
72
3.9 Test run
73
4. Usage
74
4.1 Introduction of operation panel
74
4.2 Operation instruction
79
4.3 Electric heater
104
4.4 Failure codes
105
2
Catalogue
5. Maintenance
110
5.1 Precaution of maintenance for units with flammable refrigerant
110
5.2 Attention
113
5.3 Cleaning of water filter
113
5.4 Cleaning of plate heat exchanger
113
5.5 Gas charging
113
5.6 Condenser coil
115
5.7 Service of indoor control unit
115
5.8 Service of monoblock unit
117
6. Attached drawing
121
6.1 Outlines and dimensions
121
6.2 Exploded view
123
6.3 Wiring diagram
125
6.4 Appendix A:Wiring
128
3
1. Before use
1.1 Safety precautions
Cautions: 1.Do not use means to accelerate the defrosting process or to
clean,other than those recommended
by the manufacturer. 2.The appliance shall be stored in a room without
continuously operating ignition sources
(for example: open flames, an operating gas appliance or an operating electric
heater.). 3.Do not pierce or burn. 4.Be aware that refrigerants may not
contain an odour. 5.Appliance shall be installed, operated and stored in a
room with a floor area larger than X m2
(refer to specifications sheet). 6.The installation of pipe-work shall be kept
to a minimum X m2 (refer to specifications sheet). 7.Spaces where refrigerant
pipes shall be compliance with national gas regulations. 8.Servicing shall be
performed only as recommended by the manufacturer. 9.The appliance shall be
stored in a well-ventilated area where the room size corresponds to the room
area as specified for operation. 10.All working procedure that affets safety
means shall only be carried by competent persons.
Gerneral Notice:
1.Transport of equipment containing flammable refrigerants Compliance with the
transport regulations
2. Marking of equipment using signs Compliance with local regulations
3.Disposal of equipment using flammable refrigerants Compliance with national
regulations
4.Storage of equipment/appliances The storage of equipment should be in
accordance with the manufacturer’s instructions.
5.Storage of packed (unsold)quipment Storage package protection should be
constructed such that mechanical damage to the equipment inside the package
will not cause a leak of the refrigerant charge. The maximum number of pieces
of equipment permitted to be stored together will be determined by local
regulations.
6.Information on servicing 1)Checks to the area Prior to beginning work on
systems containing flammable refrigerants, safety checks are necessary to
ensure that the risk of ignition is minimised. For repair to the refrigerating
system, the following precautions shall be complied with prior to conducting
work on the system. 2)Work procedure Work shall be undertaken under a
controlled procedure so as to minimise the risk of a flammable gas or vapour
being present while the work is being performed.
4
1. Before use
3) General work area All maintenance staff and others working in the local
area shall be instructed on the nature of work being carried out. Work in
confined spaces shall be avoided. The area around the workspace shall be
sectioned off. Ensure that the conditions within the area have been made safe
by control of flammable material. 4) Checking for presence of refrigerant The
area shall be checked with an appropriate refrigerant detector prior to and
during work, to ensure the technician is aware of potentially flammable
atmospheres. Ensure that the leak detection equipment being used is suitable
for use with flammable refrigerants, i.e. non-sparking, adequately sealed or
intrinsically safe. 5) Presence of fire extinguisher If any hot work is to be
conducted on the refrigeration equipment or any associated parts, appropriate
fire extinguishing equipment shall be available to hand. Have a dry powder or
CO2 fire extinguisher adjacent to the charging area. 6) No ignition sources No
person carrying out work in relation to a refrigeration system which involves
exposing any pipe work that contains or has contained flammable refrigerant
shall use any sources of ignition in such a manner that it may lead to the
risk of fire or explosion. All possible ignition sources, including cigarette
smoking, should be kept sufficiently far away from the site of installation,
repairing, removing and disposal, during which flammable refrigerant can
possibly be released to the surrounding space. Prior to work taking place, the
area around the equipment is to be surveyed to make sure that there are no
flammable hazards or ignition risks.”No Smoking” signs shall be displayed. 7)
Ventilated area Ensure that the area is in the open or that it is adequately
ventilated before breaking into the system or conducting any hot work. A
degree of ventilation shall continue during the period that the work is
carried out. The ventilation should safely disperse any released refrigerant
and preferably expel it externally into the atmosphere. 8) Checks to the
refrigeration equipment Where electrical components are being changed, they
shall be fit for the purpose and to the correct specification. At all times
the manufacturer’s maintenance and service guidelines shall be followed. If in
doubt consult the manufacturer’s technical department for assistance. The
following checks shall be applied to installations using flammable
refrigerants: -The charge size is in accordance with the room size within
which the refrigerant containing parts are installed; -The ventilation
machinery and outlets are operating adequately and are not obstructed; -If an
indirect refrigerating circuit is being used, the secondary circuit shall be
checked for the presence of refrigerant; -Marking to the equipment continues
to be visible and legible. Markings and signs that are illegible shall be
corrected; -Refrigeration pipe or components are installed in a position where
they are unlikely to be exposed to any substance which may corrode refrigerant
containing components, unless the components are constructed of materials
which are inherently resistant to being corroded or are suitably protected
against being so corroded.
5
1. Before use
9) Checks to electrical devices Repair and maintenance to electrical
components shall include initial safety checks and component inspection
procedures. If a fault exists that could compromise safety, then no electrical
supply shall be connected to the circuit until it is satisfactorily dealt
with. If the fault cannot be corrected immediately but it is necessary to
continue operation, an adequate temporary solution shall be used. This shall
be reported to the owner of the equipment so all parties are advised. Initial
safety checks shall include: .That capacitors are discharged: this shall be
done in a safe manner to avoid possibility of sparking; .That there no live
electrical components and wiring are exposed while charging, recovering or
purging the system; .That there is continuity of earth bonding.
7.Repairs to sealed components 1)During repairs to sealed components, all
electrical supplies shall be disconnected from the equipment being worked upon
prior to any removal of sealed covers, etc. If it isabsolutely necessary to
have an electrical supply to equipment during servicing, then a permanently
operating form of leak detection shall be located at the most critical point
to warn of a potentially hazardous situation. 2) Particular attention shall be
paid to the following to ensure that by working on electrical components, the
casing is not altered in such a way that the level of protection is affected.
This shall include damage to cables, excessive number of connections,
terminals not made to original specification, damage to seals, incorrect
fitting of glands, etc. Ensure that apparatus is mounted securely. Ensure that
seals or sealing materials have not degraded such that they no longer serve
the purpose of preventing the ingress of flammable atmospheres. Replacement
parts shall be in accordance with the manufacturer’s specifications. NOTE: The
use of silicon sealant may inhibit the effectiveness of some types of leak
detection equipment. Intrinsically safe components do not have to be isolated
prior to working on them.
8.Repair to intrinsically safe components Do not apply any permanent inductive
or capacitance loads to the circuit without ensuring that this will not exceed
the permissible voltage and current permitted for the equipment in use.
Intrinsically safe components are the only types that can be worked on while
live in the presence of a flammable atmosphere.The test apparatus shall be at
the correct rating. Replace components only with parts specified by the
manufacturer. Other parts may result in the ignition of refrigerant in the
atmosphere from a leak.
6
1. Before use
9.Cabling Check that cabling will not be subject to wear,corrosion, excessive
pressure, vibration, sharp edges or any other adverse environmental effects.
The check shall also take into account the effects of aging or continual
vibration from sources such as compressors or fans.
10.Detection of flammable refrigerants Under no circumstances shall potential
sources of ignition be used in the searching for or detection of refrigerant
leaks. A halide torch (or any other detector using a naked flame) shall not be
used.
11.Leak detection methods The following leak detection methods are deemed
acceptable for systems containing flammable refrigerants. Electronic leak
detectors shall be used to detect flammable refrigerants, but the sensitivity
may not be adequate, or may need re-calibration. (Detection equipment shall be
calibrated in a refrigerant-free area.) Ensure that the detector is not a
potential source of ignition and is suitable for the refrigerant used. Leak
detection equipment shall be set at a percentage of the LFL of the refrigerant
and shall be calibrated to the refrigerant employed and the appropriate
percentage of gas (25% maximum) is confirmed. Leak detection fluids are
suitable for use with most refrigerants but the use of detergents containing
chlorine shall be avoided as the chlorine may react with the refrigerant and
corrode the copper pipe-work. If a leak is suspected, all naked flames shall
be removed/ extinguished. If a leakage of refrigerant is found which requires
brazing, all of the refrigerant shall be recovered from the system, or
isolated (by means of shut off valves) in a part of the system remote from the
leak. Oxygen free nitrogen (OFN) shall then be purged through the system both
before and during the brazing process.
12.Removal and evacuation When breaking into the refrigerant circuit to make
repairs or for any other purpose conventional procedures shall be used.
However, it is important that best practice is followed since flammability is
a consideration. The following procedure shall be adhered to: · Remove
refrigerant; · Purge the circuit with inert gas; · Evacuate; · Purge again
with inert gas; · Open the circuit by cutting or brazing. The refrigerant
charge shall be recovered into the correct recovery cylinders. The system
shall be “flushed” with OFN to render the unit safe. This process may need to
be repeated several times. Compressed air or oxygen shall not be used for this
task. Flushing shall be achieved by breaking the vacuum in the system with OFN
and continuing to fill until the working pressure is achieved, then venting to
atmosphere, and finally pulling down to a vacuum. This process shall be
repeated until no refrigerant is within the system. When the final OFN charge
is used, the system shall be vented down to atmospheric pressure to enable
work to take place. This operation is absolutely vital if brazing operations
on the pipe-work are to take place. Ensure that the outlet for the vacuum pump
is not close to any ignition sources and there is ventilation available.
7
1. Before use
13.Charging procedures In addition to conventional charging procedures, the
following requirements shall be followed. Ensure that contamination of
different refrigerants does not occur when using charging equipment. Hoses or
lines shall be as short as possible to minimise the amount of refrigerant
contained in them. Cylinders shall be kept upright.
Ensure that the refrigeration system is earthed prior to charging the system
with refrigerant.
Label the system when charging is complete (if not already).
Extreme care shall be taken not to overfill the refrigeration system. Prior
to recharging the system it shall be pressure tested with OFN. The system
shall be leak tested on completion of charging but prior to commissioning. A
follow up leak test shall be carried out prior to leaving the site.
14.Decommissioning Before carrying out this procedure, it is essential that
the technician is completely familiar with the equipment and all its detail.
It is recommended good practice that all refrigerants are recovered safely.
Prior to the task being carried out, an oil and refrigerant sample shall be
taken in case analysis is required prior to re-use of reclaimed refrigerant.
It is essential that electrical power is available before the task is
commenced. a) Become familiar with the equipment and its operation. b) Isolate
system electrically. c) Before attempting the procedure ensure that:
.Mechanical handling equipment is available, if required, for handling
refrigerant cylinders; .All personal protective equipment is available and
being used correctly; .The recovery process is supervised at all times by a
competent person; .Recovery equipment and cylinders conform to the appropriate
standards. d) Pump down refrigerant system, if possible. e) If a vacuum is not
possible, make a manifold so that refrigerant can be removed from various
parts of the system. f) Make sure that cylinder is situated on the scales
before recovery takes place. g) Start the recovery machine and operate in
accordance with manufacturer’s instructions. h) Do not overfill cylinders. (No
more than 80%volume liquid charge). I) Do not exceed the maximum working
pressure of the cylinder, even temporarily. j) When the cylinders have been
filled correctly and the process completed, make sure that the cylinders and
the equipment are removed from site promptly and all isolation valves on the
equipment are closed off. k) Recovered refrigerant shall not be charged into
another refrigeration system unless it has been cleaned and checked.
15.Labelling Equipment shall be labelled stating that it has been de-
commissioned and emptied of refrigerant. The label shall be dated and signed.
Ensure that there are labels on the equipment stating the equipment contains
flammable refrigerant.
16.Recovery When removing refrigerant from a system, either for servicing or
decommissioning, it is recommended good practice that all refrigerants are
removed safely. When transferring refrigerant into cylinders, ensure that only
appropriate refrigerant recovery cylinders are employed. Ensure that the
correct number of cylinders for holding
8
1. Before use
the total system charge is available. All cylinders to be used are designated
for the recovered refrigerant and labelled for that refrigerant (i.e. special
cylinders for the recovery of refrigerant). Cylinders shall be complete with
pressure relief valve and associated shut-off valves in good working order.
Empty recovery cylinders are evacuated and, if possible, cooled before
recovery occurs. The recovery equipment shall be in good working order with a
set of instructions concerning the equipment that is at hand and shall be
suitable for the recovery of flammable refrigerants. In addition, a set of
calibrated weighing scales shall be available and in good working order. Hoses
shall be complete with leak-free disconnect couplings and in good condition.
Before using the recovery machine, check that it is in satisfactory working
order, has been properly maintained and that any associated electrical
components are sealed to prevent ignition in the event of a refrigerant
release. Consult manufacturer if in doubt. The recovered refrigerant shall be
returned to the refrigerant supplier in the correct recovery cylinder, and the
relevant Waste Transfer Note arranged. Do not mix refrigerants in recovery
units and especially not in cylinders. If compressors or compressor oils are
to be removed, ensure that they have been evacuated to an acceptable level to
make certain that flammable refrigerant does not remain within the lubricant.
The evacuation process shall be carried out prior to returning the compressor
to the suppliers. Only electric heating to the compressor body shall be
employed to accelerate this process. When oil is drained from a system, it
shall be carried out safely. The unit contains fluorinated greenhouse gases.
The refrigerant must not be released into the air! All products comply with
the following EU regulations: Low Voltage Directive, Electromagnetic
Compatibility.
9
1. Before use
1.2 Safety precautions
The following symbols are very important. Please be sure to understand their
meaning, which concerns the product and your personal safety.
Warning
Caution
Prohibition
User Manual
The installation, dismantlement To avoid electrical shock, make Be sure to read this manual before
and maintenance of the unit must be performed by qualified personnel. It is forbidden to do any changes to the structure of the unit.
sure to disconnect the power supply 1 minute or more before servicing the electrical parts. Even after 1 minute, always measure the voltage at the terminals of main
use.
Otherwise injury of person or unit circuit capacitors or electrical parts
damage might happen.
and, before touching, make sure
that those voltages are lower
than the safety voltage.
Ground wire
For sanitary hot water, please always add a mixture valve before water tap and set it to proper temperature.
Use a dedicated socket for this unit, otherwise malfunction may occur.
The power supply to the unit must be grounded.
This appliance can be used by children aged from 8 years and above and persons with reduced physical, sensory or mental capabilities or lack of experience and knowledge if they have been given supervision or instruction concerning use of the appliance in a safe way and understand the hazards involved. Children shall not play with the appliance. Cleaning and user maintenance shall not be made by children without supervision.
Do not touch the air outlet grill when fan motor is running.
Do not touch the power plug with Do not operate your air conditioner
wet hands. Never pull out the plug in a wet room such as a bathroom
by pulling the power cable.
or laundry room.Water or any kind
of liquid is strictly forbidden to be
poured into the product, or may
cause electric creepage or
breakdown of the product.
10
1. Before use
Fuse
Steel Copper
If the supply cord is damaged, it must be replaced by the manufacturer, its service agent or similarly qualified persons in order to avoid a hazard.
Please select the correct fuse or breaker as per recommended. Steel wire or copper wire cannot be taken as substitute for fuse or breaker. Otherwise, damages maybe caused.
Be aware fingers might be hurt by the fin of the coil.
ON
Main
Power Cable RCD
OFF
Indoor control
unit
It is mandatory to use a suitable circuit breaker for the heat pump and make sure the power supply to the unit corresponds to the specifications. Otherwise the unit might be damaged.
Disposal of Scrap Batteries(if there is).Please discard the batteries as sorted municipal waste at the accessible collection point.
An all-pole disconnection device which has at least 3mm clearances in all poles , and have a leakage current that may exceed 10mA, the residual current device (RCD) having a rated residual operating current not exceeding 30mA, and disconnection must be incorporated in the fixed wiring in accordance with the wiring rules.
System water filling
T/P valve
Connect to heating/cooling system
Connect to heat pump
Buffer tank
One way valve Filter
1. It’s suggested to use pure water for filling the system. 2. If use city water for filling, please soften the water and add a filter. Note: After filling, the system of water system should be 0.15~0.6MPa.
City water inlet
This marking indicates that this product should not be disposed with other household wastes throughout the EU. To prevent possible harm to the environment or human health from uncontrolled waste disposal, recycle it responsibly to promote the sustainable reuse of material resources. To return your used device, please use the return and collection systems or contact the retailer where the product was purchased. They can take this product for environmental safe recycling.
11
Evaporator
1. Before use
1.3 Working principle
Water Outlet
Power supply Four-way vavle
Compressor
Water inlet
Water pump
Filter
Heat exchanger
Three-way valve
Pressure check valve
Fan motor
Refrigerant
Filter
T-connector
Heating Cooling
12
1. Before use
1.4 Main components
1.4.1 Indoor control unit
Thermal 6/9/12
Cable gland
Safety valve kit
Operation panel
Water outlet 2 Water outlet 1
Door
13
Water inlet Electric box cover Water pump
Electric heater Water pump
1. Before use
1.4.2 Monoblock unit
Thermal 6/9/12
Thermal 6 GWP: 675: 0,61 tonnes equivalent CO2, refrigant/quantity: R32/0,9kg
Thermal 9 GWP: 675: 0,95 tonnes equivalent CO2, refrigant/quantity: R32/1,4kg.
Thermal 12 GWP: 675: 1,22 tonnes equivalent CO2, refrigant/quantity:
R32/1,8kg.
14
1. Before use
1.5 Specifications
Thermal 6
Thermal 9
Thermal 12
Note: (1) Heating condition: water inlet/outlet temperature: 30/35, Ambient
temperature: DB 7/WB 6; (2) Heating condition: water inlet/outlet temperature:
40/45, Ambient temperature: DB 7/WB 6; (3) Cooling condition: water
inlet/outlet temperature: 23/18, Ambient temperature: DB 35/WB 24; (4) Cooling
condition: water inlet/outlet temperature: 12/7, Ambient temperature: DB 35/WB
24; (5) The specifications are subject to change without prior notice. For
actual specifications of unit, please refer to the stickers on the unit.
15
2. Assembly Configurations – Flowchart
16
Locate the Configuration that Meets Your Needs
Follow the flowchart on the right in order to locate which of the assembly
configuration matches the needs of the end user, each of which contains
specific assembly and wiring diagrams, with software instructions.
Beginning from the green “Start Here” bubble, follow the appropriate arrows to
each question, which are dependent on the needs of the user.
The corresponding assembly instructions will be found by turning to the page
number in the end bubble.
Note: The instructions in this section are meant to achieve the minimum
requirements for successful system operation only.
For more in-depth settings explanations, please refer to the users manual.
Please ensure that the configuration matches the assembly drawing depicted on
the right for a one temperature zone without domestic hot water setup.
Note: Refer to the next page for wiring and software operation instructions.
Name Temp.Sensor Safety valve Kit Ball valve Water filter Air purging valve
Symbol
Name Water pump Mixing valve Motorized valve Expansion tank
Symbol
Notice: The Fan Coil Unit, Floor Heating System, and Radiator are placeholder distribution systems only and can be substituted by any other appropriate distribution systems.
Note:Dotted lines meanable to be controlled by the Heat Pump.
2. Assembly Configurations – Drawing 1
17
One Temperature Zone ,without DHW
2. Assembly Configurations – Drawing 1
Assembly 1: Wiring Diagram
To achieve successful operation at a minimum, ensure the ports below are
properly connected.
Software: Basic Settings
1.Set the needed working modes of the unit via the menu
2.Temperature configuration options for Heating/Cooling circuit 1 are found
under H.Configuring the set water heating temperatures:
H.1.Setting a heating curve:
H.2. If no heating curve is desired: C.Configuring the set water cooling
temperature (if applicable): 3.Locate and activate the buffer tank and
appropriate pumps under
18
Please ensure that the configuration matches the assembly drawing depicted on the right for a one temperature zone without domestic hot water setup, that includes a component circuit capable of heating or cooling only,through the use of a two-way motorized valve.
Note:
For the cooling-only or heating-only circuit, a motorized two-way valve can be connected to the unit, to cut the water supply during heating or cooling operation.
Refer to the next page for wiring and software operation instructions.
Name Temp.Sensor Safety valve Kit Ball valve Water filter Air purging valve
Symbol
Name
Symbol
Water pump
Mixing valve
Motorized valve Expansion tank Note:Dotted lines meanable to be controlled by the Heat Pump.
Notice: The Fan Coil Unit, Floor Heating System, and Radiator are placeholder distribution systems only and can be substituted by any other appropriate distribution systems.
2. Assembly Configurations – Drawing 2
19
One Temperature Zone ,without DHW,with a heating-only (or cooling-only) circuit,by usage of a motorized 2-way valve
2. Assembly Configurations – Drawing 2
Assembly 2: Wiring Diagram
To achieve successful operation at a minimum, ensure the ports below are
properly connected.
Software: Basic Settings
1.Set the needed working modes of the unit via the menu
2.Temperature configuration options for Heating/Cooling circuit 1 are found
under H.Configuring the set water heating temperatures:
H.1.Setting a heating curve:
H.2. If no heating curve is desired: C.Configuring the set water cooling
temperature (if applicable): 3.Locate and activate the buffer tank and
appropriate pumps under
20
2. Assembly Configurations – Drawing 2
Software: Basic Settings (continued)
4.The location of the configuration for heating-only or cooling-only system is
under
21
2. Assembly Configurations – Drawing 3
22
Please ensure that the configuration matches the assembly drawing depicted on the right for a two temperature zone without domestic hot water setup.
Note:
Refer to the next page for wiring and software operation instructions.
Name Temp.Sensor Safety valve Kit Ball valve Water filter Air purging valve
Symbol
Name Water pump Mixing valve Motorized valve Expansion tank
Symbol
Notice: The Fan Coil Unit, Floor Heating System,and Radiator are placeholder distribution systems only and can be substituted by any other appropriate distribution systems.
Note:Dotted lines meanable to be controlled by the Heat Pump.
Two Temperature Zones ,without DHW
2. Assembly Configurations – Drawing 3
Assembly 3: Wiring Diagram
To achieve successful operation at a minimum, ensure the ports below are
properly connected.
For connection for mixing valve 2,please refers to the appendix A (on page
128-129) of this manual for more information.
Software: Basic Settings
1.Set the needed working modes of the unit via the menu
2.Temperature configuration options for Heating/Cooling circuit 1 are found
under H.Configuring the set water heating temperatures:
H.1.Setting a heating curve:
H.2. If no heating curve is desired: C.Configuring the set water cooling
temperature (if applicable): 3.Locate and activate the buffer tank and
appropriate pumps under
23
Dependent on whether cooling is needed
2. Assembly Configurations – Drawing 3
Software: Basic Settings (continued)
3.(cont.) Configure the water pump to operate for heating or cooling:
4.Temperature configuration options for Heating/Cooling circuit 2 are found
under Please activate entire Heating/Cooling circuit 2 setting
H. Configuring the set water heating temperatures: H.1.Setting a heating
curve:
H.2. If no heating curve is desired: C. Configuring the set water cooling
temperature (if applicable): 4.1.Activate the mixing valve to manage the
second circuit: Note: This pair of settings will interpret “Heating/Cooling
Circuit 2 as the low demand distribution system, requiring a lower set
temperature for heating and higher set temperature for cooling.
24
Please ensure that the configuration matches the assembly drawing depicted on the right for a two temperature zone without domestic hot water setup, that includes a component circuit capable of heating or cooling only,through the use of a two-way motorized valve.
Note:
For the cooling-only or heating-only circuit, a motorized two-way valve can be connected to the unit, to cut the water supply during heating or cooling operation.
Refer to the next page for wiring and software operation instructions.
Name Temp.Sensor Safety valve Kit Ball valve Water filter Air purging valve
Symbol
Name
Symbol
Water pump Mixing valve Motorized valve Expansion tank Note:Dotted lines meanable to be controlled by the Heat Pump.
Notice: The Fan Coil Unit, Floor Heating System, and Radiator are placeholder distribution systems only and can be substituted by any other appropriate distribution systems.
2. Assembly Configurations – Drawing 4
25
Two Temperature Zones ,without DHW,with a heating-only (or cooling-only) circuit,by usage of a motorized 2-way valve
2. Assembly Configurations – Drawing 4
Assembly 4: Wiring Diagram
To achieve successful operation at a minimum, ensure the ports below are
properly connected.
For connection for mixing valve 2,please refers to the appendix A (on page
128-129) of this manual for more information.
Software: Basic Settings
1.Set the needed working modes of the unit via the menu
2.Temperature configuration options for Heating/Cooling circuit 1 are found
under H.Configuring the set water heating temperatures:
H.1.Setting a heating curve:
H.2. If no heating curve is desired: C.Configuring the set water cooling
temperature (if applicable): 3.Locate and activate the buffer tank and
appropriate pumps under
26
Dependent on whether cooling is needed
2. Assembly Configurations – Drawing 4
Software: Basic Settings (continued)
3.(cont.) Configure the water pump to operate for heating or cooling:
4. The location of the configuration for heating-only or cooling-only system
is under
5. Temperature configuration options for Heating/Cooling circuit 2 are found
under H. Configuring the set water heating temperatures: H.1.Setting a heating
curve:
H.2. If no heating curve is desired:
C. Configuring the set water cooling temperature (if applicable): 5.1.
Activate the mixing valve to manage the second circuit: Note: This pair of
settings will interpret “Heating/Cooling Circuit 2 as the low demand
distribution system,requiring a lower set temperature for heating and higher
set temperature for cooling.
27
2. Assembly Configurations – Drawing 5
28
Please ensure that the configuration matches the assembly drawing depicted on the right for a two temperature zone without domestic hot water setup, that utilizes the secondary pump for a heating-only operation.
Note:
For the heating-only circuit, a motorized two-way valve can be connected to the unit,to cut the water supply during heating operation.
Refer to the next page for wiring and software operation instructions.
Name Temp.Sensor Safety valve Kit Ball valve Water filter Air purging valve
Symbol
Name Water pump Mixing valve Motorized valve Expansion tank
Symbol
Notice: The Fan Coil Unit, Floor Heating System, and Radiator are placeholder distribution systems only and can be substituted by any other appropriate distribution systems.
Note:Dotted lines meanable to be controlled by the Heat Pump.
Two Temperature Zones ,without DHW,with a heating-only circuit,enabled by setting the secondary pump to heating-only
2. Assembly Configurations – Drawing 5
Assembly 5: Wiring Diagram
To achieve successful operation at a minimum, ensure the ports below are
properly connected.
For connection for mixing valve 2,please refers to the appendix A (on page
128-129) of this manual for more information.
Software: Basic Settings
1.Set the needed working modes of the unit via the menu
2.Temperature configuration options for Heating/Cooling circuit 1 are found
under H.Configuring the set water heating temperatures:
H.1.Setting a heating curve:
H.2. If no heating curve is desired: C.Configuring the set water cooling
temperature (if applicable): 3.Locate and activate the buffer tank and
appropriate pumps under
29
2. Assembly Configurations – Drawing 5
Software: Basic Settings (continued)
3.(cont.) Configure the water pump to operate for heating or cooling:
4. Temperature configuration options for Heating/Cooling circuit 2 are found
under H. Configuring the set water heating temperatures: H.1.Setting a heating
curve:
H.2. If no heating curve is desired: C. Configuring the set water cooling
temperature (if applicable): 4.1. Activate the mixing valve to manage the
second circuit: Note: This pair of settings will interpret “Heating/Cooling
Circuit 2 as the low demand distribution system,requiring a lower set
temperature for heating and higher set temperature for cooling.
30
Please ensure that the configuration matches the assembly drawing depicted on
the right for a one temperature zone setup that includes domestic hot water.
Note: Refer to the next page for wiring and software operation instructions.
Name Temp.Sensor Safety valve Kit Ball valve Water filter Air purging valve
Symbol
Name
Symbol
Water pump
Notice: The Fan Coil Unit,
Mixing valve
Floor Heating System, and
Radiator are placeholder
Motorized valve
distribution systems only
Expansion tank
and can be substituted by any other appropriate
Note:Dotted lines meanable to be controlled by the Heat Pump.distribution systems.
2. Assembly Configurations – Drawing 6
31
One Temperature Zone ,with DHW
2. Assembly Configurations – Drawing 6
Assembly 6: Wiring Diagram
To achieve successful operation at a minimum, ensure the ports below are
properly connected.
Software: Basic Settings
1.Set the needed working modes of the unit via the menu
2.Temperature configuration options for Heating/Cooling circuit 1 are found
under H.Configuring the set water heating temperatures:
H.1.Setting a heating curve:
H.2. If no heating curve is desired: C.Configuring the set water cooling
temperature (if applicable): 3.Locate and activate the buffer tank and
appropriate pumps under
32
2. Assembly Configurations – Drawing 6
Software: Basic Settings (continued)
4. Double-check to ensure that the Domestic Hot Water option is enabled under
5. Configure the desired setpoint for water temperature (default set to 50°C):
33
2. Assembly Configurations – Drawing 7
34
Please ensure that the configuration matches the assembly drawing depicted on the right for a one temperature zone setup that includes domestic hot water,that also includes a component circuit capable of heating or cooling only, through the use of a two-way motorized valve.
Note:
For the cooling-only or heating-only circuit, a motorized two-way valve can be connected to the unit, to cut the water supply during heating or cooling operation.
Refer to the next page for wiring and software operation instructions.
Name Temp.Sensor Safety valve Kit Ball valve Water filter Air purging valve
Symbol
Name
Symbol
Water pump
Notice: The Fan Coil Unit,
Floor Heating System, and
Mixing valve
Radiator are placeholder
Motorized valve
distribution systems only and can be substituted by
Expansion tank
any other appropriate
distribution systems.
Note:Dotted lines meanable to be controlled by the Heat Pump.
One Temperature Zone ,with DHW,with a heating-only (or cooling-only) circuit,by usage of a motorized 2-way valve
2. Assembly Configurations – Drawing 7
Assembly 7: Wiring Diagram
To achieve successful operation at a minimum, ensure the ports below are
properly connected.
Software: Basic Settings
1.Set the needed working modes of the unit via the menu
2.Temperature configuration options for Heating/Cooling circuit 1 are found
under H.Configuring the set water heating temperatures:
H.1.Setting a heating curve:
H.2. If no heating curve is desired: C.Configuring the set water cooling
temperature (if applicable): 3.Locate and activate the buffer tank and
appropriate pumps under
35
2. Assembly Configurations – Drawing 7
Software: Basic Settings (continued)
4.The location of the configuration for heating-only or cooling-only system is
under
5. Double-check to ensure that the Domestic Hot Water option is enabled under
6. Configure the desired setpoint for water temperature (default set to 50°C):
36
Please ensure that the configuration matches the assembly drawing depicted on
the right for a two temperature zone setup that includes domestic hot water.
Note: Refer to the next page for wiring and software operation instructions.
Name Temp.Sensor Safety valve Kit Ball valve Water filter Air purging valve
Symbol
Name
Symbol
Water pump Mixing valve Motorized valve Expansion tank
Notice: The Fan Coil Unit, Floor Heating System, and Radiator are placeholder distribution systems only and can be substituted by any other appropriate distribution systems.
Note:Dotted lines meanable to be controlled by the Heat Pump.
2. Assembly Configurations – Drawing 8
37
Two Temperature Zone ,with DHW
2. Assembly Configurations – Drawing 8
Assembly 8: Wiring Diagram
To achieve successful operation at a minimum, ensure the ports below are
properly connected.
For connection for mixing valve 2,please refers to the appendix A (on page
128-129) of this manual for more information.
Software: Basic Settings
1.Set the needed working modes of the unit via the menu
2.Temperature configuration options for Heating/Cooling circuit 1 are found
under H.Configuring the set water heating temperatures:
H.1.Setting a heating curve:
H.2. If no heating curve is desired: C.Configuring the set water cooling
temperature (if applicable): 3.Locate and activate the buffer tank and
appropriate pumps under
38
Dependent on whether cooling is needed
2. Assembly Configurations – Drawing 8
Software: Basic Settings (continued)
3.(cont.) Configure the water pump to operate for heating or cooling:
4. Temperature configuration options for Heating/Cooling circuit 2 are found
under H. configuring the set water heating temperatures:
H.1. Setting a heating curve:
H.2. If no heating curve is desired:
C. Configuring the set water cooling temperature (if applicable): 4.1.
Activate the mixing valve to manage the second circuit: Note: This pair of
settings will interpret “Heating/Cooling Circuit 2 as the low demand
distribution system,requiring a lower set temperature for heating and higher
set temperature for cooling. 5. Double-check to ensure that the Domestic Hot
Water option is enabled under
6. Configure the desired setpoint for water temperature (default set to
50°C):
39
2. Assembly Configurations – Drawing 9
40
Please ensure that the configuration matches the assembly drawing depicted on the right for a two temperature zone setup that includes domestic hot water, also that includes a component circuit capable of heating or cooling only, through the use of a two-way motorized valve.
Note:
For the cooling-only or heating-only circuit, a motorized two-way valve can be connected to the unit, to cut the water supply during heating or cooling operation.
Refer to the next page for wiring and software operation instructions.
Name Temp.Sensor Safety valve Kit Ball valve Water filter Air purging valve
Symbol
Name
Symbol
Water pump Mixing valve Motorized valve Expansion tank Note:Dotted lines meanable to be controlled by the Heat Pump.
Notice: The Fan Coil Unit, Floor Heating System, and Radiator are placeholder distribution systems only and can be substituted by any other appropriate distribution systems.
Two Temperature Zones ,without DHW,with a heating-only (or cooling-only) circuit,by usage of a motorized 2-way valve
2. Assembly Configurations – Drawing 9
Assembly 9: Wiring Diagram
To achieve successful operation at a minimum, ensure the ports below are
properly connected.
For connection for mixing valve 2,please refers to the appendix A (on page
128-129) of this manual for more information.
Software: Basic Settings
1.Set the needed working modes of the unit via the menu
2.Temperature configuration options for Heating/Cooling circuit 1 are found
under H.Configuring the set water heating temperatures:
H.1.Setting a heating curve:
H.2. If no heating curve is desired: C.Configuring the set water cooling
temperature (if applicable): 3.Locate and activate the buffer tank and
appropriate pumps under
41
Dependent on whether cooling is needed
2. Assembly Configurations – Drawing 9
Software: Basic Settings (continued)
3.(cont.) Configure the water pump to operate for heating or cooling:
4. The location of the configuration for heating-only or cooling-only system
is under
5. Temperature configuration options for Heating/Cooling circuit 2 are found
under H. configuring the set water heating temperatures:
H.1. Setting a heating curve:
H.2. If no heating curve is desired: C. Configuring the set water cooling
temperature (if applicable): 5.1. Activate the mixing valve to manage the
second circuit: Note: This pair of settings will interpret “Heating/Cooling
Circuit 2 as the low demand distribution system,requiring a lower set
temperature for heating and higher set temperature for cooling. 6. Double-
check to ensure that the Domestic Hot Water option is enabled under 7.
Configure the desired setpoint for water temperature (default set to 50°C):
42
Please ensure that the configuration matches the assembly drawing depicted on
the right for a two temperature zone setup that includes domestic hot water,
also that utilizes the secondary pump for a heating-only operation.
Note: For the heating-only circuit, a motorized two-way valve can be connected
to the unit, to cut the water supply during heating operation.
Refer to the next page for wiring and software operation instructions.
Name Temp.Sensor Safety valve Kit Ball valve Water filter Air purging valve
Symbol
Name
Symbol
Water pump Mixing valve Motorized valve Expansion tank
Notice : The Fan Coil Unit, Floor Heating System, and Radiator are placeholder distribution systems only and can be substituted by any other appropriate distribution systems.
Note:Dotted lines meanable to be controlled by the Heat Pump.
2. Assembly Configurations – Drawing 10
43
Two Temperature Zones ,without DHW,with a heating-only circuit,by setting the secondary pump to heating-only
2. Assembly Configurations – Drawing 10
Assembly 10: Wiring Diagram
To achieve successful operation at a minimum, ensure the ports below are
properly connected.
For connection for mixing valve 2,please refers to the appendix A (on page
128-129) of this manual for more information.
Software: Basic Settings
1.Set the needed working modes of the unit via the menu
2.Temperature configuration options for Heating/Cooling circuit 1 are found
under H.Configuring the set water heating temperatures:
H.1.Setting a heating curve:
H.2. If no heating curve is desired: C.Configuring the set water cooling
temperature (if applicable): 3.Locate and activate the buffer tank and
appropriate pumps under
44
2. Assembly Configurations – Drawing 10
Software: Basic Settings (continued)
3.(cont.) Configure the water pump to operate for heating or cooling:
4. Temperature configuration options for Heating/Cooling circuit 2 are found
under H. configuring the set water heating temperatures:
H.1. Setting a heating curve:
H.2. If no heating curve is desired: C. Configuring the set water cooling
temperature (if applicable): 4.1. Activate the mixing valve to manage the
second circuit:
Note: This pair of settings will interpret “Heating/Cooling Circuit 2 as the
low demand distribution system,requiring a lower set temperature for heating
and higher set temperature for cooling. 5. Double-check to ensure that the
Domestic Hot Water option is enabled under
6. Configure the desired setpoint for water temperature (default set to
50°C):
45
3. Installation
3.1 General application system introduction
3.1.1 Sanitary hot water For safety purpose, it is recommended to set up the
sanitary hot water system as shown below:
- Application 1 Magnesium rod
Water from heat pump
T/P valve Water mixture valve
Water to heat pump
City water After heat pump is connected directly with the tank, city water
will be heated up by hot water in the tank when it runs through a long coil
inside the tank.
Disadvantage of this application is that heat is transferred from hot water in
the tank to city water in the coil, thus it will have less volume of sanitary
hot water available compared with other solutions. The advantages of this
application is: A. Heat pump is connected with tank directly, so it can
effectively ensures the water flow rate inside heat
pump system. B. Sanitary hot water is heated up by going through the coil,
which makes it un necessary to have
sanitization. This will help the system save more energy.
46
3. Installation
2) Application 2
Magnesium rod
T/P valve
High temperature hot water export
Water mixture valve
Water from heat pump
Water to heat pump City water
By connecting the set of coil with heat pump directly, the safety of sanitary
hot water inside the tank, is also ensured.
However, the capacity of the coil should be bigger than the maximum output of
the unit (heat pump output at A7/W45). Usually this solution is used for
working together with a heat pump whose capacity is less than 14kW.
The advantage of this application is that it can supply bigger volume of hot
sanitary hot water.
The disadvantage of this application is that this coil may create big water
flow resistance to heat pump water circuit. Thus it may need to add a
secondary water pump to ensure the flow rate of heat pump unit. Otherwise it
may affect unit efficiency or make the unit work improperly.
47
3. Installation
3) Application 3 A water to water plate heat exchanger can be used instead of
the coil inside water tank, as shown below:
Magnesium rod
T/P valve
Water mixture High temperature hot water export valve
Water to water plate heat exchanger
Water from heat pump
Water to heat pump City water
With this application, it can not only ensure the volume of high temperature
hot water, but also ensure the water flow rate of heat pump system. But the
total cost will be higher than other two applications due to the cost the
plate heat exchanger.
For all these three applications, it is recommended to add a manual mixture
valve between city water inlet and water tank sanitary hot water outlet. This
can maximize the utilization of hot water in the tank and also ensures its
temperature won’t be too high to burn people.
If the structure of the tank permits, it is suggested to use a manual 4-way mixture valve in sanitary hot water system as shown below. This can further improve the utilization of hot water in the tank.
Magnesium rod
T/P valve
Water inlet from heat pump
4-Way water mixture valve
Water inlet from heat pump
City water
48
3. Installation
3.1.2 Heater /cooling distribution system Note: Buffer tank is always
recommended to be included in the system , especially when the distribution
system has water volume less then 20L/W. It should be installed between heat
pump and distribution system , in order to: 1) Ensure heat pump unit has
stable and enough water flow rate. 2) Store heat to minimize fluctuation of
system heating/cooling load. 3) Extend the water volume of distribution system
for proper working of heat pump unit.
If distribution system has enough water volume and can ensure the water flow
rate of heat pump system , buffer tank can be excluded in the system . But in
this way , please move temperature sensor Tc (Cooling/heating temperature
sensor ) to water return pipe to minimize the fluctuation of water temperature
caused by compressor speed changes.
M1
M
16
T/P valve
BFT
7
M2
T/P valve
FLH1 FLH2 FLH3
18 High temperature
hot water export
21
HWT
17
Drainage
20 City water
Item
Name
1 Monoblock unit
2 Indoor control unit
3 Buffer tank
4 Sanitary hot water storage tank
5 Motorized 3-way valve
6 Mixture valve 1 (0~10V)
7 Mixture valve 2 (0~10V)
8 Circulation pump
9 Sanitary hot water circulation pump(if need)
10 Circulation pump for distribution system 1
11 Circulation pump for distribution system 2
12 AH-Auxilary heater inside unit
13 HBH-Heating Back-up Heater
14 HWTBH-Hot Water Tank Back-up Heater
15 Sanitary hot water mixture valve
Item
Name
16 Safety valve kit
17 Ball valve
18 Pressure meter
19 Motorized 2-way valve
20 Filter
21 One-way valve
TW Hot water temperature
TC Cooling or heating water temperature
TR Room temperature
Tuo Monoblock unit outlet water temperature
Tui Monoblock unit return water temperature
Tup Monoblock unit coil temperature
Tv1 Temperature of water after mixture valve 1
Tv2 Temperature of water after mixture valve 2
49
3. Installation
3.1.3 Heating&Cooling Circuits:
This heat pump unit can control two totally different heating/cooling circuit,
as shown in the drawing. Temperature setting can be made via menu “Heating &
Cooling Circuit 1” and “Heating & Cooling Circuit 2”. Of course, if only one
circuit is needed, “heating&cooling circuit 2” in system drawing can be omit,
and leave the “Heating&cooling Circuit 2” under “heating&cooling circuit 2”
set to OFF:
3.1.4 Heating & Cooling Circuit 1
Control of Mixing Valve 1(MV1): If system water temperature may higher(lower)
than temperature that are need for circuit 1 in heating (cooling) operation,
then a mixing valve can be add to circuit 1, and connected to MV1 port in
indoor unit. Unit will control the mixing valve, mix the supply and return
water of circuit 1 to have the temperature read via sensor TV1 get to value
set under menu “Heating & Cooling Settings circuit1”. If so, TV1 under menu
“”Heating & Cooling circuit1” should be activated under installer’s level:
50
3. Installation
Note: If TV1 is not connected, while it is activated via setting here, unit
will show relative failure code. 3.1.5 Heating & Cooling circuit 2 Control of
Mixing Valve 2(MV2): If system water temperature may higher(lower) than
temperature that are need for circuit 2 in heating (cooling) operation, then a
mixing valve can be added to circuit 2, and connected to MV2 port in indoor
unit. Unit will control the mixing valve, mix the supply and return water of
circuit 2 to have the temperature read via sensor TV2 get to value set under
menu “Heating & Cooling Settings circuit 2”. If so, TV2 under menu “Heating &
Cooling Settings circuit 2” should be activated under installer’s level:
Note: If TV2 is not connected, while it is activated via setting here, unit
will show relative failure code.
Tips: When Mixing valve is needed? In general, if system water temperature may
higher(lower) than temperature that are need for this circuit, then a mixing
valve is needed.
A.If a system has two circuits, these two circuits may require different water
temperatures. Heat pump has to take the higher(lower) setting among two
circuits as the set temperature for heat pump when it works in
heating(cooling). Thus, a mixing valve is needed for the circuit that with
lower(higher) setting to ensure it gets water with correct temperature
circulates in the circuit.
B.If a system has other heating source inside that is out the control of heat
pump (e.g. Solar system), as the actual water temperature may exceed the set
temperature of heat pump, a mixing valve is also needed to ensure the circuit
gets water with correct temperature circulates in the circuit.
51
3. Installation
Control of Circu lation Pum p for circu it 1&2:
“With/without Buffer Tank”: Set whether it has a buffer tank between heat pump
unit and distribution system or not. “P1 for Heating Operation” means circuit
pump for circuit 1should work for heating operation. “P1 for Cooling
Operation” means circuit pump for circuit 1should work for cooling operation.
“P2 for Heating Operation” means circuit pump for circuit 2 should work for
heating operation. “P2 for Cooling Operation” means circuit pump for circuit 2
should work for cooling operation. If “without buffer tank” is set, both
P1(circulation pump for circuit 1) and P2(circulation pump for circuit 2) will
only work when compressor is working in the same mode as the pump is set to.
For example, if P1 is set to “P1 for Heating Operation”, P1 will be turned ON
only when compressor is working in heating mode. If both “P1for Heating
Operation” and “P1 for Cooling Operation” are both selected, P1 will be turned
ON when compressor is working in both heating and cooling mode. When heat pump
switches to DHW mode or stops after get the set temperature for heating or
cooling, pump stops.
If “with buffer tank” is set, both P1(circulation pump for circuit 1) and
P2(circulation pump fo circuit 2) will work once the distribution system has
the heating or cooling demand, as per the pump setting, and obeys following
rules:
Actual temperature in buffer tank detected via Tc 20 in heating. Only 20 and
above can be useful for distribution system in heating operation.
Actual temperature in buffer tank detected via Tc 23 in cooling. Only 23 and
below can be useful for distribution system in cooling operation. For example,
if P1 is set to “P1 for Heating Operation”, P1 will start to work as long as
the system has heating demands and Tc reading is no lower than 20 ,even if the
unit is working in DHW mode or stops after get the set temperature.
“Working of P1(2) with High Demanding Signal” means whether P1(P2) should stop
if signal for “high demanding” is off. For detailed meaning of “High Demanding
Signal”, please refers to part “D” of “Terminal Block 4” of chapter “2.5.1”,
“High demanding distribution system switch”.
3.1.6 Room temperature sensor:
Room temperature sensor (Tr) is recommended to be placed in a ideal position
of the house to check the room temperature. Thus the unit can have room
temperature control mode (please refers to 9.04 Basic Operation), and room
temperature compensate function (please refers to 1.16 Room temp. effect on
Heating Curve).
52
3. Installation
3.2 Tools needed
Most people already have the tools needed for installation: spirit level,
pencil, crosshead screwdriver, drill, 8 mm. concrete drill bit, detection
drill, square, tape measure or ruler, tape width 65 mm, hole saw about 80 mm
(deviation in size may occur), knife and two adjustable spanners or pliers
(and possibly torque wrench).
The installation of the product should be handled by professional installers or under their instructions.
3.3 Installation of the indoor control unit
3.3.1 Installation notes 1) The indoor control unit should be installed
indoors and mounted on the wall, with water outlet
downwards. 2) The indoor control unit shall be placed in dry and well-
ventilated environment. 3) Indoor control unit mustn’t be installed in an
environment where volatile, corrosive or flammable liquid
or gas exists. 4) Enough space should be left around the indoor control unit
for futher maintenance.
Please choose a suitable position to install the indoor control unit as
follows:
500mm
100mm
100mm
600mm
53
3. Installation
3.3.2 Installation Indoor control unit should be mounted on the wall as per
procedures below: 1) Take out the expansion bolts and mounting board from
accessory and put the mounting board on the
wall horizontally; Mark on the wall the location for bolts through the holes
on mounting board. 2) Drill holes with proper diameter for expansion bolts. 3)
Unscrew the nuts out from the expansion bolts. 4) Fix the mounting board on
the expansion bolts a little bit, but don’t be too tight. 5) Use a hammer to
pound the expansion bolts into the drilled holes. Fasten the nuts by turning
the wrench
to fix the mounting board on the wall. 6) Hang the indoor control unit onto
the mounting board and make sure it’s placed well before you let go
your hands. The installation is finished.
1
2
3
4
5
6
Note: You must choose very firm wall for installation otherwise the bolts may
get loose and unit be damaged!
If it’s wood wall, please use self-tapping screws in accessory instead of
expansion bolts. Please hang the mounting board directly onto the wood wall
without drilling holes. The wood wall must be firm enough. Wood walls that are
too thin, too brittle or humid are not adequate for installation.
54
3. Installation
3.4 Installation of the monoblock unit
3.4.1 Installation notes 1) The monoblock unit can be located in a open space,
corridor, balcony, and roof. 2) The monoblock unit shall be placed in dry and
well-ventilated environment; If the monoblock unit is
installed in humid environment, electronic components may get corroded, or
short-circuited because of heavy humidity. 3) Monoblock unit mustn’t be
installed in an environment where volatile, corrosive or flammable liquid or
gas exists. 4) Please don’t install monoblock unit close to bedroom or living
room, because there is some noise when it’s running. 5) When installing the
unit in harsh climatic conditions, sub-zero temperatures, snow, humidity…,
please raise the unit above the ground by about 50cm. It’s recommended to
install an awning above the monoblock unit, to protect the snow from clogging
in the air inlet and outlet and ensure the normal running. 6) Please ensure
there is drainage system around the location, to drain the condensate water
under defrosting mode. 7) When installing the unit, tilt it by lcm/m for rain
water evacuation. 8) Install monoblock unit far away from the exhaust port of
kitchen, to avoid oil smoke entering into monoblock unit and adhering to heat
exchanger. It’s hard to clean up. 9) Please don’t install the indoor control
unit and monoblock unit in damp locations, otherwise it may cause short-
circuit or corrosion of some components. The unit should be free from
corrosive and moisture surrounding. Otherwise the lifetime of the unit might
be shortened. 10) Please ensure enough space around the monoblock unit, for
better ventilation and maintenance. Please refer to the illustration below.
500mm 400mm
1500mm (Front space)
150mm(Back space 500mm
650mm
500mm (Above ground)
55
3. Installation
3.4.2 Installation User can either use the dedicated mounting bracket from the
supplier, or prepare a suitable bracket for the unit installation. Make sure
the installation meets following requirements:
- The unit must be installed on flat concrete blocks, or a dedicated mounting bracket. The bracket should be able to support at least 5 times of unit’s weight.
- All nuts must be tightened after the bracket is fixed; otherwise, it may
cause damage to the equipment. 3) User should double check and make sure the
installation of unit is firm enough. 4) The bracket can be of stainless steel,
galvanized steel, aluminum and other materials as required by the
user. 5) Besides the mounting bracket, the user can also install the monoblock unit on two concrete blocks, or a
raised concrete platform. Please make sure that the unit is securely fastened after installation. 6) Please see the dimensions of monoblock unit when choose a suitable wall bracket.
500mm
Hole for piping kits should lean to outside a little bit (8 degrees), to keep rain water or condensate water from flowing back indoors.
Sleeve 8°
Shield
56
3. Installation
3.5 Accessories
Accessories below are delivered together with the product . Please check in
time. If there is any shortage or damage, please contact local distributor.
Name User’s manual Drain pipe Safety valve kit
Quantity 1 1 1
Picture
User Manual
Name TR-Room temperature sensor
TC-water temperature sensor for cooling and heating
TW-water temperature sensor for sanitary hot water TV1-water temperature
sensor after mixture valve 1 TV2-water temperature sensor after mixture valve
2 Communication cable between indoor control unit and monoblock unit
Communication cable Signal cable between indoor control unit and monoblock
unit
Quantity 1 1 1 1 1 8 1
Name Indoor control unit bracket
Expansion bolts
Quantity 1 2
Picture
Picture
57
3. Installation
3.6 Wiring
2.6.1 Explanation of terminals 1) Terminal block 1
For user’s side
PE N L PE N1 L1 PE N2 L1 L2 L3 PE N3 L1 L2 L3 PE N L
A
B
C
A: Unit power supply (Power Cord: H05VV-F 3×2.5mm2) Unit power supply. Should be connected to city power input.
D
E
B: Power supply for AH-Auxiliary heater inside unit(Power Cord: H05VV-F
3×1.5mm2, city power input)
This should be connected to city power supply, 1 phase. It is for giving the
power to auxiliary heater inside the indoor control unit.
Terminal block 1-B
PE N1 L1
AH Power Input
AH Power Output
AH
City power supply
C: Power supply for HWTBH-Hot Water Tank Back-up Heater(Power Cord: H05VV-F
3×1.5mm2, city power input)
If sanitary hot water tank has electric heater inside, one can connect this
heater to heat pump unit, so to have it under the control of heat pump. In
that way, city power input (1 phase or 3 phase) should be connected to this
port “Electrical Heater Power Supply for Hot Water 5×1.5mm2”.
58
3. Installation
Terminal block 1-C
PE N2 L1 L2 L3
HWTBH Power Input
Terminal block 2-E
PE N2 L12 L22 L32
HWTBH Power Output
City power supply
And then connect electric heater inside sanitary hot water tank to port D on
terminal block 2.
D: Power supply for HBH-Heating Back-up Heater (Power Cord: H05VV-F 5×1.5mm2,
city power input)
When the house heating system also has a electric heater as a back-up, then
this heater can also be connected to heat pump unit and under heat pump’s
control. In that way, city power input (1 phase or 3 phase) should be
connected to this port “Reserved Electrical Heater Power Supply 5×1.5mm2”, and
then heater should be connected to port E on terminal block 2. PS: If external
heating source (on house heating circuit or hot water circuit) is not electric
heater but other heating sources, we can also connect it to the heat pump like
this if they can be controlled by electric signal, to have them under the
control of heat pump.
Terminal block 1-D
PE N3 L1 L2 L3
HBH Power Input
Terminal block 2-F
PE N3 L13 L23 L33
HBH Power Output
City power supply
E: Monoblock unit power supply (Power Cord: H05VV-F 3×2.5mm2, output)
Monoblock unit power cable should be connected with these terminals so to get
power from indoor control unit.
59
3. Installation
2) Terminal block 2
PE
For user’s side
P1 PE
P2 PE
P3 PE N2 L12 L22 L32 PE N3 L13 L23 L33
A
B
C
D
E
A,B,C: Water Pump A-Pump 1: Circulation pump(heating) B-Pump 2: Circulation
pump(cooling) C-Pump 3: Circulation pump(hot water) Pump 0: DC pump inside the
indoor control unit. If there is an external water pump in heating, cooling
and hot water system, it can be connected to these ports, to be under the
control of heat pump,
D: Power supply for HWTBH-Hot Water Tank Back-up Heater (Power Cord: H05VV-F
3×1.5mm2, power output)
Refer to explanation of port C of terminal block 1.
E: Power supply for HBH-Heating Back-up Heater (Power Cord: H05VV-F 5×1.5mm2,
power output) Refer to explanation of port D of terminal block 1.
60
3. Installation
Explanation of connectors for other heating sources A: HWTBH-Hot water tank
back-up heater Terminal block 1-C
Terminal block 2-D
PE N2 L1 L2 L3
HWTBH Power Input
PE N2 L12 L22 L32
HWTBH Power Output
City power supply
B: HBH-Heating back-up heater Terminal block 1-D
PE N3 L1 L2 L3
HBH Power Input
Terminal block 2-E
PE N3 L13 L23 L33
HBH Power Output
City power supply
61
3. Installation
3) Terminal block 3
Application Side
G A B 12V G 24VCOM 1 G 24V COM 2
A
B
C
A: Signal cable to monoblock unit Please connect A and B together with A and B
on monoblock unit.
B,C: Motorized Water mixture valve 1&2: As explained in System illustration
chapters, this unit can have two water mixture valves for distribution system
under its control.
Water Mixture Valve 1 for Heating & Cooling circuit 1 Water Mixture Valve 2
for Heating & Cooling circuit 2
62
3. Installation
4) Terminal block 4
Application Side
COM ES COM CS COM HS COM TH
A
B
C
D
D: Electrical Utility Lock Input Some electricity companies offer a special rate if the house power consumption is lowered to a certain value during peak time. If the unit is supposed to stop working during this period, one can connect the signal from electricity company to this “External Shutdown” port and use the parameter setting to activate this function.
E,F: Cool mode & heat mode switch-over This unit can switch over between heating and cooling functions automatically, according to ambient temperature, or external signal input. For ambient temperature switching, please refer to part 1.06 of introduction of user’s interface for detailed setting. For external signal input, external signal should be connected to “COOL MODEL SWITCH” for cooling operation, and “HEAT MODE SWITCH” for heating operation.
G: High demanding distribution system switch
When two heating distribution systems are connected, unit should always take
the set temperature for high demanding circuit, which needs higher temperature
in heating and lower temperature in cooling operation, as the set temperature
for the heat pump unit.
However, when this high demanding circuit is not needed or has reached the set
temperature, heat pump unit can switch the heat pump set temperature to the
values set for the other circuit, for better efficiency.
This set of connector is used to receive the signal from high demanding
circuit, if has.
When “CLOSE” signal is received, unit works with high demanding. When “OPEN”
signal is received, unit works with low demanding.
63
3. Installation
3.6.2 Wiring
It is recommended to use a suitable circuit breaker for the heat pump; The
power supply to the heat pump unit must be grounded. The wiring should be done
by professional person. The wiring should be comply with the local industry
regulation. The wiring should be done after the unit is powered off. Cable
should be fixed tightly, to ensure it won’t get loose. Don’t connect several
parts of cables together to use. Make sure the power supply in the local
coincide with the power supply marked in rating label. Make sure power supply,
cable and socket can meet the requirement of the input power of the unit.
Installation sketch
Signal cable between indoor control and monoblock unit
Auxiliary Heater power cable
Main power in user side
Power cable between indoor control and monoblock unit
Heat pump unit power supply
Sensor cable
64
3. Installation
Before wiring, open the indoor control unit front panel and take off the
electronic box cover.
- Heat pump unit power supply Get a power cable in suitable length that complies to the local safety regulations.
L N PE
C
B A
A. Insert one end of this cable through the cable gland on bottom of the
indoor control unit, and connect it with heat pump power supply terminals (PE,
N, L).
B. Fasten the cable gland to ensure the cable won’t get loosen.
C. Connect the other end to the city power supply.
65
3. Installation
2) Auxiliary Heater power cable Get a power cable in suitable length that
complies to the local safety regulations.
L1 N1 PE
C
B A
A. Insert one end of this cable through the cable gland on bottom of the
indoor control unit, and connect it with AH power supply terminals (PE, N1,
L1).
B. Fasten the cable gland to ensure the cable won’t get loosen.
C. Connect the other end to the city power supply.
66
3. Installation
3) Signal cable between indoor control unit and monoblock unit 10M
communication cable is packed in accessories bag.
B A
C
AB corresponding with each other
A. Insert one end of this cable through the cable gland on bottom of the
indoor control unit, and connect this cable to A and B on terminal block. B.
Fasten the cable gland to ensure the cable won’t get loosen. C. Take off the
top cover , and connect the other end of communication cable to correspondent
terminal block through cable gland. Fix the cable with cable gland after cable
is well connected. A and B on monoblock unit should be connected with A and B
on indoor control unit, otherwise unit will show communication failure.
67
A B
3. Installation
4.1) Power cable between indoor control unit and monoblock unit Prepare a 3
cores power cable with suitable length that complies the local safety
regulations,
B A
C
Shown as “Outdoor power supply” on wiring diagram
A. Insert one end of this cable through the cable gland on bottom of the
indoor control unit, and connect this power cable to “Outdoor power supply” on
indoor control unit terminal block. B. Fasten the cable gland to ensure the
cable won’t get loosen. C. Connect cable between indoor control unit and
monoblock unit to correspondent terminal block according to the wiring
diagram. Fasten the cable gland to ensure the cable won’t get loosen. When
connecting the power cable between the monoblock unit and indoor control unit,
cables connected to the terminal block in indoor control unit must match these
in monoblock unit. For example, if the terminals and power cables are
connected as gree/yellow cable, Lred cable, Nblue cable, Sblack cable in
indoor control unit, the connections in the monoblock unit should be in the
same way.
68
3. Installation
5) Sensor cables Take all sensors and communication cables out from the
accessories bag. Connect the sensors together with the quick connectors on
communication cables and insert the end with the connector into the indoor
unit through cable gland. Connect them with the quick connector inside the
indoor unit and place all sensors in right positions. Fasten the cable gland
after installations.
Sensor cable connection Indoor control PCB
Communication cable
Sensor
Place all sensors in right positions
COM TW COM TC COM TR COM TV1 COM TV2 COM TUP COM TUI COM TUO
A
B
TW-Water temperature sensor for sanitary hot water
TC-Water temperature sensor for cooling and heating Connect these sensors with communication cables by quick connector, and then connect
A TR-Room temperature sensor
communication cable (the end without quick connector) with terminal block. (These
sensors are packed inside the accessories TV1-Water temperature sensor after mixture valve 1 bag).
TV2-Water temperature sensor after mixture valve 2
TUP-Coil temperature sensor B TUI-Water inlet temperature sensor
TUO-Water outlet temperature sensor
Connect these sensors with communication cables by quick connector, and then connect communication cable (the end without quick connector) with terminal block. (These sensors are installed already, but should be connected to terminal block inside indoor control box via communication cables).
69
3. Installation
Install the electric box cover on indoor control unit and electric box cover
on monoblock unit back, and close the door of indoor control unit.
70
3. Installation
3.7 Installation of safety valve kit
- Install the safety valve kit to the connector on top of indoor control unit.
- Connect the drainage pipe to safety valve outlet. Safety valve outlet
- Have the drainage pipe out from the hole on the bottom by going through the
unit. Drainage pipe in
Drainage pipe out
71
3. Installation
3.8 Water pipe connection
After installing the unit, please connect the water inlet and outlet pipe
according to the local regulations. Please carefully select and operate the
water pipe. After connection, the water piping should be pressure tested,
cleaned before use.
- Filter A mesh filter must be installed in front of the water inlet of the unit and water tank, to keep the water quality and collect impurity contained in the water. Take care to keep the water filter mesh towards the bottom. Check valve is recommended to be installed at both sides of the filter, so as to clean or change the filter in a easier way.
Connect to unit water inlet
One way valve Drain pipe
Filter
Ball valve
City water inlet
- Insulation All pipes running hot water should be well insulated. The
insulation must be tied up tightly without gap (But please don’t wrap up the
check valve for future maintenance).
Please ensure enough water pressure to send the water to the required height. If the water pressure is not enough to maintain proper water flow rate for the system, please add a water pump to increase the pumping head. - Requirements of water quality A. Chloridion element in the water should be
less than 300ppm(temperature is less than 60). B. PH value of water should be
from 6 to 8. C. The water with ammonia can’t be used for the unit.
If the water quality is bad, or water flow too little, scale formation or clogging may happen after unit running for a long time, then the efficiency of cooling or heating will be low or the unit will work abnormally. Please clean water before use, or use purified water. Make sure the water quality is good enough to keep the unit long-term running in high efficiency.
72
3. Installation
3.9 Test run
After installation finished, please fulfill the water system with water and
purge out air in the system before start-up.
- Before start-up Before the unit starts up, a certain number of
verifications must be performed on the installation to ensure that the unit
will operate under the best possible conditions. The check list below is not
exhaustive and should only be used as a minimum reference basis: A. Make sure
fan rotates freely; B. Inspect all water piping for flow direction; C. Verify
all system piping is correct for operation as per installation requirements;
D. Check voltage of the unit power supply and make certain voltage is within
authorized limitations; E. Make sure the unit is properly grounded; F. Check
the presence of protective and breaking devices; G. Check all electric
connections for tightness. H. Check all piping for leaks and air is well
ventilated.
If everything above is OK, the unit can start up. If any of them fails, please fix it. - Pre-start up A. When the installation of unit is completed, water system
pipes are well connected and air purging is
done, no leakage or other problems, the unit can be powered to start up. B. Turn on the unit, press the on-off button on the operation panel to start the unit. Please check carefully
if there is some abnormal noise or vibration, or the display of wired controller is normal or not. C. After the unit is working properly for 10 minutes, without any problem, then the pre-start up is
completed; If not, please refer to the Service and Maintenance chapter in this manual to solve the problems.
It is suggested not to run “heating” or “hot water” mode, when ambient temperature is over 32 ,otherwise unit may go into protection mode easily.
73
4. Usage
4.1 Introduction of operation panel
A. Communication symbol
F. Touch screen panel
G. Mode
26
15
34.7
23.9
START ENGING
STOP
6.8
B. Working mode C. Functions D. Warning E. ON/OFF
H. Setting
A. Communication symbol When this symbol is in blue, it means communication is
working correctly. When this symbol is grey, it means communication is broken.
B. Working mode Working mode switching symbol is ON when system working mode
is under switching. If more than one working mode are activated at the same
time, correspondents working mode symbol will be shown on the display.
Heating mode Cooling mode Hot water mode
C. Functions Sleep mode Interruption Sanitary hot water storage mode Preheating mode Sanitization mode Defrosting mode
74
4. Usage
D. Warning When the unit is having a protection or failure, a symbol will be
shown on the display. Please enters into “Info” menu to check the protection
or failure codes. Yellow—-Outdoor unit protection or failure
Red—-System protection or failure
Some information, protections and failures that are more likely to happen,
will shown in front page so the customer can see it easier:
1. Coil Temp. too low This is indoor coil temperature too low. This happens
in cooling operation of the unit. Too low coil temperature may make the water
freeze up inside plate heat exchanger and cause damage. Compressor speed down
if coil temp. lower than 2; Compressor stops if coil Temp. lower than -1;
Compressor restarts if coil Temp. higher than 6. When this happens, please: A.
Check whether set temperature for cooling is too low; whether system has too
small water flow rate; check water system especially the filter. B. Check
whether system has not enough refrigerant inside by measuring the evaporating
pressure. C. Check whether ambient temperature is lower than 15.
2. Water flow rate too small System water flow rate is less than minimum
allowable flow rate. Check the water system, especially the filter; check the
working statue of water pump.
3. Water flow switch failure Water flow switch should be in open mode when
unit circulation pump is working. If not, the unit think the flow switch
itself is broken. Check whether flow switch is broken or not well connected.
Check whether there has another pump that circulates the water through the
unit, when unit circulation pump is working.
4. Communication Failure! Communication failure shown here means the
communication between operation panel, indoor PCB and outdoor PCB have been
set up, but communication data lost too much. Check whether communication
cable is longer than 30M; whether there has a source of the disturbance nearby
the unit. Unit recovers when communication recovers.
75
4. Usage
5. Serial port connect error Serial port connect error means the
communication between operation panel and indoor PCB or outdoor PCB hasn’t
been set up successfully. Check the cable connection in between. Check whether
the last three switches on outdoor power PCB are set to 001; whether last
three switches on indoor PCB are set to 001. Unit recovers when communication
recovers.
6. Cooling water Temp. too low Compressor stops if water outlet is lower than
5 in cooling mode. This too low water temperature may make the water freeze up
inside plate heat exchanger and cause damage. Check whether temperature sensor
Tc is OK and well connected; whether set water temperature too low; whether
system flow rate too small.
7. Water outlet Temp. too high Compressor stops if water outlet is higher
than 57 in heating or hot water mode. This too high water temperature may make
the system has too high condensate pressure inside and cause unit malfunction.
Check whether temperature sensor Tc and Tw is OK and well connected; whether
set water temperature too high; whether system flow rate too small.
8. Defrosting Failure If unit continuously failed to finish the defrosting
operation for three times, it stops and gives failure code S08 This can only
be recovered by re-powering the machine. Please check whether the actual water
temperature is too low for the unit to defrost, so the plate heat exchanger
has the risk of freezing up.
9. Water outlet Temp. too low This is also used to protect the safety of the
compressor. Compressor stops and AH (or HBH) starts if water outlet
temperature is lower than 15 in heating and hot water mode. Compressor
restarts when this temperature is higher than 17.
10. Too small water flow rate failure If unit stops due to “too small water
flow rate” protection (S02) over three times in certain period of
time, unit stops and gives S10 failure code. It can only be recovered by re-
powering the unit. Check the water system, especially the filter; check the
working statue of water pump.
11. Indoor anti-freezing protection failure in cooling If unit stops due to
“Indoor anti-freezing protection in cooling (S01)” over three times in certain
period of time, unit stops and gives S11 failure code. It can only be
recovered by re-powering the unit.
E. ON/OFF Press to turn ON/OFF of heat pump operation. When the unit is
powered, home page will be shown on the screen. After repowered, unit will
recover its working mode and settings automatically.
76
4. Usage
START ENGING
STOP
34.7
23.9
6.8
F. Touch screen panel
Current water temperature
Current mode Set water
temperature
Outdoor temperature
26
15
34.7
23.9
6.8
Room temperature Water tank temperature
G. Mode Press to switch unit working mode(Heating, Cooling, Hot water,
Auto).In Auto mode, unit switch its
working mode between cooling, heating and sanitary hot water automatically
according to setting.
START ENGING
STOP
34.7
Heating
Cooling
23.9
Hot Water
Auto
6.8
26
15
34.7
23.9
START ENGING
STOP
6.8
77
4. Usage
H. Setting: Press to enter into setting menu.
2. Heating/Cooling circuit 2 – see page 82
See page 103
1. Heating/Cooling circuit 1
– see page 79
5. Reduced Setpiont for Heating – see page 87
3. DHW settings – see page 83
6. Anti-Legionella Function – see page 88
7. Vacation Mode – see page 89
See page 102
4. DHW Storage – see page 85
8. User Management – see page 90
See page 103
9. Mode Settings – see page 92
10. Backup Heating – see page 94
13. Electrical Utility Lock – see page 98
14. Other options – see page 99
11. Water Pump Settings – see page 96
See page 102 12. Floor curing – see page 97
15. Unit Real-time Data – see page 101
78
4. Usage
4.2 Operation Instruction
1. Heating/Cooling circuit 1
1.Heating & Cooling Settings 1, HC/CC 1 1.01) Heating or Cooling Stops based
on Water T 1.02) Heating or Cooling Stops based on Water T
1.01: This is to set a temperature to stop unit. Unit stops operation when
[Tset+1.01] in heating operation, or [Tset1.01] in cooling operation is
reached. 1.02: This is to set a temperature to re-start unit. Unit starts
operation again when water temp. drops below [Tset-1.02] in heating operation
or increases over [ Tset+1.02] in cooling operation. Both the set values are
based on T. For example, in heating mode, if Tset=48, while 1.01=2,and 1.02=
1,when actual water temperature is higher than 50( Tset+1.01),unit stops. When
unit stops and actual water temperature drops lower than 47[ Tset- 1.02],unit
restarts.
79
4. Usage
1.03 T Compressor Speed-Reduction This parameter is used to set a temperature,
at which compressor starts to slow down its speed. Also, the set value is
based on T. Compressor always works with its maximum allowable speed, if
actual water temperature is
lower than [Tset-1.03](in heating mode) or higher than [Tset+1.03]( in cooling
mode). When actual temperature is between [Tset-1.03,Tset]in heating mode or
[Tset, Tset+1.03] in cooling mode, compressor will adjust its working speed,
to balance the total heating output and system heating load.
This setting is to keep a balance between comfort and energy saving. If this
value is set too big, even if the room is not warm (or cool) enough,
compressor will slow down its speed quite soon to save energy; If this value
is set too small, even if the room is warm (or cool) enough, compressor will
slow down its speed quite late, which consumes more power.
It’s more like a setting that tells the heat pump unit which temperature range
you’d prefer to have the heat pump stayed in.
For example, in heating mode, if Tset=48, and 1.03=2,compressor will work as
hard as possible to get 46 as soon as possible. Then compressor will lower its
speed. If even the compressor works in its lowest allowable speed, but actual
water temperature still goes over [Tset+1.01], unit stops.
Working In Heating
Compressor ON
Tset-1.03
Full Speed
Compressor Speed Down
Temp. Drops Lower Than [Tset-1.03] Stay in [Tset -1.03, Tset +1.01] Temp. Increases Higher Than [Tset+1.01]
Compressor Stop
Temp. Drops Lower Than [Tset-1.02] 1.04) Set Temp for Cooling Set an ideal
water temperature for cooling via this parameter.
1.05) Heating Curve Function Set whether heating curve function is needed or
not. If heating curve function is not needed, set 1.05=OFF,and then you can
set a fixed water set
temperature under heating mode via parameter 1.19″Set Temp For Heating”
1.06~1.15 Set the heating curve 1.06 Ambient Temp. 1 1.07 Ambient Temp. 2 1.08
Ambient Temp. 3 1.09 Ambient Temp. 4 1.10 Ambient Temp. 5 1.11 Water Temp.
A/Ambient Temp. 1 1.12 Water Temp. B/Ambient Temp. 2 1.13 Water Temp.
C/Ambient Temp. 3 1.14 Water Temp. D/Ambient Temp. 4 1.15 Water Temp.
E/Ambient Temp. 5
When 1.05=ON,user can set a heating curve which fits his house, by adjusting
the settings of parameter 1.06~1.05
80
4. Usage
Parameter 1.06~1.10 is used to set 5 different ambient temperatures; while
parameter 1.11~1.15 is used to set 5 corresponding set water temperatures VS
these 5 ambient temperatures. Then the controller will create a heating curve
according to these settings, and try to reach the set water temperature
automatically according to actual ambient temperature.
Tsh
Tsh1
Tsh2 (Tsha)
Tsh3
Tsh4
Tsh5
T(Ta)
Ta1
Ta2
Ta3
Ta4
Ta5
Tips:
(Ta)
Heating curve function is based on the factor that the lower the ambient, the higher house heating
water temperature needs to be. This heating curve function can help the heat pump unit gain a higher
COP, as well as make the house more comfortable.
As house insulation level and people’s sense of cold may vary from one another, the factory-set curve
may not suit you the best. You can set one curve according to your need.
If you feel too hot, you can lower the settings of water temperatures (parameter 1.11~1.15), which
correspond to the ambient temperature parameters (1.06~1.10) . If you feel too cold, then adjust these
settings a little higher. You can also adjust the ambient temperature settings, if you think the factory
settings are not perfect for your need.
1.16~1.18) Water Temp. Setting Adjustment function
These three parameters work together to gain an ideal water temperature for an ideal room temperature
When this function is ON, unit will adjust the set water temperature (a set value or calculated value
via heating curve), according to the difference between actual room temperature and idea room
temperature.
1.16 Room temp. effect on Heating Curve: Turn ON or OFF this function.
1.17 Idea Room temp. in Heating: Set an ideal room temperature in heating. When in Room
Temperature Control mode, this parameter will also be the Room Set Temperature.
1. 18 Idea Room temp. in Cooling: Set an ideal room temperature in cooling. When in Room
Temperature Control mode, this parameter will also be the Room Set Temperature.
For example
If 1.16 =ON, unit works in heating mode.
If water set temperature in the heating curve is 35.
If actual room temperature is 27,while parameter 1.17( Ideal Room Temp. in Heating Mode)
is set to 22 , then the unit will deduct (27 -22)=5 from water set temperature, which means
unit will take 30 as the set water temperature.
1.19 Set Temp For Heating If heating curve function is OFF, a fixed water
temperature fox heating can be set via “Set Temp For Heating”.
1.20 Low Temperature Limit 1. 21 High Temperature Limit These two parameters
are used by the installer, to set the set temperature range for circuit 1 for
safety purpose. 1.22) Mixing Valve Set whether circuit 1 has a mixing valve
connected or not. For more details, please refers to chapter 2.1.4.
81
4. Usage
2.Heating / Cooling circuit 2
2.01 Heating&cooling Circuit 2 Set whether the system has the second circuit .
2.02 Set Temp For Cooling Set the set temperature for cooling operation of
circuit 2. 2.03 Set Temp For Heating
If heating curve function is disabled for circuit 2, a fixed value of set
water temperature in heating mode can be set here. 2.04 With/Without Mixing
Valve 2
Set whether circuit2 has a mixing valve connected. For more details, please
refers to chapter 2.1.5 2.05 Heating Curve Turns ON/OFF of heating curve
function for circuit 2. 2.06 Water Temp. A/Ambient Temp. 1 2.07 Water Temp.
B/Ambient Temp. 2 2.08 Water Temp. C/Ambient Temp. 3 2.09 Water Temp.
D/Ambient Temp. 4 2.10 Water Temp. E/Ambient Temp. 5 Temperature set here is
water temperature, it is based on the same ambient temperature settings for
circuit 1, parameters 1.06~1.10. Temperature settings of the heating operation
for circuit 2 VS ambient temperatures. Controller will create a heating curve
for secondary heating system according to these settings. If parameter 2.05 is
OFF, only 2.03 needs setting, and unit will take this set value as fixed set
water temperature for secondary heating system. 2.11 High Temperature Limit
2.12 Low Temperature Limit
These two parameters are used by the installer, to set the set temperature
range for circuit 2 for safety purpose.
82
4. Usage
3. DHW Settings
3.01 Setpoint DHW Set temperature for sanitary hot water. 3.02 DHW Restart T
Setting Heat pump unit will start working for sanitary hot water again, after
temperature drops below Tset-3.02 here. 3.03 Shifting Priority Turn ON/OFF
this function. Air to water heat pump is an equipment that absorbs heat from
surrounding air, and transfers it to water. The lower the ambient temperature
is, the less heat the unit absorbs. This makes the unit heating capacity and
efficiency drop when ambient temperature drops. The unit takes longer time to
heat up the sanitary hot water. However, the lower the ambient temperature is,
the more heat the house demands. If the unit does not provide enough heat
while it is working for hot water, the temperature inside the house may drop
too much, and people in it feel uncomfortable. So parameters 3.03~3.08 try to
divide the working time for sanitary hot water into several cycles, after
ambient temperature drops below a set value. When this function is ON, AH
(Auxiliary Heater) or HWTBH (Hot Water Tank Back-up Heater) or both, depending
on their priority, will work individually or together to enhance heat pump’s
capacity in sanitary hot water mode to heat up the water as soon as possible.
3.04 Shifting Priority Starting Temp. Set an ambient temperature below which
this function starts to work. When shifting priority function is activated,
heat pump will try to find a balance between DHW and Heating operation after
ambient temperature drops below this temperature. 3.05 Sanitary Water Min.
Working Hours Set the minimum working period for sanitary hot water mode. 3.06
Heating Max. Working Hours Set the maximum working period for heating mode,
after unit enters into heating mode. 3.07 Allowable Temp Drift in Heating Set
allowable temperature drift in heating mode. 3.08 DHW Backup Heater for
Shifting Priority Working mode of HWTBH (Hot Water Tank Back-up Heater) in
this function. If this parameter is set ON, when heat pump is switching to
house heating, HWTBH will keep on working to help the uni heat up hot water as
soon as possible.
83
4. Usage
If shifting priority function is ON, and ambient temperature is lower than [3.04],unit works as shown below: House heating water under water temp.
The running time for DHW is cleared. Unit Starts heating
YES
and counting the running time.
Unit keep on working in DHW
NO
and counting the running time.
NO
The ambient temp. Is below (3.04)
Whether the YES unit works in DHW
NO
Whether unit works YES in DHW over (3.05)
Whether house heating water temperature drops over (3.07)
Unit works in heating YES
Whether unit works in YES Heating over (3.06)
NO
The running time for Heating is cleared. Unit starts DHW and counting the running time.
Unit keep on working in Heating and counting the running time.
84
4. Usage
4.DHW Storage
Sanitary Hot Water Storage Function After showers, house usually needs only
medium temperature sanitary hot water in day time. This function is used to
store high temperature sanitary hot water in low demand time (mid-night, or
day time of working days), and reheat the water to medium temperature out of
this time period. 4.01 Sanitary Hot Water Storage Function Turn ON/OFF this
function. 4.02 Sanitary Hot Water Storage Timer Set a working time period for
this function, and the unit starts to work towards sanitary hot water set
temperature in parameter 3.01 within the set time range. Different time
periods for every day in a week can be set.
4.03 Reheating Function Turn ON/OFF reheat function. 4.04 Reheating Function
Timer Set a working time period for reheat function, and within this time
period, unit will work with a lower set value for DHW (value set in parameter
4.05). Different time periods for every day in a week can be set.
85
4. Usage
4.05 Reheating Set Temp. Set a lower set value for DHW operation. Unit will
work with this set value when reheating function
is activated in the set time period (time period set in parameter 4.04).
4.06Reheating Restart T Setting
Set “reheat restart”water T. When water temperature drops below T based on
reheat set temperature within the set reheating time period, unit restarts.
86
4. Usage
5. Reduced Setpoint for Heating
Reduced Setpoint Function: Sometimes the house heating demand maybe lower than
normal, like during sleep period or working time. In this way, a reduced value
based on standard set value can be set here for better efficiency of the whole
system. Quiet Operation: Also, for a better noise issue, a Quiet Operation can
be also set in this menu. After activating this function and setting the time
period for quiet operation, unit will try to reduce its noise level. Note:
Unit efficiency in quiet operation mode will be lower than standard working
mode. 5.01 Reduced Setpoint
Turn ON/ OFF Reduced Setpoint function. 5.02 Temp. Drop/Rise
Set temperature drop (in heating) or increase (in cooling) based on standard
set temperature during Reduced Setpoint operation. 5.03 Timer for Reduced
Setpoint Function
Set a working time period for Reduced Setpoint function. Different time
periods for every day in a week can be set. 5.04 Quiet Operation Turn ON/ OFF
Quiet Operation function. 5.05 Allowable Temp. Drifting Set allowable
temperature drift during Quiet Operation. When the unit works in quiet mode,
its output may drop because both fan and compressor may need to work in lower
speed. However, temperature in the system may drop (in heating) or increase
(in cooling) too much due to the lower output. So when actual temperature
drift from the standard set value is more than the T set value set here, unit
will end this quiet operation, to ernsure comfortable house temperature. 5.06
Timer for Quiet Operation Set a working time period for Reduced Setpoint
function Different time periods for every day in a week can be set.
87
4. Usage
6. Anti-Legionella Function
If user uses sanitary hot water directly out from the HWT (hot water tank),
for the health purpose, it’ s requested that he needs to heat up the water
inside the tank over 60 for anti- legionella purpose once a week. Note:Please
always refers to local regulation for a correct usage of this function. 6.01
Anti-Legionella Program
Turn ON/ OFF Anti-Legionella function. 6.02 Day and Time
Set at which time in which weekday(s) for the start of anti-legionella
operation. 6.03 Setpoint
Set the target sanitary hot water temperature for anti-legionella. Please
refers to the local regulation for the correct setting of this temperature.
6.04 Duration
Set for how long the unit should try to keep this set high temperature, to
ensure all bacteria in the shower water tank can be killed. 6.05 Finish Time
Set an ending time for this anti-legionella function, even it is not finished
successfully. This time should be longer than what it is set in parameter 6.04
.
88
4. Usage
7. Vacation Mode
If you need to be away from house for some days, you can use this Vacation
Mode function to reduce the set temperatures for both sanitary hot water and
house heating , to save more energy. 7.01) Vacation Mode
Turn ON/OFF Vacation Mode. 7.02) Sanitary Hot Water Temp. Drop During Vacation
Mode
Set a temperature drop for sanitary hot water based on standard DHW set value
during the set time period for vacation mode. 7.03)Heating Water Temp. Drop
During Vacation Mode
Set a temperature drop for heating based on standard DHW set value during the
set time period for vacation mode. 7.04) Vacation Start Date
Set the date that vacation starts. 7.05) Vacation Finish Date
Set the date that vacation finishes.
89
4. Usage
8. User Management
8.01) Permission Level For the safety of the product,some parameters can only
be adjusted under installer’s
permission level. The permission level can be changed in this menu. A password
is needed for activating the installer’s permission level. 8.02)
Heating/Cooling ON/OFF Timer
To turn ON/OFF the timer function for heating/cooling operation. 8.03)
Heating/Cooling ON/OFF Timer
Set the ON and OFF timer for the heating/cooling operation.Different time
periods for every weekdays in a week can be set.
90
4. Usage
8.04) Language Set system language.
8.05) Set Date and Time Set system clock date and time.
8.06) Distribution System Setting The unit is default set to have 3-way
motorized valve inside the unit, which has different
flow directions for sanitary hot water/cooling+heating mode. If user needs to
have sanitary hot water and heating on the same distribution system, he can
set this parameter to”Hot Water+Heating/Cooling”. Note: If it is set to
“Sanitary Hot Water+Heating/Cooling”, temperature sensor for sanitary hot
water (Tw) will be used for the control of heating operation also. Please
place it either inside an ideal position in Hot Water Tank. 8.07) Save Current
Settings
This parameter is used by installer to save the current settings as “Installer
Settings”, so the customer can load the saved settings into the system, when
needed. 8.08) Load Saved Settings
Loaded the saved “Installer Settings”. 8.09) Reset to Factory Settings
Reset the whole system back to factory default settings. Note: Saved”Installer
Settings” will be cleared. Note: Most of above menus and parameters are
designed for installer only. They should only be adjusted by installer or
professional customer under the instruction of installer, otherwise
malfunction of the unit may happen.
91
4. Usage
9. Mode Settings
9.01) Sanitary Hot Water Set whether the system has sanitary hot water circuit
or not. When unit works in Sanitary Water mode,
3-way motorized valve will guide water to HWT automatically. 9.02) Heating
Set whether the system has water circuit for house heating purpose or not.
When unit works in heating mode, 3-way motorized valve will guide water to
heating circuit automatically. 9.03) Cooling
Set whether the system has water circuit for house cooling purpose or not.
When unit works in cooling mode,3-way motorized valve will guide water to
cooling circuit automatically. NoteAs whether the system can work in hot
water, heating or cooling mode depend quite much on the distribution system,
these setting can only be done under installer level, to ensure the safety of
the distribution system. 9.04) Basic Operation Mode This parameter is used to
set the basic operation modes, as”Water Temperature Control”or “Room
Temperature Control”. When “Basic Operation Mode” is activated, unit takes
room temperature as control object. When “Basic Operation Mode” is not
activated, unit takes water temperature as control object. Heating or cooling
function take water as the control object as default. However when a room
temperature sensor is connected to the unit and a more precise control of room
temperature where the sensor is placed is preferred, “Room Temperature
Control”mode can be selected. Note: When”Room Temperature Control”mode is
selected, system will not operate under the heating curve function and actual
water temperature may swing significantly.
92
4. Usage
9.05) Max Allowed Duration For Min Compressor Speed When unit output is higher
than demand,compressor speed will be reduced.If compressor has
continuously worked in minimum compressor speed for over time set via”Max
Allowed Duration For Min Compressor Speed”,unit stops. 9.06) Cooling and
Heating Switch
This function is for having the unit start cooling or heating operation
automatically, according to: If setting =”Ambient Temp”, system will
automatically choose cooling or heating operation based on the outdoor ambient
temperature, compared with parameter set in 9.07 and 9.08. If setting
=”External Signal Control”, an external room thermostat or central control
system in the building can control the cooling or heating requirements by
connecting it to the respective signal ports. The signals are simple 1-0 (on-
off) signal. If cooling port receives the signal, the system switches to
cooling; If heating port receives the signal, the system switches to heating.
When neither port receives the signal, the system stays in standby mode. If
setting =”Ambient Temp.+External Signal Control”,unit will take both the
ambient temperature and external signal into consideration for cooling or
heating mode selection. Note: If parameter is set to OFF, auto switch function
is not activated. Then make sure that parameter (Heating Water Circuit) and
(Cooling Water Circuit) are not set to ON simultaneously, as the system can
not determine actual requirement, due to mode conflict. To avoid mode
conflict, if”External Signal Control”is used to take control, please ensure
that the external signal will not be activated at the cooling and heating
ports at the same time. 9.07) Ambient Temp. To Start Heating This parameter is
used to set the ambient temperature to start the heating operation. For
example, if default value is 18, the system will start heating operation
automatically when ambient temperature is lower than 18. The setting is only
available when parameter “Cooling and Heating Switch”=” Ambient Temp. ” Or
“Ambient Temp.+External Signal Control”. 9.08) Ambient Temp. To Start Cooling
This parameter is used to set the ambient temperature to start the cooling
operation. For example, if set value is 28, the system will start heating
operation automatically when ambient temperature is higher than 28. The
setting is only available when parameter “Cooling and Heating Switch
“=”Ambient Temp. Or “Ambient Temp.+External Signal Control”. Note: In order to
avoid short cycling between different modes, unit will also take the average
temperature in the past time for reference of choosing the working mode.
93
4. Usage
10. Backup Heating
AH—Auxiliary Heater inside the indoor unit HBH—Heating Back-up Heater
HWTBH—Hot Water Tank Back-up Heater 10.01) Backup Heating Sources For Heating
Set whether the system has HBH (Heating Back-up Heater). 10.02) Priority for
Backup Heating Sources (HBH) Set the priority of HBH compared with unit AH
(Auxiliary Electric Heater inside the indoor unit). When unit works in
heating, if heat pump unit can’t provide enough power, it will turn on AH or
HBH (which set to have the higher priority) automatically. If after AH or HBH
is working, that the total output power is still not big enough, unit will
turn on the lower priority Backup Heating Source also. 10.03) Backup Heating
Source for Sanitary Hot Water Set whether the system has HWTBH (Hot Water Tank
Back-up Heater). 10.04) Priority for Backup Heating Sources (HWTBH) Set the
priority of HWTBH compared with unit AH (Auxiliary Electric Heater inside the
indoor unit).
When unit works in hot water, if heat pump unit can’t provide enough power, it
will turn on AH or HWTBH (which set to have the higher priority)
automatically. If after AH or HWTBH is working, that the total output power is
still not big enough, unit will turn on the lower priority Backup Heating
Source also. 10.05) External Heating Source Start Accumulating Value
Accumulated Value between operation time VS set temp. to start other heating
source for heating operation.
94
4. Usage
This is for adjusting how fast Backup Heating Sources for heating operation
will be turned ON if heat pump unit can’t provide enough power. The bigger the
value is set, longer time it takes to start the Backup Heating Sources if heat
pump capacity is not enough. 10.06) Water Temperature Rise Reading Interval
Time interval for checking the temperature increase when unit works in DHW
mode. If temperature increases too slow during this set interval time, unit
will activate other heating source for DHW operation.
The smaller the value is set, unit is more likely to activate AH or HWTBH for
a fast heating of DHW.
Backup Heating for DHW If system has no HWTBH (set via parameter 10.03), or
HWTBH has lower priority than AH (set via parameter 10.04 ): If heat pump
capacity is not enough to heat up DHW fast enough, unit starts AH. If after AH
starts, it still cannot heat up DHW fast enough, HWTBH starts. When the set
and actual water temperature is higher than heat pump maximum allowable water
temperature, heat pump stops and unit starts AH. If after AH starts, hot water
temperature still increases too slow, HWTBH starts. If system has HWTBH (set
via parameter 10.03), and HWTBH has higher priority than AH (set via parameter
10.04):
If system has HWTBH (set via parameter 10.03), and HWTBH has higher priority
than AH (set via parameter 10.04):
When the set and actual water temperature is higher than heat pump maximum
allowable water temperature, HWTBH works ALONE for DHW while heat pump unit
will work in heating or cooling mode according to demand.
When actual water temperature is lower than heat pump maximum allowable water
temperature, heat pump works in hot water mode. If heat pump capacity is not
enough to heat up DHW fast enough, unit starts HWTBH. If after HWTBH starts,
hot water temperature still increases too slow, AH starts.
Under shifting priority operation, according to parameter 3.08 ,AH or AH+HWTBH
work together with heat pump to heat sanitary hot water to the set value as
soon as possible, so heat pump unit can concentrate on heating mode
afterwards. 10.07) Emergency Operation
When heat pump failed to work, whether the unit should turn ON the back-up
heating system automatically.
Note: If this function is activated, customer should check the working status
of heat pump unit occasionally, to ensure heat pump unit is functioning well.
95
4. Usage
11.Water Pump Settings
11.1) Circulation Pump P0 Type This is to set the type of circulation pump
inside the unit, P0.
11.2) Speed Setting of Circulation Pump P0 This is to set the working speed of
circulation pump inside the unit, P0.
11.3) Working Mode of Circulation Pump P0 This is to set the working mode of
circulation pump for cooling/heating operation inside
the unit, P0. P0 can work as the following settings:
1. Interval working mode. In this setting, P0 stops after compressor stops,
but runs for a while after stops for an interval period.
2. ON constantly. P0 will work constantly even if compressor stops after
reaching the set temperature.
3. OFF with compressor. It means P0 stops after compressor stops. 11.4) Pump
OFF Interval 11.5) Pump On Time
If unit circulation pump P0 working mode is set to “Interval working mode”,
that means circulation pump stops after compressor stops, but after it stops,
it will runs for [11.5] minutes after stops for every [11.4] minutes interval
time. 11.6 Buffer Tank 11.7 P1 for Heating Operation 11.8 P1 for Cooling
Operation 11.9 P1 with High Temp. Demand 11.10 P2 for Heating Operation 11.11
P2 for Cooling Operation 11.12 P2 with High Temp. Demand These parameters are
used for setting the working of external circulation pump P1 and P2, for
heating/cooling circuit, (HC/CC 1) and heating/cooling circuit, (HC/CC 2).
For more details, please refers to chapter 2.1.3~2.1.5.
96
4. Usage
12. Floor Curing
After initial Installation or Long Time Non-operation, a floor heating system
may be very wet in the concrete. Most of the heating capacity from heat pump
unit is consumed to dry up the water in the concrete for its evaporation. This
floor curing function is used to dry the floor to ensure the safety of heat
pump system. 12.1) Floor Curing
Turn ON/OFF this function. For a newly-built floor heating system, floor must
be cured before setting the heat pump into standard working mode. 12.2) Floor
Curing Temperature Setting Stage 1 12.3) Floor Curing Operation Duration Stage
1
Set temperature and lasting time for first-stage of Floor Curing operation.
12.4) Floor Curing Temperature Setting Stage 2 12.5) Floor Curing Operation
Duration Stage 2
Set temperature and lasting time for second-stage of Floor Curing operation.
12.6) Floor Curing Running Hours 12.7) Highest Water Temp. in Floor Curing
Operation
Three two values are operation data during floor curing operation. Unit will
take down the operation time and highest water temperature the system has
reached during Floor Curing operation.
Note: After Floor Curing operation is finished, if water temperature inside
the distribution system is still far below the set value of [12.4], it means
there has still some water inside the concrete of floor heating system, thus
Floor Curing function should be turned ON again, until temperature can
increase over [12.4].
97
4. Usage
13.Electrical Utility Lock
Some electricity companies offer a special rate to the houses who lowered
their power consumption during peak time. When peak time comes, electricity
company will send an ON or OFF signal to every house, indicating that they
hope the house owners to turn OFF some electric equipments. This system can be
connected to the unit if the unit is supposed to stop working during this
period, and use the following parameter settings to activate this function.
13.1) Electrical Utility Lock
Set ON/OFF Electrical Utility Lock function. 13.2) Operation Signal for
Electrical Utility Lock
Set the type of signal from electricity company.”Normally Open”means when unit
can work as normal when it gets ON signal; the unit should stop working when
it receives a OFF signal; “Normally Close”means the opposite. 13.3) HBH During
Electrical Utility Lock
Set whether turn on HBH (Heating Back-up Heater), when unit is blocked by
Electrical Utility Lock. e.g. gas boiler. 13.4) Working Mode of Pump During
Electrical Utility Lock
Set the working of circulation pump when unit is blocked by Electrical Utility
Lock. If it’s activated, the circulation pump will keep on working when
compressor stops. If it’s not activated, the circulation pump will stop
working when compressor stops.
98
4. Usage
14. Other Options
14.1) Motorized Diverting Valve Switching Time Set how many minutes as
switching time of the motorized diverting valve spending on switching
the water flow fully between DHW and Heating/Cooling circuit. Note: This
parameter must comply with the motorized diverting valve. Otherwise unit may
not be able to work due to not enough water flow rate. 14.2) Power On Time for
Motorized Diverting Valve
Set how long the motorized diverting valve should be powered, for switching
the water flow fully between DHW and Heating/Cooling circuit. 14.3)
Refrigerant Recycle
This function can be used by installers to recycle the refrigerant in the
complete system into condensing unit for service purpose. When it is
activated, unit will be forced to work in cooling operation for some time, to
push all refrigerant back to condensing unit. 14.4) Control Panel Backlight
Set the backlight touch screen operation panel to be”Always on”or how long
before it becomes off for energy saving. 14.5) Exit System
Exit from unit program and returns to WINCE operation system. This is used for
software updating.
99
4. Usage
14.6) Ambient Temp. to activate first class anti-freezing 14.7) Ambient Temp.
to activate second class anti-freezing 14.8) Ambient Temp. to stop second
class anti-freezing 14.9) Water Temp. to activate second class anti-freezing
14.10) Water Temp. to stop second class anti-freezing
These parameters are used for setting the anti-freezing protection of the unit
in winter time, when unit is powered but turned OFF.
When ambient temperature is lower than fist class anti-freezing starting
ambient temperature, unit will circulate the water in the system at interval
for anti-freezing.
When ambient temperature drops below second class anti-freezing starting
ambient Temperature, heat pump unit will start either compressor or backup
heating sources to maintain the water temperature within the range “Water
Temp. to activate second class anti-freezing” and “Water Temp. To stop second
class anti-freezing”.
Note: This function is provided to the customer FREE OF CHARGE for helping
their house heating and DHW water system free from freezing up. Customer
should always have his own protection system for preventing the water system
from freezing up. We have no responsibility or obligation if any damage has
caused by water freezing. 14.11) Mode Switch during Defrosting
If water temperature is too low, the condenser may have the risk of freezing
up and cause damage the complete refrigerant system. Thus, if water
temperature in current working mode is too low for defrosting, unit will check
the water temperature in other circuit. If the water temperature in other
circuit is good enough for defrosting, it will switch the water flow to this
circuit for defrosting operation automatically.
If there is no other circuit, or the water temp in other circuit is also not
high enough for defrosting, unit will stop defrosting and automatically lift
up the set water temperature, preparing for the next defrosting cycle.
If defrosting failed for over three times continuously, unit stops and can
only be recovered by re-powering the machine. Please check the water system at
this moment to ensure everything works properly before re-powering the unit.
Note: This function can only work with outdoor software higher than
AC13I20.WP.V004_T01 or AC13I17.WP.V009_T01, otherwise this function will
interrupt the working of the machine during defrosting all the time. 14.12)
Fan Speed Limit This function is for reducing the fan speed in order to reduce
the noise, however it would reduce the performance of the heat pump at the
same time. The fan speed limitation can be set at down to two levels 95% and
90%. This function is not recommended unless the noise is strongly complained
by customer/neighbor.
100
4. Usage
15. Unit Real-time Data
This menu is designed for viewing the running data of the system. Following
parameters that are related to the working of the system can be viewed in this
menu: 01): Control System Version No 02): Database Version 03): Heat Exchanger
Water Outlet Temperature-Indoor – Tuo 04): Heat Exchanger Water Return
Temperature-Indoor – Tui 05): Indoor Coil Temp. – Tup 06): Sanitary Hot Water
Temp.- TW 07): Cooling/ Heating Water Temp.-TC 08): Water Flow Rate 09):
Compressor Working Speed 10): EEV Openings 11): Actual Ambient Temp. 12):
Average Ambient Temp. in 1 Hour 13) Average Ambient Temp. in 24 Hour 14) High
Pressure – Pd 15): Low Pressure – Ps 16): Discharge Temp. – Td 17): Suction
Temp. – Ts 18): Outdoor Coil Temp. – Tp 19): Source Side Water Inlet
temperature (For Water to Water unit only) 20): Source Side Water Outlet
temperature (For Water to Water unit only) 21): Fan Speed 22): Fan Speed 2
23): Outdoor Unit Working Current 24): Voltage 25): Eeprom Version No.
101
4. Usage
Info Press “Info” to view water system and water system working status.
Display of Failure Code
Display of Failure
Record of Previous Failure
TW—-Water temperature for Sanitary hot water tank TC—–Water temperature for
buffer tank TR—–Room temperature TA—–Ambient temperature
102
4. Usage
Home Home: Press this button at any page, operation panel goes back to home
page.
26
15
34.7
23.9
START ENGING
STOP
6.8
103
4. Usage
4.3 Electric heater
The inbuilt electric heater can be used as a back-up heater or auxiliary
heater to our heat pump unit, when ambient temperature is too low, or heat
pump fails to work properly, which causes insufficient heat. This heater will
start to work when any of following two conditions is met: 1. Water
temperature is lower than what is set via digital thermostat for electric
heater. 2. Heat pump unit thinks its capacity is not enough, so it turns ON
the heater.
Notice! There is a separate power cable for electric heater on top of
3kW or 6kW electric heater
indoor unit. It supplies the power to electric heater directly.
Make sure the unit is full of water before turning it on.
Do not touch it to get burned when it is turned on. High
temperature here.
Make sure the power supply to the heater corresponds to the
specifications.
The installation, dismantlement and maintenance of the heater
must be performed by qualified personnel. It is forbidden to
do any changes to the structure of the heater.
Digital thermostat is default set to 30.
Maximum set temperature of digital thermostat is 120. But
it is strongly suggest not to set the temperature over 75,
otherwise it may make the unit build up too high pressure inside
and cause damage or danger.
Operation of digital thermostat
This heater (AH) is controlled by heat pump unit automatically according to
the parameter setting in menu “Backup Heating”.
In case the heat pump control system breaks down, customer can manual set a
set temperature for water circulates through the unit via the digital
thermostat for Electric Heater (AH).
Important Notice: Before turn ON the thermostat, system must be full filled
with water and correctly air purged, otherwise electric may get over heat and
cause fire.
104
4. Usage
Operation of digital thermostat
-
Press for 3 seconds to turn ON OFF of the electric heater. When heater is turned OFF, it shows “- – -“.
-
When heater is turned ON, press for 3 seconds to show the set temperature. After release, this set temperature blinks on the display.
-
When set temperature is blinking, press or to increase or decrease the set temperature of electric heater.
-
Controller will save this setting and show actual water temperature in the display if no operation in 6 seconds.
4.4 Failure codes
Outdoor
Type Code Description
Blinking times
P01
Main line current protection
1
P02
Compressor phase current protection
2
Protection
P03
IPM module protection
3
P04
Compressor oil return protection
4
Compressor shut
down due to high/
P05
low pressure switch open caused by
5
abnormal high/low
pressure
Unit working statue
Compressor stops
Compressor stops Compressor stops Compressor speed up
Compressor stops
Solution
Input current too high or too low, or system works in over-load condition.
Unit recovers automatically after 5 minutes when it happened the first time.
If same failure happened 3 times in a certain period of time, unit stops until
repowered. Check unit input current. Check whether fan motor and water pump is
working OK; whether condenser is blocked; whether water temperature too high,
and whether water inlet&outlet temperature has too big difference (should no
bigger than 8)
Compressor input current too high or too low, or system works in over-load
condition. Check compressor input current. Check whether fan motor and water
pump is working OK; whether condenser is blocked; whether water temperature
too high, and whether water inlet&outlet temperature has too big difference
(should no bigger than 8)
Compressor drive failure. Check whether cable is broken or loosen. Check
whether compressor driver PCB or compressor is broken.
If unit has been continuously working in low speed for certain period of time,
unit starts this protection to suck compressor oil back into compressor. This
is a normal protection and doesn’t need any treatment.
If system pressure is too high or too low, it activates this protection. Unit
recovers automatically after 5 minutes when it happened the first time. If
same failure happened 3 times in a certain period of time, unit stops until
repowered. Check whether fan motor and water pump is working OK; whether
condenser is blocked; whether water temperature too high, and whether water
inlet&outlet temperature has too big difference (should no bigger than 8)
105
4. Usage
Type Code Description
Blinking Unit working
times
statue
Solution
Compressor speed
down due to
P06
abnormal high pressure detected
by condensing
pressure sensor
If system pressure is too high , it activates this protection. Unit
recovers automatically after 5 minutes when it happened the first
time. If same failure happened 3 times in a certain period of time,
6
Compressor stops unit stops until repowered. Check whether fan motor and water pump
is working OK; whether condenser is blocked; whether water
temperature too high, and whether water inlet&outlet temperature
has too big difference (should no bigger than 8)
P07
Compressor preheating
7
Standard function, doesn’t need any treatment.
This is a normal protection and doesn’t need any treatment. When compressor did not work for long time and ambient temperature is low, compressor crankcase heater work for certain period of time before compressor start to warm up the compressor.
Compressor P08 discharge temp. too 8
high protection
Check whether water temperature set value is too high, especially Compressor
stops when ambient temperature is low; whether water flow rate too small;
whether system is lacking of enough refrigerant.
Outdoor evaporator
P09 coil temp. sensor
9
protection
Compressor stops Check whether air circulates fluently in outdoor unit.
Protection
P10
AC over high/low voltage protection
10
Compressor stops
Unit input voltage too high or too low. Check the voltage of unit power supply.
Compressor shut
P11
down due to too high/low ambient
temperature
11 Compressor stops Ambient temperature is too high or too low for unit to work.
Compressor speed
P12
limit due to too high/low ambient
temperature
0
Compressor speed down
This is a normal protection and doesn’t need any treatment.
Compressor speed
down due to
P14
abnormal low pressure detected
by condensing
pressure sensor
If system pressure is too low , it activates this protection. Unit
recovers automatically after 5 minutes when it happened the first
time. If same failure happened 3 times in a certain period of time,
unit stops until repowered. Check whether system has not enough
14
Compressor stops
refrigerant or leakage inside(more likely it is not enough refrigerant that caused this abnormal evaporating pressure); whether fan motor
and water pump is working OK; whether condenser is blocked;
whether EEV whether EEV works normally; whether water
temperature too low, and whether water inlet&outlet temperature has
too big difference in cooling(should no bigger than 8).
F01
Outdoor ambient temp. sensor failure
17
Compressor stops
Check whether ambient temperature sensor is open, short-circuit or value drifts too much. Replace it if necessary.
Outdoor evaporator
F02 coil temp. sensor
18
failure
Compressor stops
Check whether outdoor coil temperature sensor is open, short-circuit or value drifts too much. Replace it if necessary.
Compressor F03 discharge temp.
sensor failure
19
Compressor stops
Check whether compressor discharge temperature sensor is open, short-circuit or value drifts too much. Replace it if necessary.
F04
Outdoor Suction temp. sensor failure
20
Compressor stops
Check whether outdoor suction temperature sensor is open, short-circuit or value drifts too much. Replace it if necessary.
Failure
Evaporating F05 pressure sensor
failure
21
Compressor stops
Check whether evaporating temperature sensor is open, short-circuit or broken. Replace it if necessary.
Condensing F06 pressure sensor
failure
22
Compressor stops
Check whether condensing temperature sensor is open, short-circuit or broken. Replace it if necessary.
F07
High/low pressure switch failure
If pressure switch is in open position when unit is in standby statue, 23
Compressor stops or 2 minutes after compressor stops, unit gives this failure.
Check
whether high or low pressure switch is broken or not well connected.
F09
DC fan failure (one)
25
Compressor speed down
Speed of DC fan or one of the DC fan (for dual fan system) can’t reach the required value or no feedback signal. Please check whether the PCB or fan motor is broken.
106
4. Usage
Type Failure
Code Description
F10
DC fan failure (two)
Blinking Unit working
times
statue
26 Compressor stops
F11
System evaporating pressure too low
27
Compressor stops
Solution
Speed of both DC fans (for dual fan system) can’t reach the required value or
no feedback signal. Please check whether the PCB or fan motor is broken.
If system too low pressure protection detected by evaporating pressure sensor
happened 3 times in a certain period of time, it gives this failure code and
unit can’t be restarted until repowered. Check whether system has not enough
refrigerant or leakage inside(more likely it is not enough refrigerant that
caused this abnormal evaporating pressure); whether fan motor and water pump
is working OK; whether condenser is blocked; whether EEV whether EEV works
normally; whether water temperature too low, and whether water inlet&outlet
temperature has too big difference in cooling (should no bigger than 8).
If system too high pressure protection detected by condensing
pressure sensor happened 3 times in a certain period of time, it gives
this failure code and unit can’t be restarted until repowered. Check
F12
System condensing pressure too high
28
whether water flow rate is not enough (more likely it is not enough Compressor
stops water flow rate that caused system build up too high pressure);
whether fan motor and water pump is working OK; whether
condenser is blocked; whether EEV works normally; whether water
temperature too high, and whether water inlet&outlet temperature has
too big difference (should no bigger than 8)
Communication
Communication failure between operation panel and the indoor or
between operation
outdoor PCB. Check the cable connection in between. Check whether
E01 panel and indoor
33 Compressor stops the last three switches on outdoor power PCB are set to 001; Whether
PCB or outdoor
four switches on indoor PCB are set to 1000. Unit recovers when
PCB failure
communication recovers.
Communication
between outdoor E02 main control PCB
34
Check the communication cable between outdoor power PCB and Compressor stops deiver PCB. Check whether outdoor power PCB and deiver PCB is
and module PCB
broken.
Compressor phase
E03 current failure
35
(open/short circuit)
Compressor phase
System E04 current overload
36
failure
(over current)
E05
Compressor driver failure
37
Module VDC over
E06 high/low voltage
38
failure
E07 AC current failure 39
E08 EEPROM failure
40
Compressor stops
Check whether the power cable to compressor is broken or shortcircuit.
Compressor stops
Check whether the power cable to compressor is broken or shortcircuit.
Compressor stops
Check whether compressor drive PCB is broken, or cable to compressor is wrong connected.
Compressor stops Input voltage too high or too low.
Check the current to outdoor unit, and compare it with the unit
current shown on the operation panel. If the difference is not big,
Compressor stops
check whether the system has enough refrigerant (more likely it is not enough refrigerant that caused this abnormal low current). If the
difference is big, outdoor power PCB is broken. Please replace it with
a new one.
Cut the unit power and short-circuit JP404 port on outdoor power
Compressor stops PCB, repower the unit, cut power again and cancel the short- circuit
on JP404 port. If still not OK, replace the outdoor power PCB.
107
4. Usage
Indoor
Type Failure
Code Description
Blinking Unit working
times
statue
F13
Room temp. sensor failure
7
Unit stops
F14
Sanitary hot water temp. sensor failure
3
Unit stops
Cooling/heating
F15 water temp. sensor
6
failure
F16
Unit water outlet temp. sensor failure
4
Unit stops Unit stops
F17
Unit water inlet temp. sensor failure
5
Unit stops
F18
Indoor coil temp. sensor failure
8
Unit stops
Mixture valve 1 F21 temperature sensor
failure
11
Unit keep on working, mixture valve 1 output fixed to 0.
Mixture valve 2 F22 temperature sensor
failure
12
Unit keep on working, mixture valve 2 output fixed to 0.
Communication
between operation
F25 panel and indoor
1 Unit stops
PCB or outdoor
PCB failure
F27
Indoor EEPROM failure
13
Unit keep on working
Water pump PWM F28 signal feedback
failure
14
Unit keep on working
Solution
Check whether room temperature sensor is open, short-circuit or value drifts
too much. Replace it if necessary. Check whether sanitary hot water
temperature sensor is open, shortcircuit or value drifts too much. Replace it
if necessary.
Check whether cooling/heating water temperature sensor is open, short-circuit
or value drifts too much. Replace it if necessary.
Check whether unit water outlet temperature sensor is open, shortcircuit or
value drifts too much. Replace it if necessary. Check whether unit water inlet
temperature sensor is open, shortcircuit or value drifts too much. Replace it
if necessary. Check whether indoor temperature sensor is open, short-circuit
or value drifts too much. Replace it if necessary.
Check whether TV1 temperature sensor is open, short-circuit or value drifts
too much. Replace it if necessary.
Check whether TV2 temperature sensor is open, short-circuit or value drifts
too much. Replace it if necessary.
Communication failure between operation panel and the indoor or outdoor PCB.
Check the cable connection in between. Check whether the last three switches
on outdoor power PCB are set to 001; Whether four switches on indoor PCB are
set to 1000. Unit recovers when communication recovers. Cut the unit power,
connect CN213-5 and CN213-6 together, repower the unit and then cut the power
and cancel the connect. If still not OK, replace the indoor PCB.
Check water pump cable connection; check power supply to water pump; check
whether water pump is broken.
F29
Mixture valve 1 failure
17
F30
Mixture valve 2 failure
18
Indoor anti-freezing S01 protection in
cooling
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>