SIEMENS RPM Remote Printer Module Instruction Manual

June 9, 2024
SIEMENS

SIEMENS RPM Remote Printer Module

INTRODUCTION

The Model RPM from Siemens Industry, Inc., is an HNET module that interfaces to a Centronics parallel printer. It must be located where access to the FireFinder-XLS/Desigo Fire Safety Modular/Cerberus PRO Modular HNET network and the PSC-12 24VDC power limited output are available.

The RPM is required whenever a logging printer is needed. It translates
the HNET messages into a standard Centronics printer interface. When used
in conjunction with the PAL-1, it provides a supervised logging printer meeting the requirements of NFPA 72 Proprietary or UL 1076 Security systems. For NFPA 72 Local, Auxiliary or Remote Station applications any UL EDP listed Centronics parallel printer may be used (See notes 2, 3, and 4 on Figure 3).
The RPM also provides an optional Foreign System Interface (FSI). The FSI allows other building systems to monitor the status of the FireFinder- XLS/Desigo Fire Safety Modular/Cerberus PRO Modular system. The FSI connects to Ports 1-3 on the RPM. This connection can be either RS-232 (Ports 1 or 3) or RS-485 (Port 2). Only one FSI connection per RPM is allowed. The FireFinder-XLS/Desigo Fire Safety Modular/Cerberus PRO Modular system supports a maximum of two simultaneous FSI connections. With two simultaneous FSI connections the following combinations are supported: Two Local FSI connections or one Global and one Local FSI connection. A total of two Global FSI connections are supported in an XNET network. Each Global FSI connection must originate from its own XLS/Desigo Fire Safety Modular/Cerberus PRO Modular node. Use of the RPM for FSI is not supported for Desigo CC/Cerberus DMS WAN applications.

Features

RPM features are as follows:

  • Supervision of the PAL-1 includes paper out, paper jam, printer off line, printer power off and printer disconnected.
  • an be connected to the HNET either Style 4 or Style 7.
  • Includes diagnostic LEDs to indicate failure of the HNET or the CPU. It also has a power on indicator.
  • Includes a reset switch in the event that the RPM requires a hardware reset.
  • Can be mounted on any smooth surface within 6 feet of the PAL-1.
  • Single Foreign System Interface (FSI) connection (not supported for Desigo CC/Cerberus DMS WAN).
  • FSI supports Local (single system) or Global (multiple systems) operation.

OPERATION

When a system event occurs, the PMI/PMI-2/PMI-3 (XLS), FCM2041-U2 (Desigo Fire Safety Modular), FCM2041-U3 (Cerberus PRO Modular) sends a print message to the RPM via HNET. The RPM is responsible for printing the message. The RPM contains a buffer to ensure that events that occur at a rate faster than the PAL-1 can print them are not lost.

If the FSI option is selected (via Zeus) the same event is sent to the FSI port. This event remains in a buffer until the Foreign System removes it. The RPM continuously monitors the connection to the PAL- 1 checking for any errors that would inhibit printing. Any errors that are detected are communicated to the PMI/PMI- 2/PMI-3 (XLS), FCM2041-U2 (Desigo Fire Safety Modular), FCM2041-U3 (Cerberus PRO Modular) via HNET for annunciation. Restoration to the normal condition is also detected and communicated to the PMI/PMI-2/PMI-3 (XLS), FCM2041-U2 (Desigo Fire Safety Modular), FCM2041-U3 (Cerberus PRO Modular). Print messages that arrive at the RPM during a printer fault are stored in the buffer.SIEMENS-RPM-Remote-Printer-Module-
FIG-2

Controls and Indicators

The HNET side panel of the RPM contains one reset switch, three LEDs, one termination switch and one HNET address switch as shown in Figure 2. A reset switch is located on the top of the panel. Pushing the reset switch re- initializes the RPM operation.

  • POWER (Green) Normally ON. When illuminated, indicates that power for the RPM is applied to the module.
  • CPU FAIL (Yellow) Normally OFF. When illuminated, indicates that the module microprocessor has failed.
  • HNET FAIL (Yellow) Normally OFF. When illuminated, indicates that the HNET communication with the RPM has terminated.

A three-position switch located directly beneath the LEDs on the HNET side of the RPM is used to set the HNET network address of the RPM.

PRE-INSTALLATION

Before connecting either the printer, power, FSI or the HNET, the network address must be set for the RPM using the three-position switch. (Refer to Figure 2 for the location of the switch.) The address for the RPM must be the same as the address selected for it in the Zeus Programming Tool. To increment each digit of the address, press the “+” button above the desired digit; to decrement each digit, press the “-” button below the desired digit. The range of allowable addresses is from 001 to 251 (leading zeros must be used).

NOTE
If the RPM is located at the end of the HNET network (Style 4 only), the termination switch must be set to ON. Otherwise, it must be set to OFF.

Two terminal block covers are provided with the RPM. Each comes as two separate parts, a lower bracket which has a ¾ inch conduit opening and a cover. Attach the lower bracket to each end of the RPM using four of the #10 nuts provided in the RPM hardware kit. Reserve the covers and the remaining hardware until the RPM is mounted and wired. Mount the RPM to either the wall or desk where the PAL-1 is located. Use the four mounting holes in the lower bracket.SIEMENS-RPM-Remote-Printer-Module-FIG-4

NOTES:

  1. The maximum distance from the RPM to the PAL-1 is 6 feet. The two modules must be in the same room.
  2. For NFPA 72 Local, Auxiliary and Remote Station configurations, connect the output of the RPM to any UL EDP listed printer.
  3. The printer must support the EPSON FX command set.
  4. For NFPA 72 Proprietary of UL 1076 configurations use printer SIEMENS Model PAL-1, a UL listed for fire Centronics parallel printer.
  5. The printer is supervised for AC loss, off line, paper out, paper jam, and connection to the RPM.
  6. After loading the paper in the PAL-1 printer, turn off the power and follow the steps below.
  • While pressing the LOAD PARK button, turn on the power to the PAL-1 printer. Keep pressing the LOAD PARK button for 5 seconds.
  • Release the LOAD PARK button.
  • The current setting will print.
  • When printing is completed, the ON LINE indicator will be lit. If the ON LINE indicator is not lit, press the ON LINE button.

WIRING

Remove all system power before installation, first battery then AC. (To power up, connect the AC first, then the battery.) The PAL-1 is connected to the RPM with a standard PC printer cable. This cable is supplied with the RPM. Connect the PAL-1 to the RPM using this cable. The two ends of the cable are different, ensuring proper connection. See Figure 4. The RPM requires 24VDC to operate. This power is available on the PSC-12. See Figure 5 for wiring details.

NOTES:

  1. 18 AWG min., 12 AWG max.
  2. Power limited to NFPA72 per NEC 760.
  3.  No end of line device required.
  4. 50Ω max. total wire resistance.
  5. Refer to PSC-12 Installation Instructions, P/N 315-033060 for ground fault detection impedance.SIEMENS-RPM-Remote-Printer-Module-FIG-5

The RPM can be connected to the HNET either Style 4 or Style 7. Refer to the Zeus configuration for the proper Style. In either case, the RPM can be connected in the middle of an HNET. For a Style 4 network, the RPM can also be connected at the end. If the RPM is connected at the end, care must be taken to properly terminate the HNET. See Figures 6 and 7 for the wiring instructions when the RPM is in the middle and Figure 8 when the RPM is at the end of the network.SIEMENS-RPM-Remote-Printer-Module-
FIG-6SIEMENS-RPM-Remote-Printer-Module-
FIG-7

The PAL-1 requires a standby power source in the event of the loss of primary input power (AC mains). Refer to Figure 9 for the connection of a UPS to meet this requirement.

NOTES

  1. All wires 14 AWG min., 600V insulation.
  2. Wiring to the printer must be 14 AWG min., 600V insulation in conduit.
  3. Use the UPS ICS Lifeline Model 9300057.
  4. Standby Power require-ments: 120 VAC, 0.6A for 24 hours.SIEMENS-RPM-Remote-Printer-Module-FIG-9

NOTES:

  1. 14-18 AWG.
  2. 25 feet Max.
  3. Power Limited to NFPA 70 per NEC 760.
  4. Maximum Voltage 20V peak to peak.
  5. Maximum Current 25mA.
  6. Not supervised.
  7. Foreign System must be UL EDP or ETI listed.
  8. Only ONE FSI (RS-232 or RS-485) connection allowed per RPM.

NOTES:

  1. 14-18 AWG. Twisted pair or twisted shielded pair.
  2. Must be connected within the same room.
  3. Power Limited to NFPA 70 per NEC 760.
  4. Maximum Voltage 8V peak to peak.
  5. Maximum Current 150mA.
  6. Optional supervision (selected in Zeus) (2 wire only).
  7. Foreign System must be UL EDP or ETI listed.
  8. A 120 ohm EOLR is internally connected to Port 2 terminals 1 and 2.
  9. Only ONE FSI (RS-232 or RS-485) connection allowed per RPM.SIEMENS-RPM-Remote-Printer-Module-FIG-11

INSTALLATION

The RPM mounts with two flanges on the side of the terminal block covers. Select a smooth surface within 6 feet of the PAL-1 for the RPM. Position the RPM and attach it to the mounting surface using the four #6 self tapping screws provided. Install the terminal block covers using the 6 remaining #10 nuts. Refer to Figure 3.

ELECTRICAL RATINGS

24V Back Plane Current 0
Screw Terminal 24V Current 150mA Max.
6.2V Back Plane Current 0
24V Standby Current 150mA Max.

Output Power

CAN Network Pair

| 8V peak to peak max.
75mA  max. (during msg transmission)

CYBER SECURITY DISCLAIMER
Siemens provides a portfolio of products, solutions, systems and services that includes security functions that support the secure operation of plants, systems, machines, and networks. In the field of Building Technologies, this in-cludes building automation and control, fire safety, security management as well as physical security systems. In order to protect plants, systems, machines and networks against cyber threats, it is necessary to implement – and continuously maintain – a holistic, state-of-the-art security concept. Siemens’ portfolio only forms one element of such a concept. You are responsible for preventing unauthorized access to your plants, systems, machines and networks which should only be connected to an enterprise network or the internet if and to the extent such a connection is necessary and only when appropriate security measures (e.g. firewalls and/or network segmentation) are in place. Additionally, Siemens’ guidance on appropriate security measures should be taken into account. For additional informa-tion, please contact your Siemens sales representative or visit https://www.siemens.com/global/en/home/company/topicareas/future-of- manufactur-ing/industrial-security.html. Siemens’ portfolio undergoes continuous development to make it more se-cure. Siemens strongly recommends that updates are applied as soon as they are available and that the latest versions are used. Use of versions that are no longer supported, and failure to apply the latest updates may increase your exposure to cyber threats. Siemens strongly recommends to comply with security advisories on the latest security threats, patches and other related measures, published, among others, under https://www.siemens.com/cert/en/cert-security-advisories.htm.

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

SIEMENS User Manuals

Related Manuals