HEIKO PB-950HE4 Split Cassette Air Conditioners Owner’s Manual
- June 9, 2024
- HEIKO
Table of Contents
HEIKO PB-950HE4 Split Cassette Air Conditioners
SPLIT Cassette air conditioners with peripheral airflow
- Heiko cassette air conditioners are a great solution for installation at homes, offices or restaurants.
- The product range includes appliances with different capacity to suit the size of building area. Cassette air conditioners are available with a panel for peripheral airflow.
- Heiko appliances are discrete, installer-friendly and perfectly match any interior design.
TEMPERATURE SETPOINT from 16 to 30°C
-
Peripheral airflow
With the 360-degree cover, the air is supplied from four sides and corners to ensure efficient airflow in the room. -
High energy efficiency
Innovative solutions enabled a significant reduction of energy consumption in both cooling and heating mode. The appliances have A++/A energy rating. -
SMART airflow
An innovative solution for airflow control. The stream is directed upwards during the cooling and downwards during the heating, which enables an even distribution of air, thus preventing direct airflow on the user. -
Airflow speed control
The option to control airflow shutters vertically enables precise direction of the airflow. The function is available from the controller -
Quiet operation
The components comprising the air conditioner and the optimum airflow system ensure quiet operation for comfort during work and leisure.
WHAT IN BOX
SPECIFICATION
Rated value| Capacity – Cooling| Btu/h (rated)| 22200|
31400
---|---|---|---|---
| | kW rated (min ~ max)| 7.1 (2 ~ 7.3)| 9.2 (2.5 ~ 10.0)
| – Heating| Btu/h (rated)| 24300| 34800
| | kW rated (min. – max)| 8.0 (2.5 ~ 8)| 10.2 (3.0 ~ 10.5)
| Power input – Cooling| kW rated (min. – max)| 2.20 (0.5
~ 2.6)| 3.12 (0.5 ~ 4.0)
| – Heating| kW rated (min. – max)| 1.91 (0.5 ~ 2.6)| 2.91 (0.5 ~ 4.0)
| EER/COP| | 3.23/3.72| 3/3.5
Season value| SEER/SCOP| | 6.1/3.8| 5.9/3.8
| Energy rating (cooling/heating)| | A++/A| A+/A
| Annual energy consumption (cooling)| kWh| 406| 555
| Annual energy consumption (heating)| kWh| 1831| 2780
Electrical parameters Power supply| f/V/Hz| 1/220–240/50/60|
1/220–240/50/60
---|---|---|---
Performance Airflow| m³/h| 1260/1070/820/680|
1680/1530/1320/1190
Sound power level| dB(A)| 55| 62
| Sound pressure level| dB(A)| 42/40/38/35| 45/42/38/34
Installation| Dimensions without packaging (W/D/H)| mm| 840/840/204|
840/840/246
| Dimensions with packaging (W/D/H)| mm| 990/990/310| 990/990/310
| Net/gross weight| kg| 27/32| 31/36
| Controller| wireless option| YR-HRC01| YR-HRC01
| | wired option| YR-C01| YR-C01
Cover| Model| option| PB-950HE4| PB-950HE4
| Dimensions (W/D/H)| mm| 950/950/50| 950/950/50
| Dimensions with packaging (W/D/H)| mm| 1000/1000/110| 1000/1000/110
| Net/gross weight| kg| 6.5/9| 6.5/9
Performance| Airflow (h)| m³/h| 3000| 3500
---|---|---|---|---
| Sound power level| dB(A)| 67| 66
| Sound pressure level| dB(A)| 54| 53
Installation| Dimensions without packaging (W/D/H)| mm| 890/353/697|
920/372/760
| Dimensions with packaging (W/D/H)| mm| 1046/460/780| 1036/478/820
| Net/gross weight| kg| 48/53| 60/65
| Compressor type| | Twin rotary| Twin rotary
| Refrigerant| | R32| R32
| GWP| | 675| 675
| Liquid pipe diameter| mm| 9.52| 9.52
| Gas pipe diameter| mm| 15.88| 15.88
| Total pipeline length (max)| m| 50| 50
| Max level difference| m| 30| 30
| Refrigerant filling| kg| 1.3| 1.5
| Total pipeline length without refill| m| 10| 30
| Extra refrigerant per metre of pipeline| g/m| 45| 45
Working conditions (out)| Cooling (min – max)| °C| -10 ~ 46| -10 ~ 46
| Heating (min. – max)| °C| -15 ~ 24| -15 ~ 24