SIEMENS SLIM Loop Isolator Module Instruction Manual
- June 9, 2024
- SIEMENS
Table of Contents
SLIM Loop Isolator Module
Instruction Manual
OPERATION
Figure 1 SLIM-1 Module
The Model SLIM Loop Isolator Module from Siemens Industry, Inc. isolates short
circuits on FS-250C analog loops. By placing devices between SLIMs during
installation, a short in the wiring within that group is disconnected from the
rest of the loop.
The remainder of the devices continue to operate.
The SLIM operates in both Class A and Class B circuits.
A yellow LED flashes when a device detects a short circuit. The SLIM then
isolates that part of the loop. When the short is removed, the SLIM
automatically restores the loop to normal operation. The SLIM does not have a
loop address and therefore does not require address programming nor does it
reduce the loop capacity below 252 devices.
Remove all system power before installation, first the battery and then the
AC.
ELECTRICAL RATINGS
Voltage: | 24 Vdc |
---|---|
Current: | 1mA max |
INSTALLATION
The SLIM is a polarity insensitive module. Refer to Figure 1 for the location of the two input terminals, two output terminals and earth ground. Line 1 and Line 2 can be either line of the loop.
Terminal Number | Description |
---|---|
1 | In — Line 1 |
2 | In — Line 2 |
3 | Out — Line 1 |
4 | Out — Line 2 |
5 | Earth Ground |
Figure 2 Mounting the SLIM
Mechanical Installation (See Figure 2)
- Use a standard 3 1/2-inch deep, double gang electrical switchbox or a 4-inch square electrical box that is 2 1/8 inches deep.
- Connect the field wiring. Press the SLIM into the box and fasten the module plate to the box.
- Cover the module front plate with the plate supplied and fasten with screws supplied.
The SLIM may be used in two circuit configurations as follows:
(See Figure 3) In Class B wiring each SLIM isolates a branch on the circuit.
Note that a short on the main branch causes the entire loop to fail. To
prevent this, mount the SLIMs at the enclosure and run each branch
independently.
Class B
- All wiring must comply with national and local codes.
- In order to provide adequate protection, it is recommended that you do not install more than 20 devices on a single SLIM.
- Minimum wire gauge is 18 AWG.
- The total wire resistance (both wires) between SLIMs cannot exceed 20 ohms.
- Do not install more than 15 SLIMs per FDLC loop.
- All circuits are supervised.
- Refer to the FS-250C Manual, P/N 315-049589C for the list of compatible devices.
- All terminals are power limited.
Figure 3 SLIM Wiring Diagram – Class B Installation
Class A Single Loop
(See Figure 4) IIn Class A wiring the SLIMS are wired in series with the loop
wiring.
This results in a single continuous loop. If any group in the loop has a
short, that group is lost and a Class A circuit failure results.
- All wiring must comply with national and local codes.
- In order to provide adequate protection, it is recommended that you do not install more than 20 devices on a single SLIM.
- Minimum wire gauge is 18 AWG.
- The total wire resistance (both wires) between SLIMs cannot exceed 20 ohms.
- Do not install more than 15 SLIMs per FDLC loop.
- All circuits are supervised.
- Refer to the FS-250C Manual, P/N 315-049589C for the list of compatible devices, as applicable.
- All terminals are power limited.
Figure 4 SLIM Wiring Diagram – Class A Installation (Single Loop)
Siemens Canada Limited
Building Technologies Division
2 Kenview Boulevard
Brampton, Ontario L6T 5E4 Canada
P/N 315-034904C-3
firealarmresources.com