HEIKO R417 DC Inverter Air to Water Heat Pump User Manual

June 9, 2024
HEIKO

R417 DC Inverter Air to Water Heat Pump

Thermal 6 Thermal 9 Thermal 12
DC Inverter Air to Water Heat Pump
User’s manual
Before operating this product, please read the instructions carefully and keep this manual for future use.
This product may only be installed or serviced by qualified personnel.
This appliance is filled with R32 refrigerant.

Catalogue

1. Before use

4

1.1 Safety precautions

10

1.2 Working principle

12

1.3 Main components

13

1.4 Specifications

15

2. Assembly Configurations

16

1. Flowchart

16

2. Drawing 1

17

3. Drawing 2

19

4. Drawing 3

22

5. Drawing 4

25

6. Drawing 5

28

7. Drawing 6

31

8. Drawing 7

34

9. Drawing 8

37

10. Drawing 9

40

11. Drawing 10

43

3. Installation

46

3.1 General application system introduction

46

3.2 Tools needed

53

3.3 Installation of the indoor control unit

53

3.4 Installation of the monoblock unit

55

3.5 Accessories

57

3.6 Wiring

58

3.7 Installation of safety valve kit

71

3.8 Water pipe connection

72

3.9 Test run

73

4. Usage

74

4.1 Introduction of operation panel

74

4.2 Operation instruction

79

4.3 Electric heater

104

4.4 Failure codes

105

2

Catalogue

5. Maintenance

110

5.1 Precaution of maintenance for units with flammable refrigerant

110

5.2 Attention

113

5.3 Cleaning of water filter

113

5.4 Cleaning of plate heat exchanger

113

5.5 Gas charging

113

5.6 Condenser coil

115

5.7 Service of indoor control unit

115

5.8 Service of monoblock unit

117

6. Attached drawing

121

6.1 Outlines and dimensions

121

6.2 Exploded view

123

6.3 Wiring diagram

125

6.4 Appendix A:Wiring

128

3

1. Before use
1.1 Safety precautions
Cautions: 1.Do not use means to accelerate the defrosting process or to clean,other than those recommended
by the manufacturer. 2.The appliance shall be stored in a room without continuously operating ignition sources
(for example: open flames, an operating gas appliance or an operating electric heater.). 3.Do not pierce or burn. 4.Be aware that refrigerants may not contain an odour. 5.Appliance shall be installed, operated and stored in a room with a floor area larger than X m2
(refer to specifications sheet). 6.The installation of pipe-work shall be kept to a minimum X m2 (refer to specifications sheet). 7.Spaces where refrigerant pipes shall be compliance with national gas regulations. 8.Servicing shall be performed only as recommended by the manufacturer. 9.The appliance shall be stored in a well-ventilated area where the room size corresponds to the room
area as specified for operation. 10.All working procedure that affets safety means shall only be carried by competent persons.
Gerneral Notice:
1.Transport of equipment containing flammable refrigerants Compliance with the transport regulations
2. Marking of equipment using signs Compliance with local regulations
3.Disposal of equipment using flammable refrigerants Compliance with national regulations
4.Storage of equipment/appliances The storage of equipment should be in accordance with the manufacturer’s instructions.
5.Storage of packed (unsold)quipment Storage package protection should be constructed such that mechanical damage to the equipment inside the package will not cause a leak of the refrigerant charge. The maximum number of pieces of equipment permitted to be stored together will be determined by local regulations.
6.Information on servicing 1)Checks to the area Prior to beginning work on systems containing flammable refrigerants, safety checks are necessary to ensure that the risk of ignition is minimised. For repair to the refrigerating system, the following precautions shall be complied with prior to conducting work on the system. 2)Work procedure Work shall be undertaken under a controlled procedure so as to minimise the risk of a flammable gas or vapour being present while the work is being performed.
4

1. Before use
3) General work area All maintenance staff and others working in the local area shall be instructed on the nature of work being carried out. Work in confined spaces shall be avoided. The area around the workspace shall be sectioned off. Ensure that the conditions within the area have been made safe by control of flammable material. 4) Checking for presence of refrigerant The area shall be checked with an appropriate refrigerant detector prior to and during work, to ensure the technician is aware of potentially flammable atmospheres. Ensure that the leak detection equipment being used is suitable for use with flammable refrigerants, i.e. non-sparking, adequately sealed or intrinsically safe. 5) Presence of fire extinguisher If any hot work is to be conducted on the refrigeration equipment or any associated parts, appropriate fire extinguishing equipment shall be available to hand. Have a dry powder or CO2 fire extinguisher adjacent to the charging area. 6) No ignition sources No person carrying out work in relation to a refrigeration system which involves exposing any pipe work that contains or has contained flammable refrigerant shall use any sources of ignition in such a manner that it may lead to the risk of fire or explosion. All possible ignition sources, including cigarette smoking, should be kept sufficiently far away from the site of installation, repairing, removing and disposal, during which flammable refrigerant can possibly be released to the surrounding space. Prior to work taking place, the area around the equipment is to be surveyed to make sure that there are no flammable hazards or ignition risks.”No Smoking” signs shall be displayed. 7) Ventilated area Ensure that the area is in the open or that it is adequately ventilated before breaking into the system or conducting any hot work. A degree of ventilation shall continue during the period that the work is carried out. The ventilation should safely disperse any released refrigerant and preferably expel it externally into the atmosphere. 8) Checks to the refrigeration equipment Where electrical components are being changed, they shall be fit for the purpose and to the correct specification. At all times the manufacturer’s maintenance and service guidelines shall be followed. If in doubt consult the manufacturer’s technical department for assistance. The following checks shall be applied to installations using flammable refrigerants: -The charge size is in accordance with the room size within which the refrigerant containing parts are installed; -The ventilation machinery and outlets are operating adequately and are not obstructed; -If an indirect refrigerating circuit is being used, the secondary circuit shall be checked for the presence of refrigerant; -Marking to the equipment continues to be visible and legible. Markings and signs that are illegible shall be corrected; -Refrigeration pipe or components are installed in a position where they are unlikely to be exposed to any substance which may corrode refrigerant containing components, unless the components are constructed of materials which are inherently resistant to being corroded or are suitably protected against being so corroded.
5

1. Before use
9) Checks to electrical devices Repair and maintenance to electrical components shall include initial safety checks and component inspection procedures. If a fault exists that could compromise safety, then no electrical supply shall be connected to the circuit until it is satisfactorily dealt with. If the fault cannot be corrected immediately but it is necessary to continue operation, an adequate temporary solution shall be used. This shall be reported to the owner of the equipment so all parties are advised. Initial safety checks shall include: .That capacitors are discharged: this shall be done in a safe manner to avoid possibility of sparking; .That there no live electrical components and wiring are exposed while charging, recovering or purging the system; .That there is continuity of earth bonding.
7.Repairs to sealed components 1)During repairs to sealed components, all electrical supplies shall be disconnected from the equipment being worked upon prior to any removal of sealed covers, etc. If it isabsolutely necessary to have an electrical supply to equipment during servicing, then a permanently operating form of leak detection shall be located at the most critical point to warn of a potentially hazardous situation. 2) Particular attention shall be paid to the following to ensure that by working on electrical components, the casing is not altered in such a way that the level of protection is affected. This shall include damage to cables, excessive number of connections, terminals not made to original specification, damage to seals, incorrect fitting of glands, etc. Ensure that apparatus is mounted securely. Ensure that seals or sealing materials have not degraded such that they no longer serve the purpose of preventing the ingress of flammable atmospheres. Replacement parts shall be in accordance with the manufacturer’s specifications. NOTE: The use of silicon sealant may inhibit the effectiveness of some types of leak detection equipment. Intrinsically safe components do not have to be isolated prior to working on them.
8.Repair to intrinsically safe components Do not apply any permanent inductive or capacitance loads to the circuit without ensuring that this will not exceed the permissible voltage and current permitted for the equipment in use. Intrinsically safe components are the only types that can be worked on while live in the presence of a flammable atmosphere.The test apparatus shall be at the correct rating. Replace components only with parts specified by the manufacturer. Other parts may result in the ignition of refrigerant in the atmosphere from a leak.
6

1. Before use
9.Cabling Check that cabling will not be subject to wear,corrosion, excessive pressure, vibration, sharp edges or any other adverse environmental effects. The check shall also take into account the effects of aging or continual vibration from sources such as compressors or fans.
10.Detection of flammable refrigerants Under no circumstances shall potential sources of ignition be used in the searching for or detection of refrigerant leaks. A halide torch (or any other detector using a naked flame) shall not be used.
11.Leak detection methods The following leak detection methods are deemed acceptable for systems containing flammable refrigerants. Electronic leak detectors shall be used to detect flammable refrigerants, but the sensitivity may not be adequate, or may need re-calibration. (Detection equipment shall be calibrated in a refrigerant-free area.) Ensure that the detector is not a potential source of ignition and is suitable for the refrigerant used. Leak detection equipment shall be set at a percentage of the LFL of the refrigerant and shall be calibrated to the refrigerant employed and the appropriate percentage of gas (25% maximum) is confirmed. Leak detection fluids are suitable for use with most refrigerants but the use of detergents containing chlorine shall be avoided as the chlorine may react with the refrigerant and corrode the copper pipe-work. If a leak is suspected, all naked flames shall be removed/ extinguished. If a leakage of refrigerant is found which requires brazing, all of the refrigerant shall be recovered from the system, or isolated (by means of shut off valves) in a part of the system remote from the leak. Oxygen free nitrogen (OFN) shall then be purged through the system both before and during the brazing process.
12.Removal and evacuation When breaking into the refrigerant circuit to make repairs ­ or for any other purpose ­conventional procedures shall be used. However, it is important that best practice is followed since flammability is a consideration. The following procedure shall be adhered to: · Remove refrigerant; · Purge the circuit with inert gas; · Evacuate; · Purge again with inert gas; · Open the circuit by cutting or brazing. The refrigerant charge shall be recovered into the correct recovery cylinders. The system shall be “flushed” with OFN to render the unit safe. This process may need to be repeated several times. Compressed air or oxygen shall not be used for this task. Flushing shall be achieved by breaking the vacuum in the system with OFN and continuing to fill until the working pressure is achieved, then venting to atmosphere, and finally pulling down to a vacuum. This process shall be repeated until no refrigerant is within the system. When the final OFN charge is used, the system shall be vented down to atmospheric pressure to enable work to take place. This operation is absolutely vital if brazing operations on the pipe-work are to take place. Ensure that the outlet for the vacuum pump is not close to any ignition sources and there is ventilation available.
7

1. Before use
13.Charging procedures In addition to conventional charging procedures, the following requirements shall be followed. ­ Ensure that contamination of different refrigerants does not occur when using charging equipment. Hoses or lines shall be as short as possible to minimise the amount of refrigerant contained in them. ­ Cylinders shall be kept upright.
­ Ensure that the refrigeration system is earthed prior to charging the system with refrigerant.
­ Label the system when charging is complete (if not already).
­ Extreme care shall be taken not to overfill the refrigeration system. Prior to recharging the system it shall be pressure tested with OFN. The system shall be leak tested on completion of charging but prior to commissioning. A follow up leak test shall be carried out prior to leaving the site.
14.Decommissioning Before carrying out this procedure, it is essential that the technician is completely familiar with the equipment and all its detail. It is recommended good practice that all refrigerants are recovered safely. Prior to the task being carried out, an oil and refrigerant sample shall be taken in case analysis is required prior to re-use of reclaimed refrigerant. It is essential that electrical power is available before the task is commenced. a) Become familiar with the equipment and its operation. b) Isolate system electrically. c) Before attempting the procedure ensure that: .Mechanical handling equipment is available, if required, for handling refrigerant cylinders; .All personal protective equipment is available and being used correctly; .The recovery process is supervised at all times by a competent person; .Recovery equipment and cylinders conform to the appropriate standards. d) Pump down refrigerant system, if possible. e) If a vacuum is not possible, make a manifold so that refrigerant can be removed from various parts of the system. f) Make sure that cylinder is situated on the scales before recovery takes place. g) Start the recovery machine and operate in accordance with manufacturer’s instructions. h) Do not overfill cylinders. (No more than 80%volume liquid charge). I) Do not exceed the maximum working pressure of the cylinder, even temporarily. j) When the cylinders have been filled correctly and the process completed, make sure that the cylinders and the equipment are removed from site promptly and all isolation valves on the equipment are closed off. k) Recovered refrigerant shall not be charged into another refrigeration system unless it has been cleaned and checked.
15.Labelling Equipment shall be labelled stating that it has been de- commissioned and emptied of refrigerant. The label shall be dated and signed. Ensure that there are labels on the equipment stating the equipment contains flammable refrigerant.
16.Recovery When removing refrigerant from a system, either for servicing or decommissioning, it is recommended good practice that all refrigerants are removed safely. When transferring refrigerant into cylinders, ensure that only appropriate refrigerant recovery cylinders are employed. Ensure that the correct number of cylinders for holding
8

1. Before use
the total system charge is available. All cylinders to be used are designated for the recovered refrigerant and labelled for that refrigerant (i.e. special cylinders for the recovery of refrigerant). Cylinders shall be complete with pressure relief valve and associated shut-off valves in good working order. Empty recovery cylinders are evacuated and, if possible, cooled before recovery occurs. The recovery equipment shall be in good working order with a set of instructions concerning the equipment that is at hand and shall be suitable for the recovery of flammable refrigerants. In addition, a set of calibrated weighing scales shall be available and in good working order. Hoses shall be complete with leak-free disconnect couplings and in good condition. Before using the recovery machine, check that it is in satisfactory working order, has been properly maintained and that any associated electrical components are sealed to prevent ignition in the event of a refrigerant release. Consult manufacturer if in doubt. The recovered refrigerant shall be returned to the refrigerant supplier in the correct recovery cylinder, and the relevant Waste Transfer Note arranged. Do not mix refrigerants in recovery units and especially not in cylinders. If compressors or compressor oils are to be removed, ensure that they have been evacuated to an acceptable level to make certain that flammable refrigerant does not remain within the lubricant. The evacuation process shall be carried out prior to returning the compressor to the suppliers. Only electric heating to the compressor body shall be employed to accelerate this process. When oil is drained from a system, it shall be carried out safely. The unit contains fluorinated greenhouse gases. The refrigerant must not be released into the air! All products comply with the following EU regulations: Low Voltage Directive, Electromagnetic Compatibility.
9

1. Before use

1.2 Safety precautions
The following symbols are very important. Please be sure to understand their meaning, which concerns the product and your personal safety.

Warning

Caution

Prohibition

User Manual

The installation, dismantlement To avoid electrical shock, make Be sure to read this manual before

and maintenance of the unit must be performed by qualified personnel. It is forbidden to do any changes to the structure of the unit.

sure to disconnect the power supply 1 minute or more before servicing the electrical parts. Even after 1 minute, always measure the voltage at the terminals of main

use.

Otherwise injury of person or unit circuit capacitors or electrical parts

damage might happen.

and, before touching, make sure

that those voltages are lower

than the safety voltage.

Ground wire

For sanitary hot water, please always add a mixture valve before water tap and set it to proper temperature.

Use a dedicated socket for this unit, otherwise malfunction may occur.

The power supply to the unit must be grounded.

This appliance can be used by children aged from 8 years and above and persons with reduced physical, sensory or mental capabilities or lack of experience and knowledge if they have been given supervision or instruction concerning use of the appliance in a safe way and understand the hazards involved. Children shall not play with the appliance. Cleaning and user maintenance shall not be made by children without supervision.

Do not touch the air outlet grill when fan motor is running.

Do not touch the power plug with Do not operate your air conditioner

wet hands. Never pull out the plug in a wet room such as a bathroom

by pulling the power cable.

or laundry room.Water or any kind

of liquid is strictly forbidden to be

poured into the product, or may

cause electric creepage or

breakdown of the product.

10

1. Before use

Fuse

Steel Copper

If the supply cord is damaged, it must be replaced by the manufacturer, its service agent or similarly qualified persons in order to avoid a hazard.

Please select the correct fuse or breaker as per recommended. Steel wire or copper wire cannot be taken as substitute for fuse or breaker. Otherwise, damages maybe caused.

Be aware fingers might be hurt by the fin of the coil.

ON

Main

Power Cable RCD

OFF

Indoor control

unit

It is mandatory to use a suitable circuit breaker for the heat pump and make sure the power supply to the unit corresponds to the specifications. Otherwise the unit might be damaged.

Disposal of Scrap Batteries(if there is).Please discard the batteries as sorted municipal waste at the accessible collection point.

An all-pole disconnection device which has at least 3mm clearances in all poles , and have a leakage current that may exceed 10mA, the residual current device (RCD) having a rated residual operating current not exceeding 30mA, and disconnection must be incorporated in the fixed wiring in accordance with the wiring rules.

System water filling

T/P valve

Connect to heating/cooling system

Connect to heat pump

Buffer tank

One way valve Filter

1. It’s suggested to use pure water for filling the system. 2. If use city water for filling, please soften the water and add a filter. Note: After filling, the system of water system should be 0.15~0.6MPa.

City water inlet

This marking indicates that this product should not be disposed with other household wastes throughout the EU. To prevent possible harm to the environment or human health from uncontrolled waste disposal, recycle it responsibly to promote the sustainable reuse of material resources. To return your used device, please use the return and collection systems or contact the retailer where the product was purchased. They can take this product for environmental safe recycling.

11

Evaporator

1. Before use
1.3 Working principle
Water Outlet

Power supply Four-way vavle
Compressor

Water inlet

Water pump

Filter

Heat exchanger

Three-way valve

Pressure check valve
Fan motor

Refrigerant

Filter

T-connector

Heating Cooling

12

1. Before use
1.4 Main components
1.4.1 Indoor control unit
Thermal 6/9/12

Cable gland

Safety valve kit

Operation panel

Water outlet 2 Water outlet 1

Door

13

Water inlet Electric box cover Water pump
Electric heater Water pump

1. Before use
1.4.2 Monoblock unit
Thermal 6/9/12
Thermal 6 GWP: 675: 0,61 tonnes equivalent CO2, refrigant/quantity: R32/0,9kg Thermal 9 GWP: 675: 0,95 tonnes equivalent CO2, refrigant/quantity: R32/1,4kg. Thermal 12 GWP: 675: 1,22 tonnes equivalent CO2, refrigant/quantity: R32/1,8kg.
14

1. Before use
1.5 Specifications

Thermal 6

Thermal 9

Thermal 12

Note: (1) Heating condition: water inlet/outlet temperature: 30/35, Ambient temperature: DB 7/WB 6; (2) Heating condition: water inlet/outlet temperature: 40/45, Ambient temperature: DB 7/WB 6; (3) Cooling condition: water inlet/outlet temperature: 23/18, Ambient temperature: DB 35/WB 24; (4) Cooling condition: water inlet/outlet temperature: 12/7, Ambient temperature: DB 35/WB 24; (5) The specifications are subject to change without prior notice. For actual specifications of unit, please refer to the stickers on the unit.
15

2. Assembly Configurations – Flowchart
16

Locate the Configuration that Meets Your Needs
Follow the flowchart on the right in order to locate which of the assembly configuration matches the needs of the end user, each of which contains specific assembly and wiring diagrams, with software instructions.
Beginning from the green “Start Here” bubble, follow the appropriate arrows to each question, which are dependent on the needs of the user.
The corresponding assembly instructions will be found by turning to the page number in the end bubble.
Note: The instructions in this section are meant to achieve the minimum requirements for successful system operation only.
For more in-depth settings explanations, please refer to the users manual.

Please ensure that the configuration matches the assembly drawing depicted on the right for a one temperature zone without domestic hot water setup.
Note: Refer to the next page for wiring and software operation instructions.

Name Temp.Sensor Safety valve Kit Ball valve Water filter Air purging valve

Symbol

Name Water pump Mixing valve Motorized valve Expansion tank

Symbol

Notice: The Fan Coil Unit, Floor Heating System, and Radiator are placeholder distribution systems only and can be substituted by any other appropriate distribution systems.

Note:Dotted lines meanable to be controlled by the Heat Pump.

2. Assembly Configurations – Drawing 1
17

One Temperature Zone ,without DHW

2. Assembly Configurations – Drawing 1
Assembly 1: Wiring Diagram
To achieve successful operation at a minimum, ensure the ports below are properly connected.
Software: Basic Settings
1.Set the needed working modes of the unit via the menu
2.Temperature configuration options for Heating/Cooling circuit 1 are found under H.Configuring the set water heating temperatures:
H.1.Setting a heating curve:
H.2. If no heating curve is desired: C.Configuring the set water cooling temperature (if applicable): 3.Locate and activate the buffer tank and appropriate pumps under
18

Please ensure that the configuration matches the assembly drawing depicted on the right for a one temperature zone without domestic hot water setup, that includes a component circuit capable of heating or cooling only,through the use of a two-way motorized valve.

Note:

For the cooling-only or heating-only circuit, a motorized two-way valve can be connected to the unit, to cut the water supply during heating or cooling operation.

Refer to the next page for wiring and software operation instructions.

Name Temp.Sensor Safety valve Kit Ball valve Water filter Air purging valve

Symbol

Name

Symbol

Water pump

Mixing valve

Motorized valve Expansion tank Note:Dotted lines meanable to be controlled by the Heat Pump.

Notice: The Fan Coil Unit, Floor Heating System, and Radiator are placeholder distribution systems only and can be substituted by any other appropriate distribution systems.

2. Assembly Configurations – Drawing 2
19

One Temperature Zone ,without DHW,with a heating-only (or cooling-only) circuit,by usage of a motorized 2-way valve

2. Assembly Configurations – Drawing 2
Assembly 2: Wiring Diagram
To achieve successful operation at a minimum, ensure the ports below are properly connected.
Software: Basic Settings
1.Set the needed working modes of the unit via the menu
2.Temperature configuration options for Heating/Cooling circuit 1 are found under H.Configuring the set water heating temperatures:
H.1.Setting a heating curve:
H.2. If no heating curve is desired: C.Configuring the set water cooling temperature (if applicable): 3.Locate and activate the buffer tank and appropriate pumps under
20

2. Assembly Configurations – Drawing 2
Software: Basic Settings (continued)
4.The location of the configuration for heating-only or cooling-only system is under
21

2. Assembly Configurations – Drawing 3
22

Please ensure that the configuration matches the assembly drawing depicted on the right for a two temperature zone without domestic hot water setup.

Note:

Refer to the next page for wiring and software operation instructions.

Name Temp.Sensor Safety valve Kit Ball valve Water filter Air purging valve

Symbol

Name Water pump Mixing valve Motorized valve Expansion tank

Symbol

Notice: The Fan Coil Unit, Floor Heating System,and Radiator are placeholder distribution systems only and can be substituted by any other appropriate distribution systems.

Note:Dotted lines meanable to be controlled by the Heat Pump.

Two Temperature Zones ,without DHW

2. Assembly Configurations – Drawing 3
Assembly 3: Wiring Diagram
To achieve successful operation at a minimum, ensure the ports below are properly connected.
For connection for mixing valve 2,please refers to the appendix A (on page 128-129) of this manual for more information.
Software: Basic Settings
1.Set the needed working modes of the unit via the menu
2.Temperature configuration options for Heating/Cooling circuit 1 are found under H.Configuring the set water heating temperatures:
H.1.Setting a heating curve:
H.2. If no heating curve is desired: C.Configuring the set water cooling temperature (if applicable): 3.Locate and activate the buffer tank and appropriate pumps under
23

Dependent on whether cooling is needed

2. Assembly Configurations – Drawing 3
Software: Basic Settings (continued)
3.(cont.) Configure the water pump to operate for heating or cooling:
4.Temperature configuration options for Heating/Cooling circuit 2 are found under Please activate entire Heating/Cooling circuit 2 setting
H. Configuring the set water heating temperatures: H.1.Setting a heating curve:
H.2. If no heating curve is desired: C. Configuring the set water cooling temperature (if applicable): 4.1.Activate the mixing valve to manage the second circuit: Note: This pair of settings will interpret “Heating/Cooling Circuit 2 as the low demand distribution system, requiring a lower set temperature for heating and higher set temperature for cooling.
24

Please ensure that the configuration matches the assembly drawing depicted on the right for a two temperature zone without domestic hot water setup, that includes a component circuit capable of heating or cooling only,through the use of a two-way motorized valve.

Note:

For the cooling-only or heating-only circuit, a motorized two-way valve can be connected to the unit, to cut the water supply during heating or cooling operation.

Refer to the next page for wiring and software operation instructions.

Name Temp.Sensor Safety valve Kit Ball valve Water filter Air purging valve

Symbol

Name

Symbol

Water pump Mixing valve Motorized valve Expansion tank Note:Dotted lines meanable to be controlled by the Heat Pump.

Notice: The Fan Coil Unit, Floor Heating System, and Radiator are placeholder distribution systems only and can be substituted by any other appropriate distribution systems.

2. Assembly Configurations – Drawing 4
25

Two Temperature Zones ,without DHW,with a heating-only (or cooling-only) circuit,by usage of a motorized 2-way valve

2. Assembly Configurations – Drawing 4
Assembly 4: Wiring Diagram
To achieve successful operation at a minimum, ensure the ports below are properly connected.
For connection for mixing valve 2,please refers to the appendix A (on page 128-129) of this manual for more information.
Software: Basic Settings
1.Set the needed working modes of the unit via the menu
2.Temperature configuration options for Heating/Cooling circuit 1 are found under H.Configuring the set water heating temperatures:
H.1.Setting a heating curve:
H.2. If no heating curve is desired: C.Configuring the set water cooling temperature (if applicable): 3.Locate and activate the buffer tank and appropriate pumps under
26

Dependent on whether cooling is needed

2. Assembly Configurations – Drawing 4
Software: Basic Settings (continued)
3.(cont.) Configure the water pump to operate for heating or cooling:
4. The location of the configuration for heating-only or cooling-only system is under
5. Temperature configuration options for Heating/Cooling circuit 2 are found under H. Configuring the set water heating temperatures: H.1.Setting a heating curve:
H.2. If no heating curve is desired:
C. Configuring the set water cooling temperature (if applicable): 5.1. Activate the mixing valve to manage the second circuit: Note: This pair of settings will interpret “Heating/Cooling Circuit 2 as the low demand distribution system,requiring a lower set temperature for heating and higher set temperature for cooling.
27

2. Assembly Configurations – Drawing 5
28

Please ensure that the configuration matches the assembly drawing depicted on the right for a two temperature zone without domestic hot water setup, that utilizes the secondary pump for a heating-only operation.

Note:

For the heating-only circuit, a motorized two-way valve can be connected to the unit,to cut the water supply during heating operation.

Refer to the next page for wiring and software operation instructions.

Name Temp.Sensor Safety valve Kit Ball valve Water filter Air purging valve

Symbol

Name Water pump Mixing valve Motorized valve Expansion tank

Symbol

Notice: The Fan Coil Unit, Floor Heating System, and Radiator are placeholder distribution systems only and can be substituted by any other appropriate distribution systems.

Note:Dotted lines meanable to be controlled by the Heat Pump.

Two Temperature Zones ,without DHW,with a heating-only circuit,enabled by setting the secondary pump to heating-only

2. Assembly Configurations – Drawing 5
Assembly 5: Wiring Diagram
To achieve successful operation at a minimum, ensure the ports below are properly connected.
For connection for mixing valve 2,please refers to the appendix A (on page 128-129) of this manual for more information.
Software: Basic Settings
1.Set the needed working modes of the unit via the menu
2.Temperature configuration options for Heating/Cooling circuit 1 are found under H.Configuring the set water heating temperatures:
H.1.Setting a heating curve:
H.2. If no heating curve is desired: C.Configuring the set water cooling temperature (if applicable): 3.Locate and activate the buffer tank and appropriate pumps under
29

2. Assembly Configurations – Drawing 5
Software: Basic Settings (continued)
3.(cont.) Configure the water pump to operate for heating or cooling:
4. Temperature configuration options for Heating/Cooling circuit 2 are found under H. Configuring the set water heating temperatures: H.1.Setting a heating curve:
H.2. If no heating curve is desired: C. Configuring the set water cooling temperature (if applicable): 4.1. Activate the mixing valve to manage the second circuit: Note: This pair of settings will interpret “Heating/Cooling Circuit 2 as the low demand distribution system,requiring a lower set temperature for heating and higher set temperature for cooling.
30

Please ensure that the configuration matches the assembly drawing depicted on the right for a one temperature zone setup that includes domestic hot water.
Note: Refer to the next page for wiring and software operation instructions.

Name Temp.Sensor Safety valve Kit Ball valve Water filter Air purging valve

Symbol

Name

Symbol

Water pump

Notice: The Fan Coil Unit,

Mixing valve

Floor Heating System, and

Radiator are placeholder

Motorized valve

distribution systems only

Expansion tank

and can be substituted by any other appropriate

Note:Dotted lines meanable to be controlled by the Heat Pump.distribution systems.

2. Assembly Configurations – Drawing 6
31

One Temperature Zone ,with DHW

2. Assembly Configurations – Drawing 6
Assembly 6: Wiring Diagram
To achieve successful operation at a minimum, ensure the ports below are properly connected.
Software: Basic Settings
1.Set the needed working modes of the unit via the menu
2.Temperature configuration options for Heating/Cooling circuit 1 are found under H.Configuring the set water heating temperatures:
H.1.Setting a heating curve:
H.2. If no heating curve is desired: C.Configuring the set water cooling temperature (if applicable): 3.Locate and activate the buffer tank and appropriate pumps under
32

2. Assembly Configurations – Drawing 6
Software: Basic Settings (continued)
4. Double-check to ensure that the Domestic Hot Water option is enabled under 5. Configure the desired setpoint for water temperature (default set to 50°C):
33

2. Assembly Configurations – Drawing 7
34

Please ensure that the configuration matches the assembly drawing depicted on the right for a one temperature zone setup that includes domestic hot water,that also includes a component circuit capable of heating or cooling only, through the use of a two-way motorized valve.

Note:

For the cooling-only or heating-only circuit, a motorized two-way valve can be connected to the unit, to cut the water supply during heating or cooling operation.

Refer to the next page for wiring and software operation instructions.

Name Temp.Sensor Safety valve Kit Ball valve Water filter Air purging valve

Symbol

Name

Symbol

Water pump

Notice: The Fan Coil Unit,

Floor Heating System, and

Mixing valve

Radiator are placeholder

Motorized valve

distribution systems only and can be substituted by

Expansion tank

any other appropriate

distribution systems.

Note:Dotted lines meanable to be controlled by the Heat Pump.

One Temperature Zone ,with DHW,with a heating-only (or cooling-only) circuit,by usage of a motorized 2-way valve

2. Assembly Configurations – Drawing 7
Assembly 7: Wiring Diagram
To achieve successful operation at a minimum, ensure the ports below are properly connected.
Software: Basic Settings
1.Set the needed working modes of the unit via the menu
2.Temperature configuration options for Heating/Cooling circuit 1 are found under H.Configuring the set water heating temperatures:
H.1.Setting a heating curve:
H.2. If no heating curve is desired: C.Configuring the set water cooling temperature (if applicable): 3.Locate and activate the buffer tank and appropriate pumps under
35

2. Assembly Configurations – Drawing 7
Software: Basic Settings (continued)
4.The location of the configuration for heating-only or cooling-only system is under
5. Double-check to ensure that the Domestic Hot Water option is enabled under 6. Configure the desired setpoint for water temperature (default set to 50°C):
36

Please ensure that the configuration matches the assembly drawing depicted on the right for a two temperature zone setup that includes domestic hot water.
Note: Refer to the next page for wiring and software operation instructions.

Name Temp.Sensor Safety valve Kit Ball valve Water filter Air purging valve

Symbol

Name

Symbol

Water pump Mixing valve Motorized valve Expansion tank

Notice: The Fan Coil Unit, Floor Heating System, and Radiator are placeholder distribution systems only and can be substituted by any other appropriate distribution systems.

Note:Dotted lines meanable to be controlled by the Heat Pump.

2. Assembly Configurations – Drawing 8
37

Two Temperature Zone ,with DHW

2. Assembly Configurations – Drawing 8
Assembly 8: Wiring Diagram
To achieve successful operation at a minimum, ensure the ports below are properly connected.
For connection for mixing valve 2,please refers to the appendix A (on page 128-129) of this manual for more information.
Software: Basic Settings
1.Set the needed working modes of the unit via the menu
2.Temperature configuration options for Heating/Cooling circuit 1 are found under H.Configuring the set water heating temperatures:
H.1.Setting a heating curve:
H.2. If no heating curve is desired: C.Configuring the set water cooling temperature (if applicable): 3.Locate and activate the buffer tank and appropriate pumps under
38

Dependent on whether cooling is needed

2. Assembly Configurations – Drawing 8
Software: Basic Settings (continued)
3.(cont.) Configure the water pump to operate for heating or cooling:
4. Temperature configuration options for Heating/Cooling circuit 2 are found under H. configuring the set water heating temperatures:
H.1. Setting a heating curve:
H.2. If no heating curve is desired:
C. Configuring the set water cooling temperature (if applicable): 4.1. Activate the mixing valve to manage the second circuit: Note: This pair of settings will interpret “Heating/Cooling Circuit 2 as the low demand distribution system,requiring a lower set temperature for heating and higher set temperature for cooling. 5. Double-check to ensure that the Domestic Hot Water option is enabled under
6. Configure the desired setpoint for water temperature (default set to 50°C):
39

2. Assembly Configurations – Drawing 9
40

Please ensure that the configuration matches the assembly drawing depicted on the right for a two temperature zone setup that includes domestic hot water, also that includes a component circuit capable of heating or cooling only, through the use of a two-way motorized valve.

Note:

For the cooling-only or heating-only circuit, a motorized two-way valve can be connected to the unit, to cut the water supply during heating or cooling operation.

Refer to the next page for wiring and software operation instructions.

Name Temp.Sensor Safety valve Kit Ball valve Water filter Air purging valve

Symbol

Name

Symbol

Water pump Mixing valve Motorized valve Expansion tank Note:Dotted lines meanable to be controlled by the Heat Pump.

Notice: The Fan Coil Unit, Floor Heating System, and Radiator are placeholder distribution systems only and can be substituted by any other appropriate distribution systems.

Two Temperature Zones ,without DHW,with a heating-only (or cooling-only) circuit,by usage of a motorized 2-way valve

2. Assembly Configurations – Drawing 9
Assembly 9: Wiring Diagram
To achieve successful operation at a minimum, ensure the ports below are properly connected.
For connection for mixing valve 2,please refers to the appendix A (on page 128-129) of this manual for more information.
Software: Basic Settings
1.Set the needed working modes of the unit via the menu
2.Temperature configuration options for Heating/Cooling circuit 1 are found under H.Configuring the set water heating temperatures:
H.1.Setting a heating curve:
H.2. If no heating curve is desired: C.Configuring the set water cooling temperature (if applicable): 3.Locate and activate the buffer tank and appropriate pumps under
41

Dependent on whether cooling is needed

2. Assembly Configurations – Drawing 9
Software: Basic Settings (continued)
3.(cont.) Configure the water pump to operate for heating or cooling:
4. The location of the configuration for heating-only or cooling-only system is under
5. Temperature configuration options for Heating/Cooling circuit 2 are found under H. configuring the set water heating temperatures:
H.1. Setting a heating curve:
H.2. If no heating curve is desired: C. Configuring the set water cooling temperature (if applicable): 5.1. Activate the mixing valve to manage the second circuit: Note: This pair of settings will interpret “Heating/Cooling Circuit 2 as the low demand distribution system,requiring a lower set temperature for heating and higher set temperature for cooling. 6. Double- check to ensure that the Domestic Hot Water option is enabled under 7. Configure the desired setpoint for water temperature (default set to 50°C):
42

Please ensure that the configuration matches the assembly drawing depicted on the right for a two temperature zone setup that includes domestic hot water, also that utilizes the secondary pump for a heating-only operation.
Note: For the heating-only circuit, a motorized two-way valve can be connected to the unit, to cut the water supply during heating operation.
Refer to the next page for wiring and software operation instructions.

Name Temp.Sensor Safety valve Kit Ball valve Water filter Air purging valve

Symbol

Name

Symbol

Water pump Mixing valve Motorized valve Expansion tank

Notice : The Fan Coil Unit, Floor Heating System, and Radiator are placeholder distribution systems only and can be substituted by any other appropriate distribution systems.

Note:Dotted lines meanable to be controlled by the Heat Pump.

2. Assembly Configurations – Drawing 10
43

Two Temperature Zones ,without DHW,with a heating-only circuit,by setting the secondary pump to heating-only

2. Assembly Configurations – Drawing 10
Assembly 10: Wiring Diagram
To achieve successful operation at a minimum, ensure the ports below are properly connected.
For connection for mixing valve 2,please refers to the appendix A (on page 128-129) of this manual for more information.
Software: Basic Settings
1.Set the needed working modes of the unit via the menu
2.Temperature configuration options for Heating/Cooling circuit 1 are found under H.Configuring the set water heating temperatures:
H.1.Setting a heating curve:
H.2. If no heating curve is desired: C.Configuring the set water cooling temperature (if applicable): 3.Locate and activate the buffer tank and appropriate pumps under
44

2. Assembly Configurations – Drawing 10
Software: Basic Settings (continued)
3.(cont.) Configure the water pump to operate for heating or cooling:
4. Temperature configuration options for Heating/Cooling circuit 2 are found under H. configuring the set water heating temperatures:
H.1. Setting a heating curve:
H.2. If no heating curve is desired: C. Configuring the set water cooling temperature (if applicable): 4.1. Activate the mixing valve to manage the second circuit:
Note: This pair of settings will interpret “Heating/Cooling Circuit 2 as the low demand distribution system,requiring a lower set temperature for heating and higher set temperature for cooling. 5. Double-check to ensure that the Domestic Hot Water option is enabled under
6. Configure the desired setpoint for water temperature (default set to 50°C):
45

3. Installation
3.1 General application system introduction
3.1.1 Sanitary hot water For safety purpose, it is recommended to set up the sanitary hot water system as shown below:

  1. Application 1 Magnesium rod
    Water from heat pump

T/P valve Water mixture valve

Water to heat pump

City water After heat pump is connected directly with the tank, city water will be heated up by hot water in the tank when it runs through a long coil inside the tank.
Disadvantage of this application is that heat is transferred from hot water in the tank to city water in the coil, thus it will have less volume of sanitary hot water available compared with other solutions. The advantages of this application is: A. Heat pump is connected with tank directly, so it can effectively ensures the water flow rate inside heat
pump system. B. Sanitary hot water is heated up by going through the coil, which makes it un necessary to have
sanitization. This will help the system save more energy.

46

3. Installation
2) Application 2

Magnesium rod

T/P valve

High temperature hot water export

Water mixture valve

Water from heat pump

Water to heat pump City water

By connecting the set of coil with heat pump directly, the safety of sanitary hot water inside the tank, is also ensured.
However, the capacity of the coil should be bigger than the maximum output of the unit (heat pump output at A7/W45). Usually this solution is used for working together with a heat pump whose capacity is less than 14kW.
The advantage of this application is that it can supply bigger volume of hot sanitary hot water.
The disadvantage of this application is that this coil may create big water flow resistance to heat pump water circuit. Thus it may need to add a secondary water pump to ensure the flow rate of heat pump unit. Otherwise it may affect unit efficiency or make the unit work improperly.

47

3. Installation
3) Application 3 A water to water plate heat exchanger can be used instead of the coil inside water tank, as shown below:

Magnesium rod

T/P valve

Water mixture High temperature hot water export valve

Water to water plate heat exchanger
Water from heat pump

Water to heat pump City water
With this application, it can not only ensure the volume of high temperature hot water, but also ensure the water flow rate of heat pump system. But the total cost will be higher than other two applications due to the cost the plate heat exchanger.
For all these three applications, it is recommended to add a manual mixture valve between city water inlet and water tank sanitary hot water outlet. This can maximize the utilization of hot water in the tank and also ensures its temperature won’t be too high to burn people.

If the structure of the tank permits, it is suggested to use a manual 4-way mixture valve in sanitary hot water system as shown below. This can further improve the utilization of hot water in the tank.

Magnesium rod

T/P valve

Water inlet from heat pump

4-Way water mixture valve

Water inlet from heat pump

City water
48

3. Installation
3.1.2 Heater /cooling distribution system Note: Buffer tank is always recommended to be included in the system , especially when the distribution system has water volume less then 20L/W. It should be installed between heat pump and distribution system , in order to: 1) Ensure heat pump unit has stable and enough water flow rate. 2) Store heat to minimize fluctuation of system heating/cooling load. 3) Extend the water volume of distribution system for proper working of heat pump unit.
If distribution system has enough water volume and can ensure the water flow rate of heat pump system , buffer tank can be excluded in the system . But in this way , please move temperature sensor Tc (Cooling/heating temperature sensor ) to water return pipe to minimize the fluctuation of water temperature caused by compressor speed changes.

M1

M

16

T/P valve

BFT

7

M2

T/P valve

FLH1 FLH2 FLH3

18 High temperature
hot water export

21

HWT

17

Drainage

20 City water

Item

Name

1 Monoblock unit

2 Indoor control unit

3 Buffer tank

4 Sanitary hot water storage tank

5 Motorized 3-way valve

6 Mixture valve 1 (0~10V)

7 Mixture valve 2 (0~10V)

8 Circulation pump

9 Sanitary hot water circulation pump(if need)

10 Circulation pump for distribution system 1

11 Circulation pump for distribution system 2

12 AH-Auxilary heater inside unit

13 HBH-Heating Back-up Heater

14 HWTBH-Hot Water Tank Back-up Heater

15 Sanitary hot water mixture valve

Item

Name

16 Safety valve kit

17 Ball valve

18 Pressure meter

19 Motorized 2-way valve

20 Filter

21 One-way valve

TW Hot water temperature

TC Cooling or heating water temperature

TR Room temperature

Tuo Monoblock unit outlet water temperature

Tui Monoblock unit return water temperature

Tup Monoblock unit coil temperature

Tv1 Temperature of water after mixture valve 1

Tv2 Temperature of water after mixture valve 2

49

3. Installation
3.1.3 Heating&Cooling Circuits:
This heat pump unit can control two totally different heating/cooling circuit, as shown in the drawing. Temperature setting can be made via menu “Heating & Cooling Circuit 1” and “Heating & Cooling Circuit 2”. Of course, if only one circuit is needed, “heating&cooling circuit 2” in system drawing can be omit, and leave the “Heating&cooling Circuit 2” under “heating&cooling circuit 2” set to OFF:
3.1.4 Heating & Cooling Circuit 1
Control of Mixing Valve 1(MV1): If system water temperature may higher(lower) than temperature that are need for circuit 1 in heating (cooling) operation, then a mixing valve can be add to circuit 1, and connected to MV1 port in indoor unit. Unit will control the mixing valve, mix the supply and return water of circuit 1 to have the temperature read via sensor TV1 get to value set under menu “Heating & Cooling Settings circuit1”. If so, TV1 under menu “”Heating & Cooling circuit1” should be activated under installer’s level:
50

3. Installation
Note: If TV1 is not connected, while it is activated via setting here, unit will show relative failure code. 3.1.5 Heating & Cooling circuit 2 Control of Mixing Valve 2(MV2): If system water temperature may higher(lower) than temperature that are need for circuit 2 in heating (cooling) operation, then a mixing valve can be added to circuit 2, and connected to MV2 port in indoor unit. Unit will control the mixing valve, mix the supply and return water of circuit 2 to have the temperature read via sensor TV2 get to value set under menu “Heating & Cooling Settings circuit 2”. If so, TV2 under menu “Heating & Cooling Settings circuit 2” should be activated under installer’s level:
Note: If TV2 is not connected, while it is activated via setting here, unit will show relative failure code.
Tips: When Mixing valve is needed? In general, if system water temperature may higher(lower) than temperature that are need for this circuit, then a mixing valve is needed.
A.If a system has two circuits, these two circuits may require different water temperatures. Heat pump has to take the higher(lower) setting among two circuits as the set temperature for heat pump when it works in heating(cooling). Thus, a mixing valve is needed for the circuit that with lower(higher) setting to ensure it gets water with correct temperature circulates in the circuit.
B.If a system has other heating source inside that is out the control of heat pump (e.g. Solar system), as the actual water temperature may exceed the set temperature of heat pump, a mixing valve is also needed to ensure the circuit gets water with correct temperature circulates in the circuit.
51

3. Installation
Control of Circu lation Pum p for circu it 1&2:
“With/without Buffer Tank”: Set whether it has a buffer tank between heat pump unit and distribution system or not. “P1 for Heating Operation” means circuit pump for circuit 1should work for heating operation. “P1 for Cooling Operation” means circuit pump for circuit 1should work for cooling operation. “P2 for Heating Operation” means circuit pump for circuit 2 should work for heating operation. “P2 for Cooling Operation” means circuit pump for circuit 2 should work for cooling operation. If “without buffer tank” is set, both P1(circulation pump for circuit 1) and P2(circulation pump for circuit 2) will only work when compressor is working in the same mode as the pump is set to. For example, if P1 is set to “P1 for Heating Operation”, P1 will be turned ON only when compressor is working in heating mode. If both “P1for Heating Operation” and “P1 for Cooling Operation” are both selected, P1 will be turned ON when compressor is working in both heating and cooling mode. When heat pump switches to DHW mode or stops after get the set temperature for heating or cooling, pump stops.
If “with buffer tank” is set, both P1(circulation pump for circuit 1) and P2(circulation pump fo circuit 2) will work once the distribution system has the heating or cooling demand, as per the pump setting, and obeys following rules:
Actual temperature in buffer tank detected via Tc 20 in heating. Only 20 and above can be useful for distribution system in heating operation.
Actual temperature in buffer tank detected via Tc 23 in cooling. Only 23 and below can be useful for distribution system in cooling operation. For example, if P1 is set to “P1 for Heating Operation”, P1 will start to work as long as the system has heating demands and Tc reading is no lower than 20 ,even if the unit is working in DHW mode or stops after get the set temperature.
“Working of P1(2) with High Demanding Signal” means whether P1(P2) should stop if signal for “high demanding” is off. For detailed meaning of “High Demanding Signal”, please refers to part “D” of “Terminal Block 4” of chapter “2.5.1”, “High demanding distribution system switch”.
3.1.6 Room temperature sensor:
Room temperature sensor (Tr) is recommended to be placed in a ideal position of the house to check the room temperature. Thus the unit can have room temperature control mode (please refers to 9.04 Basic Operation), and room temperature compensate function (please refers to 1.16 Room temp. effect on Heating Curve).
52

3. Installation
3.2 Tools needed
Most people already have the tools needed for installation: spirit level, pencil, crosshead screwdriver, drill, 8 mm. concrete drill bit, detection drill, square, tape measure or ruler, tape width 65 mm, hole saw about 80 mm (deviation in size may occur), knife and two adjustable spanners or pliers (and possibly torque wrench).

The installation of the product should be handled by professional installers or under their instructions.

3.3 Installation of the indoor control unit
3.3.1 Installation notes 1) The indoor control unit should be installed indoors and mounted on the wall, with water outlet
downwards. 2) The indoor control unit shall be placed in dry and well- ventilated environment. 3) Indoor control unit mustn’t be installed in an environment where volatile, corrosive or flammable liquid
or gas exists. 4) Enough space should be left around the indoor control unit for futher maintenance.
Please choose a suitable position to install the indoor control unit as follows:

500mm

100mm

100mm

600mm

53

3. Installation

3.3.2 Installation Indoor control unit should be mounted on the wall as per procedures below: 1) Take out the expansion bolts and mounting board from accessory and put the mounting board on the
wall horizontally; Mark on the wall the location for bolts through the holes on mounting board. 2) Drill holes with proper diameter for expansion bolts. 3) Unscrew the nuts out from the expansion bolts. 4) Fix the mounting board on the expansion bolts a little bit, but don’t be too tight. 5) Use a hammer to pound the expansion bolts into the drilled holes. Fasten the nuts by turning the wrench
to fix the mounting board on the wall. 6) Hang the indoor control unit onto the mounting board and make sure it’s placed well before you let go
your hands. The installation is finished.

1

2

3

4

5

6

Note: You must choose very firm wall for installation otherwise the bolts may get loose and unit be damaged!
If it’s wood wall, please use self-tapping screws in accessory instead of expansion bolts. Please hang the mounting board directly onto the wood wall without drilling holes. The wood wall must be firm enough. Wood walls that are too thin, too brittle or humid are not adequate for installation.
54

3. Installation
3.4 Installation of the monoblock unit
3.4.1 Installation notes 1) The monoblock unit can be located in a open space, corridor, balcony, and roof. 2) The monoblock unit shall be placed in dry and well-ventilated environment; If the monoblock unit is
installed in humid environment, electronic components may get corroded, or short-circuited because of heavy humidity. 3) Monoblock unit mustn’t be installed in an environment where volatile, corrosive or flammable liquid or gas exists. 4) Please don’t install monoblock unit close to bedroom or living room, because there is some noise when it’s running. 5) When installing the unit in harsh climatic conditions, sub-zero temperatures, snow, humidity…, please raise the unit above the ground by about 50cm. It’s recommended to install an awning above the monoblock unit, to protect the snow from clogging in the air inlet and outlet and ensure the normal running. 6) Please ensure there is drainage system around the location, to drain the condensate water under defrosting mode. 7) When installing the unit, tilt it by lcm/m for rain water evacuation. 8) Install monoblock unit far away from the exhaust port of kitchen, to avoid oil smoke entering into monoblock unit and adhering to heat exchanger. It’s hard to clean up. 9) Please don’t install the indoor control unit and monoblock unit in damp locations, otherwise it may cause short- circuit or corrosion of some components. The unit should be free from corrosive and moisture surrounding. Otherwise the lifetime of the unit might be shortened. 10) Please ensure enough space around the monoblock unit, for better ventilation and maintenance. Please refer to the illustration below.

500mm 400mm
1500mm (Front space)

150mm(Back space 500mm

650mm

500mm (Above ground)

55

3. Installation
3.4.2 Installation User can either use the dedicated mounting bracket from the supplier, or prepare a suitable bracket for the unit installation. Make sure the installation meets following requirements:

  1. The unit must be installed on flat concrete blocks, or a dedicated mounting bracket. The bracket should be able to support at least 5 times of unit’s weight.
  2. All nuts must be tightened after the bracket is fixed; otherwise, it may cause damage to the equipment. 3) User should double check and make sure the installation of unit is firm enough. 4) The bracket can be of stainless steel, galvanized steel, aluminum and other materials as required by the
    user. 5) Besides the mounting bracket, the user can also install the monoblock unit on two concrete blocks, or a
    raised concrete platform. Please make sure that the unit is securely fastened after installation. 6) Please see the dimensions of monoblock unit when choose a suitable wall bracket.

500mm

Hole for piping kits should lean to outside a little bit (8 degrees), to keep rain water or condensate water from flowing back indoors.

Sleeve 8°

Shield

56

3. Installation
3.5 Accessories
Accessories below are delivered together with the product . Please check in time. If there is any shortage or damage, please contact local distributor.

Name User’s manual Drain pipe Safety valve kit

Quantity 1 1 1

Picture
User Manual

Name TR-Room temperature sensor
TC-water temperature sensor for cooling and heating
TW-water temperature sensor for sanitary hot water TV1-water temperature sensor after mixture valve 1 TV2-water temperature sensor after mixture valve 2 Communication cable between indoor control unit and monoblock unit Communication cable Signal cable between indoor control unit and monoblock unit

Quantity 1 1 1 1 1 8 1

Name Indoor control unit bracket
Expansion bolts

Quantity 1 2

Picture

Picture

57

3. Installation
3.6 Wiring
2.6.1 Explanation of terminals 1) Terminal block 1

For user’s side

PE N L PE N1 L1 PE N2 L1 L2 L3 PE N3 L1 L2 L3 PE N L

A

B

C

A: Unit power supply (Power Cord: H05VV-F 3×2.5mm2) Unit power supply. Should be connected to city power input.

D

E

B: Power supply for AH-Auxiliary heater inside unit(Power Cord: H05VV-F 3×1.5mm2, city power input)
This should be connected to city power supply, 1 phase. It is for giving the power to auxiliary heater inside the indoor control unit.

Terminal block 1-B

PE N1 L1

AH Power Input

AH Power Output

AH
City power supply
C: Power supply for HWTBH-Hot Water Tank Back-up Heater(Power Cord: H05VV-F 3×1.5mm2, city power input)
If sanitary hot water tank has electric heater inside, one can connect this heater to heat pump unit, so to have it under the control of heat pump. In that way, city power input (1 phase or 3 phase) should be connected to this port “Electrical Heater Power Supply for Hot Water 5×1.5mm2”.

58

3. Installation
Terminal block 1-C
PE N2 L1 L2 L3
HWTBH Power Input

Terminal block 2-E
PE N2 L12 L22 L32
HWTBH Power Output

City power supply
And then connect electric heater inside sanitary hot water tank to port D on terminal block 2.

D: Power supply for HBH-Heating Back-up Heater (Power Cord: H05VV-F 5×1.5mm2, city power input)
When the house heating system also has a electric heater as a back-up, then this heater can also be connected to heat pump unit and under heat pump’s control. In that way, city power input (1 phase or 3 phase) should be connected to this port “Reserved Electrical Heater Power Supply 5×1.5mm2”, and then heater should be connected to port E on terminal block 2. PS: If external heating source (on house heating circuit or hot water circuit) is not electric heater but other heating sources, we can also connect it to the heat pump like this if they can be controlled by electric signal, to have them under the control of heat pump.

Terminal block 1-D
PE N3 L1 L2 L3
HBH Power Input

Terminal block 2-F
PE N3 L13 L23 L33
HBH Power Output

City power supply
E: Monoblock unit power supply (Power Cord: H05VV-F 3×2.5mm2, output) Monoblock unit power cable should be connected with these terminals so to get power from indoor control unit.
59

3. Installation
2) Terminal block 2

PE
For user’s side

P1 PE

P2 PE

P3 PE N2 L12 L22 L32 PE N3 L13 L23 L33

A

B

C

D

E

A,B,C: Water Pump A-Pump 1: Circulation pump(heating) B-Pump 2: Circulation pump(cooling) C-Pump 3: Circulation pump(hot water) Pump 0: DC pump inside the indoor control unit. If there is an external water pump in heating, cooling and hot water system, it can be connected to these ports, to be under the control of heat pump,
D: Power supply for HWTBH-Hot Water Tank Back-up Heater (Power Cord: H05VV-F 3×1.5mm2, power output)
Refer to explanation of port C of terminal block 1.
E: Power supply for HBH-Heating Back-up Heater (Power Cord: H05VV-F 5×1.5mm2, power output) Refer to explanation of port D of terminal block 1.

60

3. Installation
Explanation of connectors for other heating sources A: HWTBH-Hot water tank back-up heater Terminal block 1-C

Terminal block 2-D

PE N2 L1 L2 L3
HWTBH Power Input

PE N2 L12 L22 L32
HWTBH Power Output

City power supply

B: HBH-Heating back-up heater Terminal block 1-D
PE N3 L1 L2 L3
HBH Power Input

Terminal block 2-E
PE N3 L13 L23 L33
HBH Power Output

City power supply

61

3. Installation
3) Terminal block 3

Application Side

G A B 12V G 24VCOM 1 G 24V COM 2

A

B

C

A: Signal cable to monoblock unit Please connect A and B together with A and B on monoblock unit.
B,C: Motorized Water mixture valve 1&2: As explained in System illustration chapters, this unit can have two water mixture valves for distribution system under its control.
Water Mixture Valve 1 for Heating & Cooling circuit 1 Water Mixture Valve 2 for Heating & Cooling circuit 2

62

3. Installation
4) Terminal block 4

Application Side

COM ES COM CS COM HS COM TH

A

B

C

D

D: Electrical Utility Lock Input Some electricity companies offer a special rate if the house power consumption is lowered to a certain value during peak time. If the unit is supposed to stop working during this period, one can connect the signal from electricity company to this “External Shutdown” port and use the parameter setting to activate this function.

E,F: Cool mode & heat mode switch-over This unit can switch over between heating and cooling functions automatically, according to ambient temperature, or external signal input. For ambient temperature switching, please refer to part 1.06 of introduction of user’s interface for detailed setting. For external signal input, external signal should be connected to “COOL MODEL SWITCH” for cooling operation, and “HEAT MODE SWITCH” for heating operation.

G: High demanding distribution system switch
When two heating distribution systems are connected, unit should always take the set temperature for high demanding circuit, which needs higher temperature in heating and lower temperature in cooling operation, as the set temperature for the heat pump unit.
However, when this high demanding circuit is not needed or has reached the set temperature, heat pump unit can switch the heat pump set temperature to the values set for the other circuit, for better efficiency.
This set of connector is used to receive the signal from high demanding circuit, if has.
When “CLOSE” signal is received, unit works with high demanding. When “OPEN” signal is received, unit works with low demanding.

63

3. Installation
3.6.2 Wiring
It is recommended to use a suitable circuit breaker for the heat pump; The power supply to the heat pump unit must be grounded. The wiring should be done by professional person. The wiring should be comply with the local industry regulation. The wiring should be done after the unit is powered off. Cable should be fixed tightly, to ensure it won’t get loose. Don’t connect several parts of cables together to use. Make sure the power supply in the local coincide with the power supply marked in rating label. Make sure power supply, cable and socket can meet the requirement of the input power of the unit.

Installation sketch
Signal cable between indoor control and monoblock unit

Auxiliary Heater power cable

Main power in user side

Power cable between indoor control and monoblock unit

Heat pump unit power supply

Sensor cable
64

3. Installation
Before wiring, open the indoor control unit front panel and take off the electronic box cover.

  1. Heat pump unit power supply Get a power cable in suitable length that complies to the local safety regulations.

L N PE

C
B A

A. Insert one end of this cable through the cable gland on bottom of the indoor control unit, and connect it with heat pump power supply terminals (PE, N, L).
B. Fasten the cable gland to ensure the cable won’t get loosen.
C. Connect the other end to the city power supply.

65

3. Installation
2) Auxiliary Heater power cable Get a power cable in suitable length that complies to the local safety regulations.

L1 N1 PE

C
B A

A. Insert one end of this cable through the cable gland on bottom of the indoor control unit, and connect it with AH power supply terminals (PE, N1, L1).
B. Fasten the cable gland to ensure the cable won’t get loosen.
C. Connect the other end to the city power supply.

66

3. Installation
3) Signal cable between indoor control unit and monoblock unit 10M communication cable is packed in accessories bag.
B A
C
AB corresponding with each other
A. Insert one end of this cable through the cable gland on bottom of the indoor control unit, and connect this cable to A and B on terminal block. B. Fasten the cable gland to ensure the cable won’t get loosen. C. Take off the top cover , and connect the other end of communication cable to correspondent terminal block through cable gland. Fix the cable with cable gland after cable is well connected. A and B on monoblock unit should be connected with A and B on indoor control unit, otherwise unit will show communication failure.
67

A B

3. Installation
4.1) Power cable between indoor control unit and monoblock unit Prepare a 3 cores power cable with suitable length that complies the local safety regulations,
B A
C
Shown as “Outdoor power supply” on wiring diagram
A. Insert one end of this cable through the cable gland on bottom of the indoor control unit, and connect this power cable to “Outdoor power supply” on indoor control unit terminal block. B. Fasten the cable gland to ensure the cable won’t get loosen. C. Connect cable between indoor control unit and monoblock unit to correspondent terminal block according to the wiring diagram. Fasten the cable gland to ensure the cable won’t get loosen. When connecting the power cable between the monoblock unit and indoor control unit, cables connected to the terminal block in indoor control unit must match these in monoblock unit. For example, if the terminals and power cables are connected as gree/yellow cable, Lred cable, Nblue cable, Sblack cable in indoor control unit, the connections in the monoblock unit should be in the same way.
68

3. Installation
5) Sensor cables Take all sensors and communication cables out from the accessories bag. Connect the sensors together with the quick connectors on communication cables and insert the end with the connector into the indoor unit through cable gland. Connect them with the quick connector inside the indoor unit and place all sensors in right positions. Fasten the cable gland after installations.
Sensor cable connection Indoor control PCB
Communication cable
Sensor
Place all sensors in right positions

COM TW COM TC COM TR COM TV1 COM TV2 COM TUP COM TUI COM TUO

A

B

TW-Water temperature sensor for sanitary hot water

TC-Water temperature sensor for cooling and heating Connect these sensors with communication cables by quick connector, and then connect

A TR-Room temperature sensor

communication cable (the end without quick connector) with terminal block. (These

sensors are packed inside the accessories TV1-Water temperature sensor after mixture valve 1 bag).

TV2-Water temperature sensor after mixture valve 2

TUP-Coil temperature sensor B TUI-Water inlet temperature sensor
TUO-Water outlet temperature sensor

Connect these sensors with communication cables by quick connector, and then connect communication cable (the end without quick connector) with terminal block. (These sensors are installed already, but should be connected to terminal block inside indoor control box via communication cables).

69

3. Installation
Install the electric box cover on indoor control unit and electric box cover on monoblock unit back, and close the door of indoor control unit.
70

3. Installation
3.7 Installation of safety valve kit

  1. Install the safety valve kit to the connector on top of indoor control unit.
  2. Connect the drainage pipe to safety valve outlet. Safety valve outlet
  3. Have the drainage pipe out from the hole on the bottom by going through the unit. Drainage pipe in
    Drainage pipe out
    71

3. Installation
3.8 Water pipe connection
After installing the unit, please connect the water inlet and outlet pipe according to the local regulations. Please carefully select and operate the water pipe. After connection, the water piping should be pressure tested, cleaned before use.

  1. Filter A mesh filter must be installed in front of the water inlet of the unit and water tank, to keep the water quality and collect impurity contained in the water. Take care to keep the water filter mesh towards the bottom. Check valve is recommended to be installed at both sides of the filter, so as to clean or change the filter in a easier way.

Connect to unit water inlet
One way valve Drain pipe

Filter

Ball valve

City water inlet

  1. Insulation All pipes running hot water should be well insulated. The insulation must be tied up tightly without gap (But please don’t wrap up the check valve for future maintenance).
    Please ensure enough water pressure to send the water to the required height. If the water pressure is not enough to maintain proper water flow rate for the system, please add a water pump to increase the pumping head.
  2. Requirements of water quality A. Chloridion element in the water should be less than 300ppm(temperature is less than 60). B. PH value of water should be from 6 to 8. C. The water with ammonia can’t be used for the unit.
    If the water quality is bad, or water flow too little, scale formation or clogging may happen after unit running for a long time, then the efficiency of cooling or heating will be low or the unit will work abnormally. Please clean water before use, or use purified water. Make sure the water quality is good enough to keep the unit long-term running in high efficiency.

72

3. Installation
3.9 Test run
After installation finished, please fulfill the water system with water and purge out air in the system before start-up.

  1. Before start-up Before the unit starts up, a certain number of verifications must be performed on the installation to ensure that the unit will operate under the best possible conditions. The check list below is not exhaustive and should only be used as a minimum reference basis: A. Make sure fan rotates freely; B. Inspect all water piping for flow direction; C. Verify all system piping is correct for operation as per installation requirements; D. Check voltage of the unit power supply and make certain voltage is within authorized limitations; E. Make sure the unit is properly grounded; F. Check the presence of protective and breaking devices; G. Check all electric connections for tightness. H. Check all piping for leaks and air is well ventilated.
    If everything above is OK, the unit can start up. If any of them fails, please fix it.
  2. Pre-start up A. When the installation of unit is completed, water system pipes are well connected and air purging is
    done, no leakage or other problems, the unit can be powered to start up. B. Turn on the unit, press the on-off button on the operation panel to start the unit. Please check carefully
    if there is some abnormal noise or vibration, or the display of wired controller is normal or not. C. After the unit is working properly for 10 minutes, without any problem, then the pre-start up is
    completed; If not, please refer to the Service and Maintenance chapter in this manual to solve the problems.
    It is suggested not to run “heating” or “hot water” mode, when ambient temperature is over 32 ,otherwise unit may go into protection mode easily.
    73

4. Usage

4.1 Introduction of operation panel
A. Communication symbol

F. Touch screen panel
G. Mode

26
15
34.7

23.9

START ENGING
STOP
6.8

B. Working mode C. Functions D. Warning E. ON/OFF
H. Setting

A. Communication symbol When this symbol is in blue, it means communication is working correctly. When this symbol is grey, it means communication is broken.
B. Working mode Working mode switching symbol is ON when system working mode is under switching. If more than one working mode are activated at the same time, correspondents working mode symbol will be shown on the display.

Heating mode Cooling mode Hot water mode

C. Functions Sleep mode Interruption Sanitary hot water storage mode Preheating mode Sanitization mode Defrosting mode

74

4. Usage
D. Warning When the unit is having a protection or failure, a symbol will be shown on the display. Please enters into “Info” menu to check the protection or failure codes. Yellow—-Outdoor unit protection or failure
Red—-System protection or failure
Some information, protections and failures that are more likely to happen, will shown in front page so the customer can see it easier:
1. Coil Temp. too low This is indoor coil temperature too low. This happens in cooling operation of the unit. Too low coil temperature may make the water freeze up inside plate heat exchanger and cause damage. Compressor speed down if coil temp. lower than 2; Compressor stops if coil Temp. lower than -1; Compressor restarts if coil Temp. higher than 6. When this happens, please: A. Check whether set temperature for cooling is too low; whether system has too small water flow rate; check water system especially the filter. B. Check whether system has not enough refrigerant inside by measuring the evaporating pressure. C. Check whether ambient temperature is lower than 15.
2. Water flow rate too small System water flow rate is less than minimum allowable flow rate. Check the water system, especially the filter; check the working statue of water pump.
3. Water flow switch failure Water flow switch should be in open mode when unit circulation pump is working. If not, the unit think the flow switch itself is broken. Check whether flow switch is broken or not well connected. Check whether there has another pump that circulates the water through the unit, when unit circulation pump is working.
4. Communication Failure! Communication failure shown here means the communication between operation panel, indoor PCB and outdoor PCB have been set up, but communication data lost too much. Check whether communication cable is longer than 30M; whether there has a source of the disturbance nearby the unit. Unit recovers when communication recovers.
75

4. Usage
5. Serial port connect error Serial port connect error means the communication between operation panel and indoor PCB or outdoor PCB hasn’t been set up successfully. Check the cable connection in between. Check whether the last three switches on outdoor power PCB are set to 001; whether last three switches on indoor PCB are set to 001. Unit recovers when communication recovers.
6. Cooling water Temp. too low Compressor stops if water outlet is lower than 5 in cooling mode. This too low water temperature may make the water freeze up inside plate heat exchanger and cause damage. Check whether temperature sensor Tc is OK and well connected; whether set water temperature too low; whether system flow rate too small.
7. Water outlet Temp. too high Compressor stops if water outlet is higher than 57 in heating or hot water mode. This too high water temperature may make the system has too high condensate pressure inside and cause unit malfunction. Check whether temperature sensor Tc and Tw is OK and well connected; whether set water temperature too high; whether system flow rate too small.
8. Defrosting Failure If unit continuously failed to finish the defrosting operation for three times, it stops and gives failure code S08 This can only be recovered by re-powering the machine. Please check whether the actual water temperature is too low for the unit to defrost, so the plate heat exchanger has the risk of freezing up.
9. Water outlet Temp. too low This is also used to protect the safety of the compressor. Compressor stops and AH (or HBH) starts if water outlet temperature is lower than 15 in heating and hot water mode. Compressor restarts when this temperature is higher than 17.
10. Too small water flow rate failure If unit stops due to “too small water flow rate” protection (S02) over three times in certain period of
time, unit stops and gives S10 failure code. It can only be recovered by re- powering the unit. Check the water system, especially the filter; check the working statue of water pump.
11. Indoor anti-freezing protection failure in cooling If unit stops due to “Indoor anti-freezing protection in cooling (S01)” over three times in certain period of time, unit stops and gives S11 failure code. It can only be recovered by re-powering the unit.
E. ON/OFF Press to turn ON/OFF of heat pump operation. When the unit is powered, home page will be shown on the screen. After repowered, unit will recover its working mode and settings automatically.
76

4. Usage

START ENGING
STOP

34.7

23.9

6.8

F. Touch screen panel

Current water temperature
Current mode Set water
temperature
Outdoor temperature

26
15
34.7

23.9

6.8

Room temperature Water tank temperature

G. Mode Press to switch unit working mode(Heating, Cooling, Hot water, Auto).In Auto mode, unit switch its
working mode between cooling, heating and sanitary hot water automatically according to setting.

START ENGING
STOP

34.7

Heating

Cooling

23.9

Hot Water

Auto

6.8

26
15
34.7

23.9

START ENGING
STOP
6.8

77

4. Usage
H. Setting: Press to enter into setting menu.
2. Heating/Cooling circuit 2 – see page 82
See page 103
1. Heating/Cooling circuit 1
– see page 79
5. Reduced Setpiont for Heating – see page 87

3. DHW settings – see page 83

6. Anti-Legionella Function – see page 88

7. Vacation Mode – see page 89

See page 102
4. DHW Storage – see page 85
8. User Management – see page 90

See page 103
9. Mode Settings – see page 92

10. Backup Heating – see page 94

13. Electrical Utility Lock – see page 98

14. Other options – see page 99

11. Water Pump Settings – see page 96
See page 102 12. Floor curing – see page 97
15. Unit Real-time Data – see page 101

78

4. Usage
4.2 Operation Instruction
1. Heating/Cooling circuit 1
1.Heating & Cooling Settings 1, HC/CC 1 1.01) Heating or Cooling Stops based on Water T 1.02) Heating or Cooling Stops based on Water T
1.01: This is to set a temperature to stop unit. Unit stops operation when [Tset+1.01] in heating operation, or [Tset­1.01] in cooling operation is reached. 1.02: This is to set a temperature to re-start unit. Unit starts operation again when water temp. drops below [Tset-1.02] in heating operation or increases over [ Tset+1.02] in cooling operation. Both the set values are based on T. For example, in heating mode, if Tset=48, while 1.01=2,and 1.02= 1,when actual water temperature is higher than 50( Tset+1.01),unit stops. When unit stops and actual water temperature drops lower than 47[ Tset- 1.02],unit restarts.
79

4. Usage

1.03 T Compressor Speed-Reduction This parameter is used to set a temperature, at which compressor starts to slow down its speed. Also, the set value is based on T. Compressor always works with its maximum allowable speed, if actual water temperature is
lower than [Tset-1.03](in heating mode) or higher than [Tset+1.03]( in cooling mode). When actual temperature is between [Tset-1.03,Tset]in heating mode or [Tset, Tset+1.03] in cooling mode, compressor will adjust its working speed, to balance the total heating output and system heating load.
This setting is to keep a balance between comfort and energy saving. If this value is set too big, even if the room is not warm (or cool) enough, compressor will slow down its speed quite soon to save energy; If this value is set too small, even if the room is warm (or cool) enough, compressor will slow down its speed quite late, which consumes more power.
It’s more like a setting that tells the heat pump unit which temperature range you’d prefer to have the heat pump stayed in.
For example, in heating mode, if Tset=48, and 1.03=2,compressor will work as hard as possible to get 46 as soon as possible. Then compressor will lower its speed. If even the compressor works in its lowest allowable speed, but actual water temperature still goes over [Tset+1.01], unit stops.

Working In Heating

Compressor ON

Tset-1.03

Full Speed

Compressor Speed Down

Temp. Drops Lower Than [Tset-1.03] Stay in [Tset -1.03, Tset +1.01] Temp. Increases Higher Than [Tset+1.01]

Compressor Stop

Temp. Drops Lower Than [Tset-1.02] 1.04) Set Temp for Cooling Set an ideal water temperature for cooling via this parameter.
1.05) Heating Curve Function Set whether heating curve function is needed or not. If heating curve function is not needed, set 1.05=OFF,and then you can set a fixed water set
temperature under heating mode via parameter 1.19″Set Temp For Heating” 1.06~1.15 Set the heating curve 1.06 Ambient Temp. 1 1.07 Ambient Temp. 2 1.08 Ambient Temp. 3 1.09 Ambient Temp. 4 1.10 Ambient Temp. 5 1.11 Water Temp. A/Ambient Temp. 1 1.12 Water Temp. B/Ambient Temp. 2 1.13 Water Temp. C/Ambient Temp. 3 1.14 Water Temp. D/Ambient Temp. 4 1.15 Water Temp. E/Ambient Temp. 5
When 1.05=ON,user can set a heating curve which fits his house, by adjusting the settings of parameter 1.06~1.05

80

4. Usage

Parameter 1.06~1.10 is used to set 5 different ambient temperatures; while parameter 1.11~1.15 is used to set 5 corresponding set water temperatures VS these 5 ambient temperatures. Then the controller will create a heating curve according to these settings, and try to reach the set water temperature automatically according to actual ambient temperature.
Tsh
Tsh1

Tsh2 (Tsha)

Tsh3

Tsh4

Tsh5

T(Ta)

Ta1

Ta2

Ta3

Ta4

Ta5

Tips:

(Ta)

Heating curve function is based on the factor that the lower the ambient, the higher house heating

water temperature needs to be. This heating curve function can help the heat pump unit gain a higher

COP, as well as make the house more comfortable.

As house insulation level and people’s sense of cold may vary from one another, the factory-set curve

may not suit you the best. You can set one curve according to your need.

If you feel too hot, you can lower the settings of water temperatures (parameter 1.11~1.15), which

correspond to the ambient temperature parameters (1.06~1.10) . If you feel too cold, then adjust these

settings a little higher. You can also adjust the ambient temperature settings, if you think the factory

settings are not perfect for your need.

1.16~1.18) Water Temp. Setting Adjustment function

These three parameters work together to gain an ideal water temperature for an ideal room temperature

When this function is ON, unit will adjust the set water temperature (a set value or calculated value

via heating curve), according to the difference between actual room temperature and idea room

temperature.

1.16 Room temp. effect on Heating Curve: Turn ON or OFF this function.

1.17 Idea Room temp. in Heating: Set an ideal room temperature in heating. When in Room

Temperature Control mode, this parameter will also be the Room Set Temperature.

1. 18 Idea Room temp. in Cooling: Set an ideal room temperature in cooling. When in Room

Temperature Control mode, this parameter will also be the Room Set Temperature.

For example

If 1.16 =ON, unit works in heating mode.

If water set temperature in the heating curve is 35.

If actual room temperature is 27,while parameter 1.17( Ideal Room Temp. in Heating Mode)

is set to 22 , then the unit will deduct (27 -22)=5 from water set temperature, which means

unit will take 30 as the set water temperature.

1.19 Set Temp For Heating If heating curve function is OFF, a fixed water temperature fox heating can be set via “Set Temp For Heating”.
1.20 Low Temperature Limit 1. 21 High Temperature Limit These two parameters are used by the installer, to set the set temperature range for circuit 1 for safety purpose. 1.22) Mixing Valve Set whether circuit 1 has a mixing valve connected or not. For more details, please refers to chapter 2.1.4.

81

4. Usage
2.Heating / Cooling circuit 2
2.01 Heating&cooling Circuit 2 Set whether the system has the second circuit .
2.02 Set Temp For Cooling Set the set temperature for cooling operation of circuit 2. 2.03 Set Temp For Heating
If heating curve function is disabled for circuit 2, a fixed value of set water temperature in heating mode can be set here. 2.04 With/Without Mixing Valve 2
Set whether circuit2 has a mixing valve connected. For more details, please refers to chapter 2.1.5 2.05 Heating Curve Turns ON/OFF of heating curve function for circuit 2. 2.06 Water Temp. A/Ambient Temp. 1 2.07 Water Temp. B/Ambient Temp. 2 2.08 Water Temp. C/Ambient Temp. 3 2.09 Water Temp. D/Ambient Temp. 4 2.10 Water Temp. E/Ambient Temp. 5 Temperature set here is water temperature, it is based on the same ambient temperature settings for circuit 1, parameters 1.06~1.10. Temperature settings of the heating operation for circuit 2 VS ambient temperatures. Controller will create a heating curve for secondary heating system according to these settings. If parameter 2.05 is OFF, only 2.03 needs setting, and unit will take this set value as fixed set water temperature for secondary heating system. 2.11 High Temperature Limit 2.12 Low Temperature Limit
These two parameters are used by the installer, to set the set temperature range for circuit 2 for safety purpose.
82

4. Usage
3. DHW Settings
3.01 Setpoint DHW Set temperature for sanitary hot water. 3.02 DHW Restart T Setting Heat pump unit will start working for sanitary hot water again, after temperature drops below Tset-3.02 here. 3.03 Shifting Priority Turn ON/OFF this function. Air to water heat pump is an equipment that absorbs heat from surrounding air, and transfers it to water. The lower the ambient temperature is, the less heat the unit absorbs. This makes the unit heating capacity and efficiency drop when ambient temperature drops. The unit takes longer time to heat up the sanitary hot water. However, the lower the ambient temperature is, the more heat the house demands. If the unit does not provide enough heat while it is working for hot water, the temperature inside the house may drop too much, and people in it feel uncomfortable. So parameters 3.03~3.08 try to divide the working time for sanitary hot water into several cycles, after ambient temperature drops below a set value. When this function is ON, AH (Auxiliary Heater) or HWTBH (Hot Water Tank Back-up Heater) or both, depending on their priority, will work individually or together to enhance heat pump’s capacity in sanitary hot water mode to heat up the water as soon as possible. 3.04 Shifting Priority Starting Temp. Set an ambient temperature below which this function starts to work. When shifting priority function is activated, heat pump will try to find a balance between DHW and Heating operation after ambient temperature drops below this temperature. 3.05 Sanitary Water Min. Working Hours Set the minimum working period for sanitary hot water mode. 3.06 Heating Max. Working Hours Set the maximum working period for heating mode, after unit enters into heating mode. 3.07 Allowable Temp Drift in Heating Set allowable temperature drift in heating mode. 3.08 DHW Backup Heater for Shifting Priority Working mode of HWTBH (Hot Water Tank Back-up Heater) in this function. If this parameter is set ON, when heat pump is switching to house heating, HWTBH will keep on working to help the uni heat up hot water as soon as possible.
83

4. Usage

If shifting priority function is ON, and ambient temperature is lower than [3.04],unit works as shown below: House heating water under water temp.

The running time for DHW is cleared. Unit Starts heating

YES

and counting the running time.

Unit keep on working in DHW

NO

and counting the running time.

NO

The ambient temp. Is below (3.04)

Whether the YES unit works in DHW
NO

Whether unit works YES in DHW over (3.05)

Whether house heating water temperature drops over (3.07)

Unit works in heating YES

Whether unit works in YES Heating over (3.06)
NO

The running time for Heating is cleared. Unit starts DHW and counting the running time.

Unit keep on working in Heating and counting the running time.

84

4. Usage
4.DHW Storage
Sanitary Hot Water Storage Function After showers, house usually needs only medium temperature sanitary hot water in day time. This function is used to store high temperature sanitary hot water in low demand time (mid-night, or day time of working days), and reheat the water to medium temperature out of this time period. 4.01 Sanitary Hot Water Storage Function Turn ON/OFF this function. 4.02 Sanitary Hot Water Storage Timer Set a working time period for this function, and the unit starts to work towards sanitary hot water set temperature in parameter 3.01 within the set time range. Different time periods for every day in a week can be set.
4.03 Reheating Function Turn ON/OFF reheat function. 4.04 Reheating Function Timer Set a working time period for reheat function, and within this time period, unit will work with a lower set value for DHW (value set in parameter 4.05). Different time periods for every day in a week can be set.
85

4. Usage
4.05 Reheating Set Temp. Set a lower set value for DHW operation. Unit will work with this set value when reheating function
is activated in the set time period (time period set in parameter 4.04). 4.06Reheating Restart T Setting
Set “reheat restart”water T. When water temperature drops below T based on reheat set temperature within the set reheating time period, unit restarts.
86

4. Usage
5. Reduced Setpoint for Heating
Reduced Setpoint Function: Sometimes the house heating demand maybe lower than normal, like during sleep period or working time. In this way, a reduced value based on standard set value can be set here for better efficiency of the whole system. Quiet Operation: Also, for a better noise issue, a Quiet Operation can be also set in this menu. After activating this function and setting the time period for quiet operation, unit will try to reduce its noise level. Note: Unit efficiency in quiet operation mode will be lower than standard working mode. 5.01 Reduced Setpoint
Turn ON/ OFF Reduced Setpoint function. 5.02 Temp. Drop/Rise
Set temperature drop (in heating) or increase (in cooling) based on standard set temperature during Reduced Setpoint operation. 5.03 Timer for Reduced Setpoint Function
Set a working time period for Reduced Setpoint function. Different time periods for every day in a week can be set. 5.04 Quiet Operation Turn ON/ OFF Quiet Operation function. 5.05 Allowable Temp. Drifting Set allowable temperature drift during Quiet Operation. When the unit works in quiet mode, its output may drop because both fan and compressor may need to work in lower speed. However, temperature in the system may drop (in heating) or increase (in cooling) too much due to the lower output. So when actual temperature drift from the standard set value is more than the T set value set here, unit will end this quiet operation, to ernsure comfortable house temperature. 5.06 Timer for Quiet Operation Set a working time period for Reduced Setpoint function Different time periods for every day in a week can be set.
87

4. Usage
6. Anti-Legionella Function
If user uses sanitary hot water directly out from the HWT (hot water tank), for the health purpose, it’ s requested that he needs to heat up the water inside the tank over 60 for anti- legionella purpose once a week. Note:Please always refers to local regulation for a correct usage of this function. 6.01 Anti-Legionella Program
Turn ON/ OFF Anti-Legionella function. 6.02 Day and Time
Set at which time in which weekday(s) for the start of anti-legionella operation. 6.03 Setpoint
Set the target sanitary hot water temperature for anti-legionella. Please refers to the local regulation for the correct setting of this temperature. 6.04 Duration
Set for how long the unit should try to keep this set high temperature, to ensure all bacteria in the shower water tank can be killed. 6.05 Finish Time
Set an ending time for this anti-legionella function, even it is not finished successfully. This time should be longer than what it is set in parameter 6.04 .
88

4. Usage
7. Vacation Mode
If you need to be away from house for some days, you can use this Vacation Mode function to reduce the set temperatures for both sanitary hot water and house heating , to save more energy. 7.01) Vacation Mode
Turn ON/OFF Vacation Mode. 7.02) Sanitary Hot Water Temp. Drop During Vacation Mode
Set a temperature drop for sanitary hot water based on standard DHW set value during the set time period for vacation mode. 7.03)Heating Water Temp. Drop During Vacation Mode
Set a temperature drop for heating based on standard DHW set value during the set time period for vacation mode. 7.04) Vacation Start Date
Set the date that vacation starts. 7.05) Vacation Finish Date
Set the date that vacation finishes.
89

4. Usage
8. User Management
8.01) Permission Level For the safety of the product,some parameters can only be adjusted under installer’s
permission level. The permission level can be changed in this menu. A password is needed for activating the installer’s permission level. 8.02) Heating/Cooling ON/OFF Timer
To turn ON/OFF the timer function for heating/cooling operation. 8.03) Heating/Cooling ON/OFF Timer
Set the ON and OFF timer for the heating/cooling operation.Different time periods for every weekdays in a week can be set.
90

4. Usage
8.04) Language Set system language.
8.05) Set Date and Time Set system clock date and time.
8.06) Distribution System Setting The unit is default set to have 3-way motorized valve inside the unit, which has different
flow directions for sanitary hot water/cooling+heating mode. If user needs to have sanitary hot water and heating on the same distribution system, he can
set this parameter to”Hot Water+Heating/Cooling”. Note: If it is set to “Sanitary Hot Water+Heating/Cooling”, temperature sensor for sanitary hot water (Tw) will be used for the control of heating operation also. Please place it either inside an ideal position in Hot Water Tank. 8.07) Save Current Settings
This parameter is used by installer to save the current settings as “Installer Settings”, so the customer can load the saved settings into the system, when needed. 8.08) Load Saved Settings
Loaded the saved “Installer Settings”. 8.09) Reset to Factory Settings
Reset the whole system back to factory default settings. Note: Saved”Installer Settings” will be cleared. Note: Most of above menus and parameters are designed for installer only. They should only be adjusted by installer or professional customer under the instruction of installer, otherwise malfunction of the unit may happen.
91

4. Usage
9. Mode Settings
9.01) Sanitary Hot Water Set whether the system has sanitary hot water circuit or not. When unit works in Sanitary Water mode,
3-way motorized valve will guide water to HWT automatically. 9.02) Heating
Set whether the system has water circuit for house heating purpose or not. When unit works in heating mode, 3-way motorized valve will guide water to heating circuit automatically. 9.03) Cooling
Set whether the system has water circuit for house cooling purpose or not. When unit works in cooling mode,3-way motorized valve will guide water to cooling circuit automatically. NoteAs whether the system can work in hot water, heating or cooling mode depend quite much on the distribution system, these setting can only be done under installer level, to ensure the safety of the distribution system. 9.04) Basic Operation Mode This parameter is used to set the basic operation modes, as”Water Temperature Control”or “Room Temperature Control”. When “Basic Operation Mode” is activated, unit takes room temperature as control object. When “Basic Operation Mode” is not activated, unit takes water temperature as control object. Heating or cooling function take water as the control object as default. However when a room temperature sensor is connected to the unit and a more precise control of room temperature where the sensor is placed is preferred, “Room Temperature Control”mode can be selected. Note: When”Room Temperature Control”mode is selected, system will not operate under the heating curve function and actual water temperature may swing significantly.
92

4. Usage
9.05) Max Allowed Duration For Min Compressor Speed When unit output is higher than demand,compressor speed will be reduced.If compressor has
continuously worked in minimum compressor speed for over time set via”Max Allowed Duration For Min Compressor Speed”,unit stops. 9.06) Cooling and Heating Switch
This function is for having the unit start cooling or heating operation automatically, according to: If setting =”Ambient Temp”, system will automatically choose cooling or heating operation based on the outdoor ambient temperature, compared with parameter set in 9.07 and 9.08. If setting =”External Signal Control”, an external room thermostat or central control system in the building can control the cooling or heating requirements by connecting it to the respective signal ports. The signals are simple 1-0 (on- off) signal. If cooling port receives the signal, the system switches to cooling; If heating port receives the signal, the system switches to heating. When neither port receives the signal, the system stays in standby mode. If setting =”Ambient Temp.+External Signal Control”,unit will take both the ambient temperature and external signal into consideration for cooling or heating mode selection. Note: If parameter is set to OFF, auto switch function is not activated. Then make sure that parameter (Heating Water Circuit) and (Cooling Water Circuit) are not set to ON simultaneously, as the system can not determine actual requirement, due to mode conflict. To avoid mode conflict, if”External Signal Control”is used to take control, please ensure that the external signal will not be activated at the cooling and heating ports at the same time. 9.07) Ambient Temp. To Start Heating This parameter is used to set the ambient temperature to start the heating operation. For example, if default value is 18, the system will start heating operation automatically when ambient temperature is lower than 18. The setting is only available when parameter “Cooling and Heating Switch”=” Ambient Temp. ” Or “Ambient Temp.+External Signal Control”. 9.08) Ambient Temp. To Start Cooling This parameter is used to set the ambient temperature to start the cooling operation. For example, if set value is 28, the system will start heating operation automatically when ambient temperature is higher than 28. The setting is only available when parameter “Cooling and Heating Switch “=”Ambient Temp. Or “Ambient Temp.+External Signal Control”. Note: In order to avoid short cycling between different modes, unit will also take the average temperature in the past time for reference of choosing the working mode.
93

4. Usage
10. Backup Heating
AH—Auxiliary Heater inside the indoor unit HBH—Heating Back-up Heater HWTBH—Hot Water Tank Back-up Heater 10.01) Backup Heating Sources For Heating Set whether the system has HBH (Heating Back-up Heater). 10.02) Priority for Backup Heating Sources (HBH) Set the priority of HBH compared with unit AH (Auxiliary Electric Heater inside the indoor unit). When unit works in heating, if heat pump unit can’t provide enough power, it will turn on AH or HBH (which set to have the higher priority) automatically. If after AH or HBH is working, that the total output power is still not big enough, unit will turn on the lower priority Backup Heating Source also. 10.03) Backup Heating Source for Sanitary Hot Water Set whether the system has HWTBH (Hot Water Tank Back-up Heater). 10.04) Priority for Backup Heating Sources (HWTBH) Set the priority of HWTBH compared with unit AH (Auxiliary Electric Heater inside the indoor unit).
When unit works in hot water, if heat pump unit can’t provide enough power, it will turn on AH or HWTBH (which set to have the higher priority) automatically. If after AH or HWTBH is working, that the total output power is still not big enough, unit will turn on the lower priority Backup Heating Source also. 10.05) External Heating Source Start Accumulating Value Accumulated Value between operation time VS set temp. to start other heating source for heating operation.
94

4. Usage
This is for adjusting how fast Backup Heating Sources for heating operation will be turned ON if heat pump unit can’t provide enough power. The bigger the value is set, longer time it takes to start the Backup Heating Sources if heat pump capacity is not enough. 10.06) Water Temperature Rise Reading Interval
Time interval for checking the temperature increase when unit works in DHW mode. If temperature increases too slow during this set interval time, unit will activate other heating source for DHW operation.
The smaller the value is set, unit is more likely to activate AH or HWTBH for a fast heating of DHW.
Backup Heating for DHW If system has no HWTBH (set via parameter 10.03), or HWTBH has lower priority than AH (set via parameter 10.04 ): If heat pump capacity is not enough to heat up DHW fast enough, unit starts AH. If after AH starts, it still cannot heat up DHW fast enough, HWTBH starts. When the set and actual water temperature is higher than heat pump maximum allowable water temperature, heat pump stops and unit starts AH. If after AH starts, hot water temperature still increases too slow, HWTBH starts. If system has HWTBH (set via parameter 10.03), and HWTBH has higher priority than AH (set via parameter 10.04):
If system has HWTBH (set via parameter 10.03), and HWTBH has higher priority than AH (set via parameter 10.04):
When the set and actual water temperature is higher than heat pump maximum allowable water temperature, HWTBH works ALONE for DHW while heat pump unit will work in heating or cooling mode according to demand.
When actual water temperature is lower than heat pump maximum allowable water temperature, heat pump works in hot water mode. If heat pump capacity is not enough to heat up DHW fast enough, unit starts HWTBH. If after HWTBH starts, hot water temperature still increases too slow, AH starts.
Under shifting priority operation, according to parameter 3.08 ,AH or AH+HWTBH work together with heat pump to heat sanitary hot water to the set value as soon as possible, so heat pump unit can concentrate on heating mode afterwards. 10.07) Emergency Operation
When heat pump failed to work, whether the unit should turn ON the back-up heating system automatically.
Note: If this function is activated, customer should check the working status of heat pump unit occasionally, to ensure heat pump unit is functioning well.
95

4. Usage
11.Water Pump Settings
11.1) Circulation Pump P0 Type This is to set the type of circulation pump inside the unit, P0.
11.2) Speed Setting of Circulation Pump P0 This is to set the working speed of circulation pump inside the unit, P0.
11.3) Working Mode of Circulation Pump P0 This is to set the working mode of circulation pump for cooling/heating operation inside
the unit, P0. P0 can work as the following settings:
1. Interval working mode. In this setting, P0 stops after compressor stops, but runs for a while after stops for an interval period.
2. ON constantly. P0 will work constantly even if compressor stops after reaching the set temperature.
3. OFF with compressor. It means P0 stops after compressor stops. 11.4) Pump OFF Interval 11.5) Pump On Time
If unit circulation pump P0 working mode is set to “Interval working mode”, that means circulation pump stops after compressor stops, but after it stops, it will runs for [11.5] minutes after stops for every [11.4] minutes interval time. 11.6 Buffer Tank 11.7 P1 for Heating Operation 11.8 P1 for Cooling Operation 11.9 P1 with High Temp. Demand 11.10 P2 for Heating Operation 11.11 P2 for Cooling Operation 11.12 P2 with High Temp. Demand These parameters are used for setting the working of external circulation pump P1 and P2, for heating/cooling circuit, (HC/CC 1) and heating/cooling circuit, (HC/CC 2).
For more details, please refers to chapter 2.1.3~2.1.5.
96

4. Usage
12. Floor Curing
After initial Installation or Long Time Non-operation, a floor heating system may be very wet in the concrete. Most of the heating capacity from heat pump unit is consumed to dry up the water in the concrete for its evaporation. This floor curing function is used to dry the floor to ensure the safety of heat pump system. 12.1) Floor Curing
Turn ON/OFF this function. For a newly-built floor heating system, floor must be cured before setting the heat pump into standard working mode. 12.2) Floor Curing Temperature Setting Stage 1 12.3) Floor Curing Operation Duration Stage 1
Set temperature and lasting time for first-stage of Floor Curing operation. 12.4) Floor Curing Temperature Setting Stage 2 12.5) Floor Curing Operation Duration Stage 2
Set temperature and lasting time for second-stage of Floor Curing operation. 12.6) Floor Curing Running Hours 12.7) Highest Water Temp. in Floor Curing Operation
Three two values are operation data during floor curing operation. Unit will take down the operation time and highest water temperature the system has reached during Floor Curing operation.
Note: After Floor Curing operation is finished, if water temperature inside the distribution system is still far below the set value of [12.4], it means there has still some water inside the concrete of floor heating system, thus Floor Curing function should be turned ON again, until temperature can increase over [12.4].
97

4. Usage
13.Electrical Utility Lock
Some electricity companies offer a special rate to the houses who lowered their power consumption during peak time. When peak time comes, electricity company will send an ON or OFF signal to every house, indicating that they hope the house owners to turn OFF some electric equipments. This system can be connected to the unit if the unit is supposed to stop working during this period, and use the following parameter settings to activate this function. 13.1) Electrical Utility Lock
Set ON/OFF Electrical Utility Lock function. 13.2) Operation Signal for Electrical Utility Lock
Set the type of signal from electricity company.”Normally Open”means when unit can work as normal when it gets ON signal; the unit should stop working when it receives a OFF signal; “Normally Close”means the opposite. 13.3) HBH During Electrical Utility Lock
Set whether turn on HBH (Heating Back-up Heater), when unit is blocked by Electrical Utility Lock. e.g. gas boiler. 13.4) Working Mode of Pump During Electrical Utility Lock
Set the working of circulation pump when unit is blocked by Electrical Utility Lock. If it’s activated, the circulation pump will keep on working when compressor stops. If it’s not activated, the circulation pump will stop working when compressor stops.
98

4. Usage
14. Other Options
14.1) Motorized Diverting Valve Switching Time Set how many minutes as switching time of the motorized diverting valve spending on switching
the water flow fully between DHW and Heating/Cooling circuit. Note: This parameter must comply with the motorized diverting valve. Otherwise unit may
not be able to work due to not enough water flow rate. 14.2) Power On Time for Motorized Diverting Valve
Set how long the motorized diverting valve should be powered, for switching the water flow fully between DHW and Heating/Cooling circuit. 14.3) Refrigerant Recycle
This function can be used by installers to recycle the refrigerant in the complete system into condensing unit for service purpose. When it is activated, unit will be forced to work in cooling operation for some time, to push all refrigerant back to condensing unit. 14.4) Control Panel Backlight
Set the backlight touch screen operation panel to be”Always on”or how long before it becomes off for energy saving. 14.5) Exit System
Exit from unit program and returns to WINCE operation system. This is used for software updating.
99

4. Usage
14.6) Ambient Temp. to activate first class anti-freezing 14.7) Ambient Temp. to activate second class anti-freezing 14.8) Ambient Temp. to stop second class anti-freezing 14.9) Water Temp. to activate second class anti-freezing 14.10) Water Temp. to stop second class anti-freezing
These parameters are used for setting the anti-freezing protection of the unit in winter time, when unit is powered but turned OFF.
When ambient temperature is lower than fist class anti-freezing starting ambient temperature, unit will circulate the water in the system at interval for anti-freezing.
When ambient temperature drops below second class anti-freezing starting ambient Temperature, heat pump unit will start either compressor or backup heating sources to maintain the water temperature within the range “Water Temp. to activate second class anti-freezing” and “Water Temp. To stop second class anti-freezing”.
Note: This function is provided to the customer FREE OF CHARGE for helping their house heating and DHW water system free from freezing up. Customer should always have his own protection system for preventing the water system from freezing up. We have no responsibility or obligation if any damage has caused by water freezing. 14.11) Mode Switch during Defrosting
If water temperature is too low, the condenser may have the risk of freezing up and cause damage the complete refrigerant system. Thus, if water temperature in current working mode is too low for defrosting, unit will check the water temperature in other circuit. If the water temperature in other circuit is good enough for defrosting, it will switch the water flow to this circuit for defrosting operation automatically.
If there is no other circuit, or the water temp in other circuit is also not high enough for defrosting, unit will stop defrosting and automatically lift up the set water temperature, preparing for the next defrosting cycle.
If defrosting failed for over three times continuously, unit stops and can only be recovered by re-powering the machine. Please check the water system at this moment to ensure everything works properly before re-powering the unit.
Note: This function can only work with outdoor software higher than AC13I20.WP.V004_T01 or AC13I17.WP.V009_T01, otherwise this function will interrupt the working of the machine during defrosting all the time. 14.12) Fan Speed Limit This function is for reducing the fan speed in order to reduce the noise, however it would reduce the performance of the heat pump at the same time. The fan speed limitation can be set at down to two levels 95% and 90%. This function is not recommended unless the noise is strongly complained by customer/neighbor.
100

4. Usage
15. Unit Real-time Data
This menu is designed for viewing the running data of the system. Following parameters that are related to the working of the system can be viewed in this menu: 01): Control System Version No 02): Database Version 03): Heat Exchanger Water Outlet Temperature-Indoor – Tuo 04): Heat Exchanger Water Return Temperature-Indoor – Tui 05): Indoor Coil Temp. – Tup 06): Sanitary Hot Water Temp.- TW 07): Cooling/ Heating Water Temp.-TC 08): Water Flow Rate 09): Compressor Working Speed 10): EEV Openings 11): Actual Ambient Temp. 12): Average Ambient Temp. in 1 Hour 13) Average Ambient Temp. in 24 Hour 14) High Pressure – Pd 15): Low Pressure – Ps 16): Discharge Temp. – Td 17): Suction Temp. – Ts 18): Outdoor Coil Temp. – Tp 19): Source Side Water Inlet temperature (For Water to Water unit only) 20): Source Side Water Outlet temperature (For Water to Water unit only) 21): Fan Speed 22): Fan Speed 2 23): Outdoor Unit Working Current 24): Voltage 25): Eeprom Version No.
101

4. Usage
Info Press “Info” to view water system and water system working status.

Display of Failure Code

Display of Failure

Record of Previous Failure

TW—-Water temperature for Sanitary hot water tank TC—–Water temperature for buffer tank TR—–Room temperature TA—–Ambient temperature
102

4. Usage
Home Home: Press this button at any page, operation panel goes back to home page.

26
15
34.7

23.9

START ENGING
STOP
6.8

103

4. Usage
4.3 Electric heater
The inbuilt electric heater can be used as a back-up heater or auxiliary heater to our heat pump unit, when ambient temperature is too low, or heat pump fails to work properly, which causes insufficient heat. This heater will start to work when any of following two conditions is met: 1. Water temperature is lower than what is set via digital thermostat for electric heater. 2. Heat pump unit thinks its capacity is not enough, so it turns ON the heater.

Notice! There is a separate power cable for electric heater on top of

3kW or 6kW electric heater

indoor unit. It supplies the power to electric heater directly.

Make sure the unit is full of water before turning it on.

Do not touch it to get burned when it is turned on. High

temperature here.

Make sure the power supply to the heater corresponds to the

specifications.

The installation, dismantlement and maintenance of the heater

must be performed by qualified personnel. It is forbidden to

do any changes to the structure of the heater.

Digital thermostat is default set to 30.

Maximum set temperature of digital thermostat is 120. But

it is strongly suggest not to set the temperature over 75,

otherwise it may make the unit build up too high pressure inside

and cause damage or danger.

Operation of digital thermostat

This heater (AH) is controlled by heat pump unit automatically according to the parameter setting in menu “Backup Heating”.
In case the heat pump control system breaks down, customer can manual set a set temperature for water circulates through the unit via the digital thermostat for Electric Heater (AH).
Important Notice: Before turn ON the thermostat, system must be full filled with water and correctly air purged, otherwise electric may get over heat and cause fire.

104

4. Usage
Operation of digital thermostat

  1. Press for 3 seconds to turn ON OFF of the electric heater. When heater is turned OFF, it shows “- – -“.

  2. When heater is turned ON, press for 3 seconds to show the set temperature. After release, this set temperature blinks on the display.

  3. When set temperature is blinking, press or to increase or decrease the set temperature of electric heater.

  4. Controller will save this setting and show actual water temperature in the display if no operation in 6 seconds.
    4.4 Failure codes

Outdoor

Type Code Description

Blinking times

P01

Main line current protection

1

P02

Compressor phase current protection

2

Protection

P03

IPM module protection

3

P04

Compressor oil return protection

4

Compressor shut

down due to high/

P05

low pressure switch open caused by

5

abnormal high/low

pressure

Unit working statue
Compressor stops
Compressor stops Compressor stops Compressor speed up
Compressor stops

Solution
Input current too high or too low, or system works in over-load condition. Unit recovers automatically after 5 minutes when it happened the first time. If same failure happened 3 times in a certain period of time, unit stops until repowered. Check unit input current. Check whether fan motor and water pump is working OK; whether condenser is blocked; whether water temperature too high, and whether water inlet&outlet temperature has too big difference (should no bigger than 8)
Compressor input current too high or too low, or system works in over-load condition. Check compressor input current. Check whether fan motor and water pump is working OK; whether condenser is blocked; whether water temperature too high, and whether water inlet&outlet temperature has too big difference (should no bigger than 8)
Compressor drive failure. Check whether cable is broken or loosen. Check whether compressor driver PCB or compressor is broken.
If unit has been continuously working in low speed for certain period of time, unit starts this protection to suck compressor oil back into compressor. This is a normal protection and doesn’t need any treatment.
If system pressure is too high or too low, it activates this protection. Unit recovers automatically after 5 minutes when it happened the first time. If same failure happened 3 times in a certain period of time, unit stops until repowered. Check whether fan motor and water pump is working OK; whether condenser is blocked; whether water temperature too high, and whether water inlet&outlet temperature has too big difference (should no bigger than 8)

105

4. Usage

Type Code Description

Blinking Unit working

times

statue

Solution

Compressor speed

down due to

P06

abnormal high pressure detected

by condensing

pressure sensor

If system pressure is too high , it activates this protection. Unit

recovers automatically after 5 minutes when it happened the first

time. If same failure happened 3 times in a certain period of time,

6

Compressor stops unit stops until repowered. Check whether fan motor and water pump

is working OK; whether condenser is blocked; whether water

temperature too high, and whether water inlet&outlet temperature

has too big difference (should no bigger than 8)

P07

Compressor preheating

7

Standard function, doesn’t need any treatment.

This is a normal protection and doesn’t need any treatment. When compressor did not work for long time and ambient temperature is low, compressor crankcase heater work for certain period of time before compressor start to warm up the compressor.

Compressor P08 discharge temp. too 8
high protection

Check whether water temperature set value is too high, especially Compressor stops when ambient temperature is low; whether water flow rate too small;
whether system is lacking of enough refrigerant.

Outdoor evaporator

P09 coil temp. sensor

9

protection

Compressor stops Check whether air circulates fluently in outdoor unit.

Protection

P10

AC over high/low voltage protection

10

Compressor stops

Unit input voltage too high or too low. Check the voltage of unit power supply.

Compressor shut

P11

down due to too high/low ambient

temperature

11 Compressor stops Ambient temperature is too high or too low for unit to work.

Compressor speed

P12

limit due to too high/low ambient

temperature

0

Compressor speed down

This is a normal protection and doesn’t need any treatment.

Compressor speed

down due to

P14

abnormal low pressure detected

by condensing

pressure sensor

If system pressure is too low , it activates this protection. Unit

recovers automatically after 5 minutes when it happened the first

time. If same failure happened 3 times in a certain period of time,

unit stops until repowered. Check whether system has not enough

14

Compressor stops

refrigerant or leakage inside(more likely it is not enough refrigerant that caused this abnormal evaporating pressure); whether fan motor

and water pump is working OK; whether condenser is blocked;

whether EEV whether EEV works normally; whether water

temperature too low, and whether water inlet&outlet temperature has

too big difference in cooling(should no bigger than 8).

F01

Outdoor ambient temp. sensor failure

17

Compressor stops

Check whether ambient temperature sensor is open, short-circuit or value drifts too much. Replace it if necessary.

Outdoor evaporator

F02 coil temp. sensor

18

failure

Compressor stops

Check whether outdoor coil temperature sensor is open, short-circuit or value drifts too much. Replace it if necessary.

Compressor F03 discharge temp.
sensor failure

19

Compressor stops

Check whether compressor discharge temperature sensor is open, short-circuit or value drifts too much. Replace it if necessary.

F04

Outdoor Suction temp. sensor failure

20

Compressor stops

Check whether outdoor suction temperature sensor is open, short-circuit or value drifts too much. Replace it if necessary.

Failure

Evaporating F05 pressure sensor

failure

21

Compressor stops

Check whether evaporating temperature sensor is open, short-circuit or broken. Replace it if necessary.

Condensing F06 pressure sensor
failure

22

Compressor stops

Check whether condensing temperature sensor is open, short-circuit or broken. Replace it if necessary.

F07

High/low pressure switch failure

If pressure switch is in open position when unit is in standby statue, 23 Compressor stops or 2 minutes after compressor stops, unit gives this failure. Check
whether high or low pressure switch is broken or not well connected.

F09

DC fan failure (one)

25

Compressor speed down

Speed of DC fan or one of the DC fan (for dual fan system) can’t reach the required value or no feedback signal. Please check whether the PCB or fan motor is broken.

106

4. Usage

Type Failure

Code Description

F10

DC fan failure (two)

Blinking Unit working

times

statue

26 Compressor stops

F11

System evaporating pressure too low

27

Compressor stops

Solution
Speed of both DC fans (for dual fan system) can’t reach the required value or no feedback signal. Please check whether the PCB or fan motor is broken.
If system too low pressure protection detected by evaporating pressure sensor happened 3 times in a certain period of time, it gives this failure code and unit can’t be restarted until repowered. Check whether system has not enough refrigerant or leakage inside(more likely it is not enough refrigerant that caused this abnormal evaporating pressure); whether fan motor and water pump is working OK; whether condenser is blocked; whether EEV whether EEV works normally; whether water temperature too low, and whether water inlet&outlet temperature has too big difference in cooling (should no bigger than 8).

If system too high pressure protection detected by condensing

pressure sensor happened 3 times in a certain period of time, it gives

this failure code and unit can’t be restarted until repowered. Check

F12

System condensing pressure too high

28

whether water flow rate is not enough (more likely it is not enough Compressor stops water flow rate that caused system build up too high pressure);
whether fan motor and water pump is working OK; whether

condenser is blocked; whether EEV works normally; whether water

temperature too high, and whether water inlet&outlet temperature has

too big difference (should no bigger than 8)

Communication

Communication failure between operation panel and the indoor or

between operation

outdoor PCB. Check the cable connection in between. Check whether

E01 panel and indoor

33 Compressor stops the last three switches on outdoor power PCB are set to 001; Whether

PCB or outdoor

four switches on indoor PCB are set to 1000. Unit recovers when

PCB failure

communication recovers.

Communication

between outdoor E02 main control PCB

34

Check the communication cable between outdoor power PCB and Compressor stops deiver PCB. Check whether outdoor power PCB and deiver PCB is

and module PCB

broken.

Compressor phase

E03 current failure

35

(open/short circuit)

Compressor phase

System E04 current overload

36

failure

(over current)

E05

Compressor driver failure

37

Module VDC over

E06 high/low voltage

38

failure

E07 AC current failure 39

E08 EEPROM failure

40

Compressor stops

Check whether the power cable to compressor is broken or shortcircuit.

Compressor stops

Check whether the power cable to compressor is broken or shortcircuit.

Compressor stops

Check whether compressor drive PCB is broken, or cable to compressor is wrong connected.

Compressor stops Input voltage too high or too low.

Check the current to outdoor unit, and compare it with the unit

current shown on the operation panel. If the difference is not big,

Compressor stops

check whether the system has enough refrigerant (more likely it is not enough refrigerant that caused this abnormal low current). If the

difference is big, outdoor power PCB is broken. Please replace it with

a new one.

Cut the unit power and short-circuit JP404 port on outdoor power

Compressor stops PCB, repower the unit, cut power again and cancel the short- circuit

on JP404 port. If still not OK, replace the outdoor power PCB.

107

4. Usage

Indoor

Type Failure

Code Description

Blinking Unit working

times

statue

F13

Room temp. sensor failure

7

Unit stops

F14

Sanitary hot water temp. sensor failure

3

Unit stops

Cooling/heating

F15 water temp. sensor

6

failure

F16

Unit water outlet temp. sensor failure

4

Unit stops Unit stops

F17

Unit water inlet temp. sensor failure

5

Unit stops

F18

Indoor coil temp. sensor failure

8

Unit stops

Mixture valve 1 F21 temperature sensor
failure

11

Unit keep on working, mixture valve 1 output fixed to 0.

Mixture valve 2 F22 temperature sensor
failure

12

Unit keep on working, mixture valve 2 output fixed to 0.

Communication

between operation

F25 panel and indoor

1 Unit stops

PCB or outdoor

PCB failure

F27

Indoor EEPROM failure

13

Unit keep on working

Water pump PWM F28 signal feedback
failure

14

Unit keep on working

Solution
Check whether room temperature sensor is open, short-circuit or value drifts too much. Replace it if necessary. Check whether sanitary hot water temperature sensor is open, shortcircuit or value drifts too much. Replace it if necessary.
Check whether cooling/heating water temperature sensor is open, short-circuit or value drifts too much. Replace it if necessary.
Check whether unit water outlet temperature sensor is open, shortcircuit or value drifts too much. Replace it if necessary. Check whether unit water inlet temperature sensor is open, shortcircuit or value drifts too much. Replace it if necessary. Check whether indoor temperature sensor is open, short-circuit or value drifts too much. Replace it if necessary.
Check whether TV1 temperature sensor is open, short-circuit or value drifts too much. Replace it if necessary.
Check whether TV2 temperature sensor is open, short-circuit or value drifts too much. Replace it if necessary.
Communication failure between operation panel and the indoor or outdoor PCB. Check the cable connection in between. Check whether the last three switches on outdoor power PCB are set to 001; Whether four switches on indoor PCB are set to 1000. Unit recovers when communication recovers. Cut the unit power, connect CN213-5 and CN213-6 together, repower the unit and then cut the power and cancel the connect. If still not OK, replace the indoor PCB.
Check water pump cable connection; check power supply to water pump; check whether water pump is broken.

F29

Mixture valve 1 failure

17

F30

Mixture valve 2 failure

18

Indoor anti-freezing S01 protection in
cooling

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

HEIKO User Manuals

Related Manuals