SIEMENS MXL VDT Interface Module Circuit Board Instruction Manual

June 9, 2024
SIEMENS

Fire Safety
CERBERUS PYROTRONICSTM MODEL VDT
Interface for the CERBERUS PYROTRONICSTM MXL

INTRODUCTION

The CERBERUS PYROTRONICS™ Model VDT Interface for the MXL provides both an alternate way of displaying printer data (in place of the TSP-40) and an additional way to control the MXL through use of the keyboard option. By using the VDT types listed below, the operator can perform commands such as acknowledging events, silencing/unsilencing audibles, resetting the system, viewing system lists, changing detector sensitivities, controlling outputs, etc., from the VDT keyboard. The VDT Interface is available with MXL firmware revisions 2.12 and higher.

OPERATION

Once the MXL system is powered up, the VDT displays system information in the same way that a printer does. To access any type of input to the VDT, begin typing the command. MXL finishes the information it is printing first, and then it presents the command prompt, as shown below:
MXL command: (text typed) Type one of the available commands using the format listed. MXL processes the command in the same way it processes a command executed
from the MXL Menu at the MKB keyboard. If there are items waiting for printing, they take precedence over any List commands. To use Control functions from the VDT, enter the level 1 or 2 password from the CSG-M at the keyboard. Before entering any Control function command, type LON (the log-on commana) at the keyboard, followed by the appropriate password. If a Control command is entered before logging on, MXL indicates that the log-on is required.
NOTE: Commands are NOT case sensitive.

CSG-M Requirements
NOTE: CSG-M does not allow this option to be unsupervised in an NFPA 72 Proprietary system.
To use the VDT interface, set the printer option in the CSG-M Network Map, MKB subaddress, to one of the following (depending on the hardware available):
TI820KSR (supervised)
MXL-VDT 80 (supervised)
MXL-VDT 132 (supervised)
VDT 80 (unsupervised)
VDT 132 (unsupervised)
Keyboard control of the VDT is NOT available if one of the following is selected:
TI820KSRO
TSP-40 Strip printer
DEC LA50
Generic 80
Generic 132

Acknowledgment and Audible Commands
The Acknowledgment and Audible commands entered at the keyboard operate in the same way as they do when entered from the MKB. To execute any of the following commands, a password log-on is required (See LON command, page 5). Type the desired command at the prompt, followed by ENTER.
NOTE: The XL3 commands given in parentheses are honored for users accustomed to XL3 commands.

AAL – Acknowledge Alarm (AA)
ASP – Acknowledge Supervisory
ATR – Acknowledge Trouble (AT)
ASC – Acknowledge Security
When Block Acknowledge is selected in the CSG-M, it acknowledges all existing unacknowledged events for that event queue. Note that the acknowledgment is printed on the VDT, as it would be on the printer.
NOTE: The CSG-M does not allow block acknowledge for an NFPA 72 Proprietary system.

When Individual Acknowledge is selected in
the CSG-M, it acknowledges the most recent unacknowledged event in that event queue. Note that the acknowledgment is printed on the VDT as it would be on the printer.
SUA – Silence/Unsilence Audibles
The SUA command toggles the state of the system’s silenceable audibles.
CRS – Reset the MXL (CR)
When all events are acknowledged, all audibles are silenced, all queue information is printed, and the Control Reset command is issued, the MXL resets just as if it had been reset from the MKB. (Note that the XL3 command CR is honored for users accustomed to XL3 commands.)

Entering the LIST Commands from the VDT
The List commands give an identical output to the printouts obtained from the MXL menu using the PRINT key. Those commands are listed and described below.
Note that some of the commands include the notations m, m-d, etc. Replace these notations with the information given in the command description. When entering module or device number information, leading zeros are NOT required. Separate the data fields (i.e., module, device, arm, etc.) with either a space, a hyphen, or a comma.

LST – List Status (LS)
Use the LST command for a listing of the current MXL status. At the command prompt, type LST followed by ENTER. A time and date stamped status summary prints a listing similar to the following:

System Status at 12:12:12 Dec 12, 2012 :
0 ALARM OQ ALARM ACK
OQ SUPERU OQ SUPERU ACK
0 TROUBLE 0 TROUBLE ACK
Q SECURTY 0 SECURTY ACK

(Note that the XL3 command LS is honored for users accustomed to XL3 commands.)

LAL – List Alarms (LA)
Use the LAL command for a listing of current alarms. At the command prompt, type LAL followed by ENTER. The events in the alarm queue are displayed on the VDT in the same format as the list alarms print item in the MXL menu (See List Alarm in the MXL/MXLV Manual, P/N 315-092036).
(Note that the XL3 command LA is honored for users accustomed to XL3 commands.)

LSP – List Supervisory
Use the LSP command for a listing of current supervisory events. At the command prompt, type LSP followed by ENTER. The events in the supervisory queue display on the VDT in the same format as the List Supervisory print item in the MXL menu (See List Supervisory in the MXL/ MXLV Manual, P/N 315-092036).
LTR – List Trouble (LT)
Use the LTR command for a listing of current troubles. At the command prompt, type LTR followed by ENTER. The events in the trouble queue display on the VDT in the same format as the List Trouble print item in the MXL menu (See List Trouble in the MXL/MXLV Manual, P/N 315- 092036).
(Note that the XL3 command LT is honored for users accustomed to XL3 commands.)
LSC – List Security
Use the LSC command for a listing of current security events. At the command prompt, type LSC followed by ENTER. The events in the security queue display on the VDT in the same format as the List Security print item in the MXL menu (See List Security in the MXL/MXLV Manual, P/N 315-092036).
LSS m – List Sensitivity Settings
Use the LSS command for a listing of sensitivities. At the command prompt, type LSS, space, and the module number of the loop for which the list is needed. Press ENTER. The sensitivity settings for the individual smoke detectors on the  selected analog loop (m) are displayed on the VDT. They appear in the same format as they appear in the List Sensitivity Settings print item in the MXL menu (See List Sensitivity Settings in the MXL/MXLV Manual, P/N 315-092036).
LAV m – List Analog (analog2) Voltage (LDO)
Use the LAV command for a listing of analog voltages. At the command prompt, type LAV, space, and the module number of the loop for which the list is needed. Press ENTER. The analog2 voltages for the individual smoke detectors on the selected analog loop (m) are displayed on the VDT in the same format as they appear in the corresponding print item in the MXL menu (See List Voltages in the MXL/MXLV Manual, P/N 315-092036).
LTV m – List Threshold Voltage
Use the LTV command for a listing of threshold voltages. At the command prompt, type LTV, space, and the module number of the loop for which the list is needed. Press ENTER. The threshold voltages for the individual devices on the selected analog loop (m) are displayed on the VDT in the same format as they are in the corresponding print item in the MXL menu (See List Voltages in the MXL/MXLV Manual, P/N 315- 092036).
LSV m – List Sensitivity Voltages (LF)
Use the LSV command for a listing of sensitivity voltages. At the command prompt, type LSV, space, and the module number of the loop for which the list is needed. The sensitivity voltages for the individual devices on the selected analog loop (m) are displayed on the VDT in the same format as they are in the corresponding print item in the MXL menu (See List Voltages in the MXL/MXLV Manual, P/N 315-092036). [Note that the XL3 command LF m (where m is the network ALD-2 loop for which the voltage listing is needed) is honored for users accustomed to XL3 commands. ] LMT – List Module Type
Use the LMT command for a listing of module types in the system. At the command prompt, type LMT, then press ENTER. The types for all modules in CSG-M are displayed on the VDT in the same format as they are in the List Module print item in the MXL menu (See List Module in the MXL/MXLV Manual, P/N 315092036).
LDT m- List Device Type
Use the LDT command for a listing of device types. At the command prompt, type LDT, space, and the module number of the loop for which the list is needed. Press ENTER. The types for the individual devices on the selected analog loop (m), aS programmed in CSG-M, are displayed on the VDT in the same format as they are in the
List Device print item in the MXL menu (See List Device in the MXL/MXLV Manual, P/N 315- 092036).
LMS m – List Messages (LM)
Use the LMS command for a listing of device messages. At the command prompt, type LMS, space, and the module number of the loop for which the list is needed. Press ENTER. The custom messages for each device on the selected analog loop (m) are displayed on the VDT in the same format as they are in the List Message print item in the MXL menu (See List Message in the MXL/MXLV Manual, P/N 315- 092036).
[Note that the XL3 command LM m (where m is the network ALD-2 loop for which the listing is needed) is honored for users accustomed to XL3 commands.] LSW – List Software Versions
Use the LSW command for a listing of MXL software version information. At the command prompt, type LSW and press ENTER. A time and date stamped report containing the system custom message, MXL and CSG-M version, CSG-M source date, and the CSG-M load time and date displays on the VDT in the same format as in the List Software Version print item of the MXL menu (See List Software Version in the MXL/MXLV Manual, P/N 315-092036).
LCV m – List XLD-1 Calibration Voltage
Use the LCV command for a listing of XLD-1 calibration voltages. At the command prompt, type LCV, space, and the module number of the loop for which the list is needed. Press ENTER. The calibration voltages for the individual devices on the selected XLD-1 analog loop (m) are displayed on the VDT in the same format as they appear in the corresponding print item in the MXL menu (See List XLD-1 Calibration Voltage in the MXL/MXLV Manual, P/N 315-092036).
LIV m – List XLD-1 ID Voltage
Use the LIV command for a listing of XLD-1 ID voltages. At the command prompt, type LIV, space, and the module number of the loop for which the list is needed. Press ENTER. The ID voltages for the individual devices on the selected XLD-1 analog loop (m) are displayed on the VDT in the same format as they appear in the corresponding print item in the MXL menu (See List XLD-1 ID Voltage in the MXL/MXLV Manual, P/N 315-092036).
L2V m – List XLD-1 2nd ID Voltage
Use the L2V command for a listing of XLD-1 2nd ID voltages. At the command prompt, type L2V, space, and the module number of the loop for which the list is needed. Press ENTER. The 2nd ID voltages for the individual devices on the selected XLD-1 analog loop (m) are displayed onthe VDT in the same format as they appear in the corresponding print item in the MXL menu (See List XLD-1 2nd ID Voltage in the MXL/ MXLV Manual, P/N 315-092036).
LKP m – List Air Sampling Smoke Percent
Use the LKP command for a listing of Air Sampling smoke percent of scale values. At the command prompt type LKP, space, and the NIM-1 (ASP) module number for which the list is needed. Press ENTER. The Air Sampling smoke percents for the selected module (m) are displayed on the VDT in the same format as they appear in the corresponding print item in the MXL menu.
LAP m – List Air Sampling Airflow Percent
Use the LAP command for a listing of Air Sampling airflow percent of scale values. At the command prompt type LAP, space, and the NIM-1 (ASP) module number for which the list is needed.
Press ENTER. The Air Sampling airflow percents for the selected module (m) are displayed on the VDT in the same format as they appear in the corresponding print item in the MXL menu.
LAT m – List Air Sampling Alarm Trip Points
Use the LAT command for a listing of Air Sampling alarm trip point values. At the command prompt type LAT, space, and the NIM-1 (ASP) module number for which the list is needed. Press ENTER. The Air Sampling alarm trip points for the selected module (m) are displayed on the VDT in the same format as they appear in the corresponding print item in the MXL menu.
LFT m – List Air Sampling Airflow Trip Points
Use the LFT command for a listing of Air Sampling airflow trip point values. At the command prompt type LFT, space, and the NIM-1 (ASP) module number for which the list is needed. Press ENTER. The Air Sampling airflow trip points for the selected module (m) are displayed on the VDT in the same format as they appear in the corresponding print item in the MXL menu.
LPS m – List Percent/Ft Sensitivity
Use the LPS command for a listing of percent/ft sensitivity. At the command prompt type LPS, space, and the module number of the loop for which the list is needed. Press ENTER. The percent/ft sensitivity for the individual devices on the selected loop (m) are displayed on the VDT in the same format as they appear in the corresponding print item in the MXL menu.
LPP m – List Percent/Ft Pre-Alarm
Use the LPP command for a listing of percent/ft pre-alarm values. At the command prompt type LPP, space, and the module number of the loop for which the list is needed. Press ENTER. The percent/ft pre-alarm values for the selected loop (m) are displayed on the VDT in the same format as they appear in the corresponding print item in the MXL menu.
LPA m – List Percent/Ft Analog
Use the LPA command for a listing of percent/ft analog values. At the command prompt type LPA, space, and the module number of the loop for which the list is needed.  Press ENTER. The percent/ft analog values for the selected loop (m) are displayed on the VDT in the same format as they appear in the corresponding print item in the MXL menu.
LAS m – List ASD Applications
Use the LAS command for a listing of ASD applications of a particular module. At the command prompt type LAS, space, and the module number for which the list is needed. Press ENTER. The ASD applications of the selected module (m) are displayed on the VDT in the same format as they appear in the corresponding print item in the MXL menu.
LOD – List Disarmed Output State
Use the LOD command to list the output points that are disarmed in the system together with their states, NORMAL or OFF-NORMAL. At the command prompt type LOD, space and the module number. Press ENTER. The system displays the disarmed output devices in that module.
LID – List Disarmed Input State
Similar to the LOD command, the LID command displays the disarmed input points in the module. Use the LID command to list the input points that are disarmed in the system together with their states, NORMAL or OFF-NORMAL. At the command prompt type LID, space and the module number. Press ENTER. The system displays the disarmed output devices in the same format as that of the LOD command.
For example:
Enter MXL command: LID 15
Listing of Disarmed Input Points for Module 1 CALD):
1-ILP-2 Photo Detector: NORMAL
15-TRI-2/ 60D Dual Switch: OFF-NORMAL
If there are no disarmed input points in that module, the system will respond as follows:
Listing of Disarmed Input Points for Module 15 CCRM4):
NO ENTRIES: Only default values found

LCM – List Modules in Commissioning Mode
Use the LCM command to list the module(s) in the system that are currently in summarized (commissioning) mode. At the command prompt type LCM. Press ENTER. The system lists the modules in commissioning mode as shown in the following example:
Listing of Modules in Commissioning Mode:
1-ALD: ON 2-ALD: ON 3-FS Interface (NIM): ON 4-CRM4: ON
If there are no modules in commissioning mode, the following message is displayed on the VDT: Listing of Modules in Commissioning Mode:
NO ENTRIES: only default values found

Entering the CONTROL Commands from the VDT
LON xxxx – Log On (Enter password)
Enter a CSG-M level 1 or level 2 password from the keyboard to access acknowledge, audible silence/ unsilence, reset, and control functions from the VDT. Type LON, space, and the password. Press ENTER. This password remains in effect as long as there is keyboard activity from the VDT keyboard for password protected commands. However, if there are 5 minutes of inactivity at the VDT keyboard, the current password log-on is canceled. The password time- out time is CSG-M programmable starting
with revision 7.01.
LOF – Log OFF (Cancel current password level) Use the LOF command to cancel the current password log-on. This prevents any further control function for the VDT keyboard until the next log-on. Type LOF and press ENTER from the VDT keyboard to execute this command. CSS m-d x – Change Sensitivity (CS)
Use the CSS command to change the sensitivity setting of a detector from the VDT. At the command prompt, type CSS, space, the moduledevice number, and the letter that  represents the desired sensitivity setting of the smoke detector. Press ENTER.

The lower case letters represent the following:
m_ The ALD-2I loop network address of the smoke detector whose sensitivity is to be changed.
d The loop subaddress of the smoke detector whose sensitivity is to be changed.
x The desired sensitivity setting for the smoke detector.

MXL software revisions before 3.00:

L – Low (0)
N – Normal (1)
M – Medium (2)
H – High (3)

MXL software revisions 3.00 and higher:

Low3 (0)
Low2 (1)
Lowl (2)
Normal (3) or Norn
Hi_1 (4)
Hi_2 (5)
Hi_3 (6)

The ranges of XLD-1 sensitivity for MXL Software revisions 6.04 and higher are:
Low1 (2)
Normal (3) or Norn
Hi_1 (4)
Hi_2 (5)

If a sensitivity setting for XLD-1 is entered outside of the XLD-1 range, yet within the ALD-2I sensitivity range, the error message Device ID mismatch will appear.
[Note that the XL3 command CS m-d x (where mis the network ALD-2I loop, d is the subaddress of the smoke detector, and x is the desired sensitivity setting using number or letter) is honored for users accustomed to XL3 commands.] CIP m-d x – Change (Arm/disarm) Input Point (CO)
Use the CIP command to arm or disarm an input device from the VDT. At the command prompt, type CIP, space, the module-device number, space, and the letter that represents the desired arm/disarm state of the input. Press ENTER.

The lower case lefters represent the following:
m The ALD-2Is loop network address of the input to be armed/disarmed.
d The loop subaddress of the input to be armed/disarmed.
x The desired arm/disarm state of the input.
A – Arm input
D – Disarm input

[Note that the XL3 command CO or COI m-d x (where m is the network ALD-2 loopd is the subaddress of the input point, and x is the desired armed/disarmed state) is honored for users accustomed to XL3 commands.]

COP m-d x y – Change Output Point (CO)
Use the COP command to manually control an output point from the VDT. At the command prompt, type COP, space, the module-device number, space, and the letters representing the desired arm/disarm and energize/de-energize state of the output. Press ENTER.

m The ALD-2I loop network address of the output to be changed.
d The loop subaddress of the output to be changed.
x The desired arm/disarm state of the output.
A – Arm output
D – Disarm output
y The desired energize/deeneraize state of the output.
E – Energize output
D – De-energize output

[Note that the XL3 command CO or COO m-d x y (where mis the network ALD-2I loop, d is the subaddress of the output point, x is the desired armed/disarmed state, and y is the desired energized/de-energized state) is honored for users accustomed to XL3 commands.] CAT – Control Air Sampling Alarm Trip Points
Use the CAT command to modify the Air Sampling alarm trip point values. At the command prompt type CAT, space, the NIM-1 (ASP) module number, space, the device number (d), space, the pre1 alarm trip level, space, the pre2 alarm trip level, space, and the alarm trip level. All trip level values should be from 0-9 with 0 indicating 100% scale. Press ENTER. The new Air Sampling alarm trip points are now in effect.
CFT – Control Air Sampling Airflow Trip Points
Use the CFT command to modify the Air Sampling airflow trip point values. At the command prompt type CFT, space, the NIM-1 (ASP) module number, space, the device number (d), space, the low airflow trip level, space, and the high airflow trip level. All trip level values should be from 0-9 with 0 indicating 100% scale. Press ENTER. The new Air Sampling air flow trouble trip points are now in effect.
CPS m-d x.x – Control Percent/Ft Sensitivity
Use the CPS command to change the percent/ft sensitivity of the selected module. At the command prompt type CPS, space, the moduledevice number, space, and the desired sensitivity %/ft settings. Press ENTER. The new percent/ft sensitivity settings are now in effect.
CPP m-d x.x – Control Percent/Ft Pre-Alarm
Use the CPP command to change the percent/ft pre-alarm settings of the selected module. At the command prompt type CPP, space, the moduledevice number, space, and the desired %/ft prealarm settings. Press ENTER. The new percent/ft pre-alarm settings are now in effect.
CAP m-d apps – Control ASD Application
Use the CAP command to change the ASD application of the selected device. At the command prompt type CAP, space, the module-device number, space, and the desired ASD application (apps). Refer to Table 1 for a listing of ASD applications and abbreviations. Press ENTER. The new percent/ft pre-alarm settings are now in effect.
NOTE: If the ASD application is changed while Test ASD is on, the changes will not be effective until Test ASD is turned off.

TABLE 1 ASD SUBMENU ABBREVIATIONS

VDT Abbrev. (ASD apps)| Application| Description
N| Disable| No Applications (Standard Photoelectric Detector)
0| Office (Retail)| Reasonably clean, climate controlled atmosphere
W| Warehouse
(Light
Manufacturing)| Airborne dust, equipment, fork truck and light to medium dock area exhaust fumes
L| Lobby (Atrium)| Relatively dean area. temperature changes, cellular phones, smoking
C| Computer Room| Very controlled environment, dean. temperature closely regulated, high cost clean machinery operating, no smoking, high air velocity
D| Dormitory| Airborne dust and temperature changes, living quarters, cooking fumes, smoking
H| Healthcare| Higher level risk, relatively dean, electronic equipment
P| Parking Garage| Airborne dust. car and diesel fumes, temperature swings
U| Utility (Transformer) Room| Normal to somewhat dirty environment. heat from running equipment
S| Precious Storage (Sensitive Environment)| Sensitive materials or equipment storage, dean dust-free environment, earliest warning desired
T| Hostile Environment| Dirty, dusty, humid, operating equipment. RF present, wide temperature swings
K| Duct (Open air or duct housing)| Dirty, dusty, humid, wide temperature swings. high air velocity

Using the TEST Command from the VDT
CTD hh:mm:ss nn-dd-yyyy – Change Time (CT)
The CTD command, followed by the time and date typed in the format described, changes the time and date in the MXL. The command is executed when ENTER is pressed. Type the command as indicated above, making sure to include spaces, colons, and hyphens.

The lower case letters represent the following:
hh — The hour, in a 24 hour format, to which the MXL is set when the command is executed.
mm The minute to which the MXL is set when the command is executed.
Ss The second to which the MXL is set when the command is executed.
nn The month to which the MXL is set when the command is executed.
dd The day to which the MXL is set when the command is executed.
yyyy The year to which the MXL is set when the command is executed.

NOTE: The following items MUST be included:

  1. The spaces between the command/time and time/date strings.
  2. The colons in the time string.
  3. The hyphens in the date string.

PWR m – Power Report
Use the PWR command for a report of power supply data for the MMB or a PSR-1. At the command prompt, type PWR, space, and the module number of the power supply for which the report is needed. Press ENTER.

HST History Log Status
Use the HST command for a summary of history log data. This data includes the history log start date, the number of events logged, the history log type, and the percent of history log used.
HAL hh:mm:ss mm-dd-yyyy – Alarm History
Use the HAL command for a list of the alarms recorded since the date shown in the command line. If the date parameter is omitted, the history log start date is used.
HSP hh:mm:ss mm-dd-yyy – Supervisory History
Use the HSP command for a list of the supervisories recorded since the date shown in the command line. If the date parameter is omitted, the history log start date is used.
HTR hh:mm:ss mm-dd-yyy – Trouble History
Use the HTR command for a list of the troubles recorded since the date shown in the command line. If the date parameter is omitted, the history log start date is used.
HSC hh:mm:ss mm-dd-yyyy – Security History
Use the HSC command for a list of the securities recorded since the date shown in the command line. If the date parameter is omitted, the history log start date is used.
HAE hh:mm:ss mm-dd-yyyy – All Event History
Use the HAE command for a list of all events recorded since the date shown in the command line. If the date parameter is omitted, the history log start date is used.
LMP – Annunciator Lamp Test
Enter the LMP command to perform a lamp test on the annunciator. The MKB lamp tests in the same way it would for the corresponding menu function.
LCD – Annunciator Display Test
Enter the LCD command to perform an LCD display test on the annunciator. The MKB tests in the same way it would for the corresponding menu function.
DEV m-d x – Device LED
Use the DEV command to turn on a device (detector) LED. Type the DEV command, space, the full device address (module-device) and the desired state, x, of the LED (use E or D). Press ENTER.
m The ALD-21 loop network address of the detector LED to be changed.
d The loop subaddress of the detector LED to be changed.
x The desired energized/deenergized state of the LED.
E – Energize LED (or LED on)
D – De-energize LED (or LED off)

MLT m – MOI Lamp Test
Use the MLT command to perform a lamp test on MOD-16 outputs of an MOI module. Type the MLT command, space, and the network address of the MOI to be lamp tested. Press ENTER. The MOI lamp tests as it would for the corresponding menu item.
XLT m – XLD-1 Point Annunciator (PAX) Lamp Test
Use the XLT command to perform a lamp test on a PAX output on a XLD-1 loop. Type the XLT command, space, and the network address of the XLD-1 loop containing the PAX to be lamp tested. Press ENTER. The PAX lamp tests in the same way it would for the corresponding menu item.
PRE m-d – Test Pre-Alarm
Use the PRE command to test pre-alarm logic. At the command prompt type PRE, space, and the module-device number. Press ENTER. The detector is sent its current analog2 reading as a pre-alarm threshold so that the detector will prealarm.
ASD – Test ASD Devcies
Use the ASD command to test ASD detectors. At the command prompt type ASD. Press ENTER. The ASD testing is enabled and a Trouble In is posted in the System. Typing ASD a second time will toggle the test, disabling the testing and posting a Trouble Out.

NOTES:

  1. When toggling between Testing Enabled and Testing Disabled, there is a three minute time period that separates the two states.
  2. If Test ASD is actived and left alone, the system will automatically disable the test (time out) after four hours.

SCM – Set Commissioning Mode for Module
Use the SCM command to set a particular module in commissioning mode. At the command prompt type SCM, space, the module number, space, ON (or OFF). Press ENTER. Type ON to activate the commissioning mode or OFF to deactivate it. For example: Enter MXL command: SCM 1 ON

Module 1 will then be put into commissioning mode. If the module is not in system, then an error message will be printed out:
Enter MXL command: SCM 266 OFF Invalid Module

CMC – Commissioning Mode Control
Use this command to activate/deactivate the commissioning mode globally. Modules that are commissioned individually stay inactive until commissioning mode is turned on globally. At the command prompt type CMC. Press ENTER.
Issuing the command CMC twice toggles the system commissioning mode on and off as shown the example below:
Enter MXL command: CMC TROUBLE IN 253 15:04:17 Feb 17, 1997-CERBERUS
Pyrotronics-
System Commissioning Mode, MXL Panel Enter MXL command: CMC
TROUBLE OUT 253 15:04:25 Feb 17, 1997-CERBERUS
Pyrotronics-
System Commissioning Mode, MXL Panel

HOF – History Logging Off
Use the HOF command to manually turn off History logging. At the command prompt type HOF. Press ENTER. MXL History logging is now temporarily disabled.
In order to access this feature, the History Option must be enabled in the CSG-M and downloaded to the MXL. A password is required for the HOF command.
History turned on or off using the MKB menu or VDT is unaffected through PANEL RESET, and defaults to the setting in CSG-M upon power-up.
HON – History Logging On
Use the HON command to manually turn on History logging. At the command prompt type HON. Press ENTER. MXL History logging is now enabled (if previously turned off). In order to access this feature, the History Option must be enabled in the CSG-M and downloaded to the MXL. A password is required for the HON command.
History turned on or off using the MKB menu or VDT is unaffected through PANEL RESET, and defaults to the setting in CSG-M upon power-up.
HAR – Arm/Disarm (Enable/ Disable) History Erasure
Use the HAR command to manually arm/disarm (enable/disable) History log erasure. At the command prompt type HAR. Press ENTER. The HAR command must be enabled before History log erasure can be made using the HER command. In order to access this feature, the History Option must be enabled in the CSG-M and downloaded to the MXL. A password is required for the HAR command.

HER – History Log Erase
Use the HER command to manually erase the History log. (The History Erase option must be enabled first via the MKB menu or HAR command at the VDT). At the command prompt type HER. Press ENTER.
In order to access this feature, the History Option must be enabled in the CSG-M and downloaded to the MXL. A password is required for the HER command.

MXL-VDT 80/132 SETUP
To enter the MXL-VDT setup menu, simultaneously press both the Shift and Select keys.
Use the following parameters in the setup menu when setting up the supervised MXL-VDT 80/132 terminal.

Note: To return to MXL-VDT default settings, depress D from the terminal setup menu.

GENERAL SETUP

Characteristic| Setting
Emulation
Enhancements
Virtual Term
Scroll Style
Auto Scroll
Auto Wrap
Received
Auto Page*
Warning Bell
Margin Bell
Bell Sound Per
Block Term
Send ACK
Monitor Mode| Wyse50+
Off
Off
Jump
On
On
CR
On
On
Off
Preference (default 3-loud)
US/CR
Off

*To view other pages when the auto page setting is on, simultaneously press the Cntrl and Pg Up keys or the Cntrl and Pg Dn keys.

DISPLAY SETUP

Characteristic| Setting
Columns
80/132 Clear
Lines
Pages
Status Line
Cursor Style
Cursor
Screen Saver
Background
Attributes
Wprt Intensity
Wprt Reverse
Wprt Underline
Refresh
Pound Clear
Auto Front Load| Per CSG-M (default 80)
Off
24
1 x lines
Ext
Per preference (default steady block)
Per preference (default on)
Off
Dark
Page
Normal
Off
Off
60 Hz
US
On

FUNCTION KEY SETUP
None required – Performed by MXL
TABS SETUP
None required
ANSWERBACK SETUP
Do NOT alter data in this menu.
Data is preset at factory.
Altering this data results in VDT supervision errors.

KEYBOARD SETUP

Characteristic| Setting
Key Click| On
Key Repeat| Off
Key Lock| Caps
Return Key| CR
Enter Key| CR
Back Space Key| BS/DEL
Left Alt Key| Funct
Break| Off
Xmt Limit| None
Fkey Xmt Limit| None
Key Code| ASCII
Language| US
ANSI SETUP

Characteristic| Setting
Fkey Lock| Off
Feature Lock| On
KeyPad| Numeric
Cursor Keys| Normal
Xfer Term| EOS
Char Mode| National
Keys| Typewriter
VT100 ID| VT100
Print| National
Send| All
Send Area| Screen
Print Area| Screen
Send Term|  None
Print Term| None
Print Mode| Normal
Auto Answerbk| On
COMMUNICATION SETUP

Characteristic| Setting
Main Baud Rate| Per CSG-M (default 1200 baud)
Main Data/Parity| Per CSG-M (default 8 data bits/no parity)
 Main Stop Bits| Per CSG-M (default 1 stop bit)
Ignore 8th Bit| On
Main Rcv Hndsk| None
Main Xmt Hndsk| None
Comm Mode| Full Duplex
Disconnect| 2 seconds

Use the following minimum cabling requirements when connecting a supervised interactive terminal to an MXL System.
PIM-1 to MXL-VDT (80-132)
Minimum Cabling Requirements

FROM PIM-1 TO MXL-VDT(80-132)
Terminal No. Signal
4 RxD
5 TxD
2 SigGnd

PIM-1 to TI-820KSR
Minimum Cabling Requirements

FROM PIM-1 TO MXL-VDT(80-132)
Pin No. Signal
4 RxD
5 TxD
2 SigGnd
3 Printer Busy

MXL-VDT 80/132 SETUP USING EITHER THE AUXILIARY OR PARALLEL PORT
Use the following settings in the setup menu when installing an unsupervised VDT with an unsupervised printer. The settings are given for several printers.
NOTE: The CSG-M selection for the termi-nal for all three printers listed below must be either VDT-80 or VDT-132 (unsupervised).
When installing a parallel printer, use a standard DB-25 (male) to Centronix printer cable.

GENERAL SETUP Setting
Characteristic Texas Inst TI-820KSR

Printer
Emulation| Wyse 50+| Wyse 50&| Wyse 50+
Enhancements| Off| Off| Off
 Virtual Term| Off| Off| Off
Scroll Style| Jump|  Jump| Jump
Auto Scroll| On| On| On
 Auto Wrap| Off| Off| Off
Received| CR| CR| CR
 Auto Page*| Off| Off| Off
Warning Bell| On| On| On
Margin Bell| Off| Off| Off
 Bell Sound| 1| 1| 1
Block Term| US/CR| US/CR| US/CR
 Send ACK| Off| On| On
 Monitor Mode| Off| Off| Off

To view other pages when the auto page setting is on, simultaneously press the Cntrl and Pg Up keys or the Cntrl and Pg Dn keys.

COMMUNICATION SETUP

Characteristic| Setting
Texas Inst 71-820KSR| C. Itoh CI-2500| Generic Parallel Printer
Main Baud Rate
Main Data/Parity
Main Stop Bits
Ignore 8th Bit
Main Rcv Hndsk
Main Xmt Hndsk
Comm Mode
Disconnect
Aux Baud
Aux Data/Parity
Aux Stop Bits
Aux Rcv Hndsk
Aux Xmt Hndsk
Aux Port
Aux Interface
Printer| Per CSG-M
Per CSG-M
Per CSG-M
On
None
None
Full Duplex
2 seconds

Per CSG-M
Per CSG-M
None
None
RS232
RS232
Serial| Per CSG-M
Per CSG-M
Per CSG-M
On
None
None
Full Duplex
2 seconds

as desired
as desired
DTR/XOff
XONXOff
RS232/422
RS422
Serial| Per CSG-M
Per CSG-M
Per CSG-M
On
None
None
Full Duplex
2 seconds


**
DTR/XOff
None
RS232/422
RS433
Parallel

  • For best results, set the auxiliary port baud rate higher than the main baud rate.
    ** Setting doesn’t matter when using parallel printer.

DISPLAY SETUP

Characteristic| Setting
Texas Inst  71-820KSR| C. Itoh CI-2500| Generic Parallel Printer
Columns
80/132 Clear
Lines
Pages
Status Line
Cursor Style
Cursor
Screen Saver
Background
Attributes
Wprt Intensity
Wprt Reverse
Wprt Underline
Refresh
Pound Char
Auto Font Load| Per CSG-M
Off
Per preference
1 x lines
Off
Per preference
On
Off
Dark
Page
Normal
Off
Off
60
Hz
US
On| 80
Off
24
1 x lines
Off
Per preference
On
Off
Dark
Page
Normal
Off
Off
60
Hz
US
On| Per CSG-M
Off
Per preference
1 x lines
Off
Per preference
On
Off
Dark
Page
Normal
Off
Off
60 Hz
US
On

KEYBOARD SETUP

Characteristic Setting
Texas Inst TI-820KSR C. Itoh Cl-2500
Key Click  Off
Key Repeat  Off
Key Lock  Caps
Return Key  CR
Enter Key  CR
Back Space Key  BS/DEL
Left Alt Key  Funct
Break  Off
Xmt Limit  None
Fkey Xmt Limit  None
Key Code  ASCII
Language  US

ANSI SETUP

Characteristic Setting
Texas Inst TI-820KSR C. Itoh Cl-2500
 Fkey Lock  Off
 Feature Lock On
 KeyPad Numeric
 Xfer Term EOS
 Cursor Keys Normal
 Char Mode National
 Keys  Typewriter
 VT100 ID  VT-100
 Print  National
 Send  All
 Send Area  Scroll Rgn
 Print Area  Scroll Rgn
 Send Term  None
 Print Term  None
 Print Mode Bidirectional
 Auto Answerbk  On

FUNCTION KEY SETUP
None required – Performed by MXL
TABS SETUP
None required
ANSWERBACK SETUP
Do NOT alter data in this menu. Data is preset at factory. Altering this data results in VDT supervision errors.
CABLING REQUIREMENTS FOR AUXILIARY PORT TO PRINTER

LINK TERMINAL (Aux port) pinouts DB-9 cable| C. ITOH CI-2500 pinouts
DB-25 cable| TI-820KSR pinouts
DB-25 cable
---|---|---
2 RXD
1 DCD
3 TXD
4 DTR
5 GND
6 DSR
7 RTS
8 CTS| 2 Send Data
3 Receive Data
7 Signal Ground
11 Restraint| 8 Received line signal data
2 TXD
3 RXD
6 DSR
7 GND
20 DTR
5 CTS
4 RTS

RECOMMENDED PRINTER SETTINGS
Use the following factory tested settings for an unsupervised C. Itoh CI-2500 or Texas Instruments TI-820KSR printer used with an unsu-pervised VDT. (Refer to the corresponding printer operation manual for further information.)

C. ITOH CI-2500 PRINTER

Function No.| Menu No. Status
00 MODE
07 PRINTER ID
11 BUFFER
13 PW ON
14 DIRECTION
15 WRAPAROUND
17 AUTO CR
22 AUTO LF
23 CAN
32 GL, GO
35 G3
41 RAM AREA
81 OFF-LINE STATE
82 DSR
83 RTS TIMING
84 CD
85 CTS
91 OVER RUN
92 DATA BIT
93 PROTOCOL
94 STOP BIT
95 PARITY
96 BPS| 02 L (DEC EMULATION)
04 LEVEL 1
02 NORMAL
01 ON LINE
03 UNI-DIR
02 WRAP
01 CR + LF
02 CR + LF
01 NORMAL
01 US ASCII
01 US ASCII
01 DATA BUF
01 ALL RECEIVE
02 INVALID
02 BSY SYNC
02 INVALID
02 INVALID
01 20
02 TO AGREE WITH TERMINAL AUX
02 RDY/BSY2
01 TO AGREE WITH TERMINAL AUX
01 TO AGREE WITH TERMINAL AUX
01 TO AGREE WITH TERMINAL AUX
TEXAS INSTRUMENTS TI-820KSR PRINTER

Printer Settings (See Manual)| Print Configuration (Typical)
10
8
088
001
132
001
008| # characters per inch (16.5 CPI)
Line spacing (8 = single space 8 LPI)
Bottom margin line number (001-112)
Top margin line number (001-112)
Right margin column number (001-218)
Left margin column number (001-218)
Form length in lines (001-112)

TEXAS INSTRUMENTS TI-820KSR PRINTER

Printer Settings (See Manual) Communication Settings (Recommended)
83 Transmit DC3 or Break on Printer Busy, DC1 on ready
81 Enable recognition of device and format control commands from

communication line. (DFC option required.)
| Transmit space parity, reverse parity checkoff. Set to agree with terminal auxiliary port settings.
| Baud rate. Set to agree with terminal auxiliary port settings.
14| Full duplex reverse channel off ready (console mode.)

MXL-VDT QUICK REFERENCE GUIDE
To display the following guide on the VDT, or to print it out on a printer connected to the VDT, use either the HLP or Shift F1 command on the MXL-VDT.

ACKNOWLEDGEMENT AND AUDIBLE COMMANDS

MXL Menu Item| MXL
Command| XL3
Command| Programmed
Function Key| MXL Rev.
Effectivity
Acknowledge Alarm
Acknowledge Security

Acknowledge Supervisory
Acknowledge Trouble

Silence/Unsilence Audibles*| AAL
ASC
ASP
ATR
SUA| AA


AT| Fl
F5
F3
F4
F2| 2.12
2.12
2.12
2.12
2.12

  • Password level 1 or higher required to access this command.

ENTERING LIST COMMANDS FROM THE VDT

MXL Menu Item| MXL
Command| XL3
Command| Programmed
Function Key| MXL Rev.
Effectivity
List Alarms| LAL| LA| F7| 2.12
List Analog (analog2) Voltage| LVA m| LDO m| Shift F6| 2.12
List Device Type| LDT m| —| Shift F2| 2.12
List Messages| LMS m| —| Shift F3| 2.12
List Module Type| LSC| —| Shift F4| 2.12
List Security| LSS m| —| F10| 2.12
List Sensitivity Settings| LSV m| —| Shift F5| 2.12
List Sensitivity Voltages| LSW| LF m| Shift F7| 2.12
List Software Version| LSP| —| —| 2.12
List Status| LTV m| LS| F6| 2.12
List Supervisory| LTR| —| F8| 2.12
List Threshold Voltage| LCV m| —| Shift F8| 2.12
List Trouble| LIV m| LT| F9| 2.12
List Calibration Voltage| L2V m| LD 2| —| 6.04
List ID Voltage| LKP m| LD 3| —| 6.04
List 2nd ID Voltage| LAP m| LD 1| —| 6.04
List Smoke Percent Scale| LAT m| —| —| 6.06
List Airflow Percent Scale| LFT m| —| —| 6.06
List Alarm Trip Points| LPS m| —| —| 6.06
List Airflow Trip Points| LPP m| —| —| 6.06
List Percent/Ft Sensitivity| LPA m| —| —| 7.00
List Percent/Ft Pre-alarm| LAT m| —| —| 7.00
List Percent/Ft Analog|  LPA m| —| —| 7.00
List ASD Apps|  LPA m| —| —| 8.00
List Disarmed Output State| LOD m| —| —| 9.00
List Disarmed Input State| LID m| —| —| 9.00
List Modules in Commissioning Mode| LCM| —| —| 9.00

TDVEHTMORFSDNAMMOCLORTNOCGNIRETNE

MXL Menu Item| MXL
Command| XL3
Command| Programmed
Function Key| MXL Rev.
Effectivity
---|---|---|---|---
Charge (AmVdisarm) hpul Point’
m = module nunter
a = subaddress of input point
x = A-arm. D-disarm| CP m-d x| CO or COI
m-d x| Shift F9| 2.
Change Output Point’
m . module number
a = sibaddress of input point
x = A-arm. D-disarm
y = E-energize output, D-de-energize output| COP m-d x y| CO or COO
m-d x y| Shift F10| 2.
Charge Sensitivity’
m = module number
a = smoke detector subaddress
x = desired sensitivity setting
MXL Revisions before 3.0:
L-Low. M-Medium. N-Normal. H-High
MXL Revisions 3.0 and higher for ALD-21 smoke detectors:
0-Low3. 1-Low2. 2-Low3.
3-Normal. 4-Hi_1. 5-Hi_2. 6-Hi_3
MXL Revisions 6.04 and higher for XLD-1 smoke detectors:
2-Low1. 3-Normal, 4-Hi_1. 5-Hi_2| CSS m-d x| CS m-d x| Shift F12| 2.12
3.00
6.04
Log Off (cancel arrent password)| LOF| —| Shift F11| 2.
Log On (enter password)| LON| —| F11| 2.
Reset the MXL’| CRS| CR| F12| 2.
Control Alarm Trip Points CAT m-d p1 p2 aim
m = module number
a = device number
p1 = PreAlarm 1 trip point (0-9, 1=10% scale, 0=100% scale)
p2 = PreAlarm 2 trip point (0-9, 1.10% scale, 0.100% scale) aim = Alarm 1 trip point (0-9, 1.10% scale, 0=100% scale) Note: p1 <= p2 <=alm| —| —| 6.
Control Airflow Trip Points CFT m-d lo hi
m = module number
a = device number
lo = Low Airflow Trouble trip point (0-9, 1=10% scale. 0=100% scale) hi = High Airflow Trotble trip point (0-9, 1=10% scale, 0=100% scale) Note: hi-lo > 1| —| —| 6.
MXL Menu Item| MXL
Command| XL3
Command| Programmed
Function Key| MXL Rev.
Effectivity
---|---|---|---|---
Control Percent/Ft Sensitivity
in = module number
d = subaddress of smoke detector
x.x = desired sensitivity %/ft setting:
.5 – 4.0 %/ft — Photo; .6 – 1.7 %/ft — Ion| CPS m-d x.x| | | 7.00
Control Percent/Ft Pre-alarm
m = module number
d = subaddress of smoke detector
x.x = desired sensitivity %/ft setting:
.2 – 2.0 %/ft — Photo: .2 – 0.7 %/ft –Ion| CPP m-d x.x| | | 7.00
Control Change Apps
m = module number
d = device number
apps = abbreviation of ASD application
(Refer to Table 1. page 7, for applications abbreviations)| CAP m-d apps | —| | 8.00

  • Password level 1 or higher required to access this command.

SETTING THE TIME FROM THE VDT

MXL Menu Item| MXL Command| XL3 Command| MXL Rev. Effectivity
Change Time
It = 2-digit number of hours (24 hour format)
mm = 2-digit number of minutes
ss = 2-digit number of seconds
m = 2-digit month of the year
dd = 2-digit day of the month
yyyy = 4 digits of the year| CTD hh:mm:ss
nn-dd-yyyy| CT hh:mm:ss
nn-dd-yyyy| 2.12

  • Password level 2 or higher required to access this command.

ENTERING TEST COMMANDS FROM THE VDT

MXL Test Menu Items| MXL Command| MXL Rev. Effectivity
Device LED Control—
m . module number
d = subaddress device LED
x = E-energize LED, D-de-energize LED| DEV m-d x| 2.
Lamp Test of MKB-2—| LMP| 2.
M01-1 Lamp Test”
m = MOI module number| MLT m| 2.
Power Report—
m = PSR-1 or MMB module number| PWR m| 2.
Test LCD display on MKB-2″| LCD| 2.
MXL Revisions 3.0 and higher
History Status
Alarm History
Si.penAsory History Trouble History
Security History
All Event History
hh = start hour
mm = start minute
ss = start seconds
mm = start month
dd = start day
yyyy = start year| HST
HAL hh:mm:ss:mm-dd-yyyy
HSP hh:mm:ss:mm-dd-wyy
HTR hh:mm:ss:mm-dd-yyyy
HSC hh:mm:ss:mm-dd-my
HAE hh:mm:ss:mm-dd-ym| 3.0
XLD-1 PAX Lamp Test| XLT m| 6.
Test Pre-Alarm
m = module number
d = subaddress of smoke detector| PRE m-d| 7.0
Test ASD Devices| ASD| 8.0
Set Commissioning Mode for Module
m = module number
ON = activates commissioning mode
OFF = deactivates commissioning mode| SCM m (ON/OFF)| 9.0
Commissioning Mode Control| CMC| 9.0
History Manually Turned Off History Manually Turned On History Manually Armed/Disarmed History Manually Erased| HOF
HON
HAR
HER| 10.0

Password level 2 or higher required to access this command.
NOTE: The function keys are programmed into the MXL-VDT terminal at system power-up.
SIEMENS MXL VDT Interface Module Circuit Board - fig
1CAUTION:** This table refers to whether or not the wiring connections are supervised The table does not refer to the type of printer used in the System. SIEMENS MXL VDT Interface Module Circuit Board -
fig 2.NOTES:

  1. Terminals TB1-8 and 9 are connected together on the PIM-1.
  2. The busy signal from the printer prevents the loss of characters if the printer falls behind. Refer to the printer manual for the proper pin [usually 11 (TB1-3) or 20 (TB1-9)J.

Figure 1 PIM-1 Connection Diagram SIEMENS MXL VDT Interface Module
Circuit Board - fig 3

NOTES:

  1. Refer to PIM-1 Installation Instructions. PM 315-091462, for the connection to MXL.
  2. See PIM-1 to MXL-VDT Minimum Cabling Requirements table. page 11. for specific cabling requirements.
  3. AC power connection is 110 VAC, 60Hz.
  4. Maximum cable distance from PIM-1 (P3) to MXL-VDT is 25 feet. The modules and cable must be in the same room. 5. MXL-VDT auxiliary and parallel ports may be connected to UL-EDP listed printer which serves as an unsupervised ancillary device only.

Figure 2 MXL-VDT Installation Diagram
STANDBY POWER
The MXL-VDT requires a standby power source in the event of the loss of primary input power (AC mains.) Refer to Figure 3 below for the wiring diagram.
SIEMENS MXL VDT Interface Module Circuit Board - fig 4 NOTES:

  1. All wires 14 AWG min, 600V insulation.
  2. Wiring to the printer and PIM-1 must be 14 AWG min, 600V insulation in conduit
  3. Use the UPS ICS Lifeline Model 9300057.
  4. Standby Power Requirements: 120 VAC. 0.6A for 24 hours.
    Figure 3 MXL-VDT Standby Power Wiring Diagram

Siemens Building Technologies, Inc.
8 Fernwood Road Florham
Park, New Jersey 07932
P/N 315-091734-9
Siemens Building Technologies, Ltd.
2 Kenview Boulevard Brampton
Ontario L6T 5E4 CN
Technical Manuals Online! – http://www.tech-nian.com
firealarmresources.com

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals