HOCHIKI FNV 100 Voice Evacuation Interface System Instruction Manual
- June 9, 2024
- HOCHIKI
Table of Contents
- FNV 100 Voice Evacuation Interface System
- INSTALLATION
- TERMINAL DESIGNATIONS
- 6-32 wire clamp screw 14-18 AWG
- 8-32 wire clamp screw 12-18 AWG
- OPERATION
- SPECIFICATIONS:
- TYPICAL INSTALLATION
- CABINET LAYOUT
- OPTIONAL SUPERVISORY CIRCUIT APPLICATION
- MULTIPLE UNIT CONNECTION DETAIL
- SWITCH SETTINGS
- TROUBLE CODES
- END OF LINE RESISTORS
- References
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
FNV 25 / FNV 50 / FNV 100
VOICE EVACUATION INTERFACE SYSTEM
INSTALLATION INSTRUCTIONS
FNV 100 Voice Evacuation Interface System
The FNV 25/ FNV 50/FNV 100 is a self contained amplifier, tone generator,
digital message repeater and supervisory interface. It is designed to be used
in conjunction with a UL listed Fire Alarm Control Panel (FACP) to provide a
Listed Voice Evacuation Alarm System.
The FACP provides all initiating circuitry and a signaling circuit to the FNV
25/ FNV 50/ FNV 100. The FNV 25/ FNV 50 /FNV 100 provides its own internal
supervision as well as supervision for its speaker lines. Any fault is
reported back to the FACP. In normal standby the supervisory circuit from the
panel is connected to a matching OLR. Should the FNV 25/FNV 50 FNV 100 suffer
an internal failure or should there be any fault on the speaker line a contact
would open and the FACP would report it as an open fault for that circuit.
The FNV 25/ FNV 50 /FNV 100 is designed to be powered from 120 VAC at 60 Hz.
The FNV 25 will provide 25W to the speaker circuit. The FNV 50 will provide
50W The FNV 100 will provide 100W. . Speakers may be 25 or 70 VRMS (jumper
selected, 25 V is factory set).
INSTALLATION
Installer must insure that all wiring and devices installed in system meet the
following standards:
National Electrical Code (NFPA 70)
NFPA Standard 72
Life Safety Code (NFPA 101)
Install equipment in a clean, dry environment, avoid installation where
equipment could be subjected to vibration.
Remove electronic assemblies from the enclosure prior to any drilling or
punching of the enclosure. Where possible, make all cable entries from the
rear or sides. Before making any modifications to the enclosure, be certain
that they will not interfere with assemblies or batteries.
WIRING (Refer to wiring and terminal designation diagrams)
-
Connect speaker lines to TB1 – 5(+) & 6(-), observe polarity and insure all speakers are connected likewise.
For Class “A” (Style “Z”) the returns are TB1 – 7(-) & 8(+). -
Insure that the microphone is attached to connector P2. If Microphone is not installed insure that switch SN2 – 8 is in the OFF position.
-
Attach the appropriate EOLR for the FACP to TB3 – 3 & 4 and TB3 – 5 & 6. The TB3 term 5 & 6 value must be placed at the end of the speaker line as well. You must use EOLR value as specified in the FACP manufactures installation instructions for the indicating appliance circuit. Note: if your system includes one or more EVX-4Z zone splitters, the FACP EOLR is relocated. See EVX-4Z install instructions P/N 1-5010 Rev C.
-
Connect FACP signaling circuit to TB1 – 3(+) & 4(-), Alarm Polarity (alarm polarity is shown).
-
Connect 120 VAC, 60 Hz, power to the black and white pigtail leads from transformer primary.
Secure ground lead to grounding stud in cabinet. -
Once power is on to the unit, connect battery wiring harness, Red (+) / Black (-).Observe polarity. Minimum battery size is 24V 7AHr. Maximum battery size is 18Ahr on FNV 25 / 50 & 24Ahr on FNV 100. (use 2 12V batteries connected in series, see typical installation diagram). If the unit does not have its own batteries and relies on an external power supply with battery back-up, insure that switch SN2 – 7 is in the OFF position. NOTE: Wiring for batteries is Non Power-Limited.
Care must be taken to insure that all Power-Limited wiring maintain a minimum spacing of ¼” from any Non Power-Limited wiring. If batteries must be located in separate enclosure, provide separate conduit run for battery wiring only.
Once all power and circuits are connected, the Green LED will remain on to
indicate that the FNV 25/ FNV 50/
FNV 100 is fully operational and all circuits are nominal.
TERMINAL DESIGNATIONS
TB1:
TER 1 & 2 – Power Input 24-32V AC/DC (NOTE 1, 4)
TER 3 & 4 – FACP Signal Circuit Input – 10mA max. (Alarm Polarity shown) (NOTE
1, 4)
TER 5 & 6 – 25/70 VRMS Speaker Loop Style Y/Z (Class “A”/”B” start) (NOTE 2,
TB3:
TER 1 & 2 (NOTE 1, 4)
Optional FACP Supervisory Circuit (See installation instructions page 5
diagram 2 for details (32V – 0.4A max.)).
Factory set for none – J1 (installed)
TER 3 & 4
FACP Signal/Supervisory Circuit EOLR
TER 5 & 6
Matching EOLR for speaker supervisory circuit
TER 7 (NOTE 1, 3, 5)
General purpose output (pulls to circuit neg on fault condition
32V – 0.2A max). Not for Fire Protective Signaling use.
NOTES:
-
Intended for connection to
Listed Class 2 / Class 3 (Power
Limited) sources only. -
Power Limited
-
Non-Supervised
-
Supervised
-
Terminating equipment must be installed in same room as
Field wiring connections:
6-32 wire clamp screw 14-18 AWG
8-32 wire clamp screw 12-18 AWG
Horizontal wire entry terminal 18-26 AWG
Wire gauge determined by circuit load
TB2:
TER 1 – Circuit Neg
TER 2 (NOTE 1, 3) Aux Audio Input (0.5V nominal) (1VRMS – 1mA max.)
TER 3 (NOTE 1, 3, 5)
PreAmp In/Out (600 Ohm 0dBm)
TER 4 (NOTE 1, 3, 5) Master – Programmable +24VDC Active Slave – +24VDC
Input
TER 5 (NOTE 1, 3, 5) Signal Active Master – Out / Slave – In
TER 6 (NOTE 1, 3) Aux Audio Enable (+24V)(32V – 5mA max.)
TER 7 (NOTE 1, 3) Aux Signal Activate (+24V) (32V – 5mA max.)
TER 8 (NOTE 2, 3, 5) Alarm Voltage +24V when unit is in alarm condition
(0.1A)
TER 9 (NOTE 2, 3) Int V+ (+24V) disconnected in alarm condition (0.1A)
TER 10 (NOTE 2, 3) V+ (+24V 0.1A)
TER 11 (NOTE 5) Mic PTT (+24V 0.1A)
FACTORY DEFAULT SWITCH / JUMPER SETTINGS:
SN1
1 = OFF 8 sec. initial delay
2 = ON
3 = OFF
4 = ON 8 sec. repeat delay
5 = OFF
6 = ON Message On
7 = OFF 3 Repeats
8 = ON| SN2
1 = OFF Temporal Whoop Signal
2 = OFF
3 = OFF
4 = Fault Code Lock (default up (off))
5 = X Do not use (default up (off))
6 = AC Fault Delay
7 = ON Battery connected
8 = ON Mic connected| J1 A/B
1 – 2 = SHORT
J2
25 VRMS 2-3 = SHORT
70 VRMS 1-2 = SHORT
To change output voltage
move shorting block.
J5
1 + 2 SHORT = Ground Fault Enable
---|---|---
OPTIONS:
AUX +24VDC OUTPUT – TB2-4,8, 9 & 10
These terminals provide a max. 200 mA of regulated 24VDC power for auxiliary
functions. Do not exceed 200 mA load combined on these terminals. For
connection to Listed General Signal devices only (Non-Fire Protective
Signaling applications). Terminal 4 activation is programmed in the U6 ePROM
chip. Standard chips are programmed for TB2-4 to go active +24VDC under the
following conditions: Aux Signal Active, Aux Audio Enable, Bell Circuit
Active, RSI Active. Reprogramming of these functions must be done at the
factory and require replacing eprom U6.
CONNECTION OF AN AUX AUDIO SOURCE – TB2-1 & 2
An aux audio source from additional paging equipment may be connected to the
FNV 25/50/100 to augment an existing paging system. It is not intended for
continuous signal input, but may be used for paging applications. For such an
operation the Aux Audio Enable input, TB2-6, must be powered from Int V+,
TB2-9. This is to insure that in the event of an alarm, the aux audio will not
override the evacuation signal. See Wiring Diagram 5 for connection detail.
OPTIONAL SUPERVISORY CIRCUIT – TB3-1 & 2
In place of normal supervision via the signaling circuit, an alternate method
may be employed using any supervisory circuit from the FACP. Connection would
be made to Terminal Block 3, Ter. 1 and 2. This would provide a normally
closed connection to the EOLR on Ter. 3 and 4. The relay contact in the
circuit will open upon any trouble condition and report an open circuit
trouble to the FACP.
NOTE, jumper shorting blocks A and B must be removed from J1 if a circuit
is to be connected in this manner. See Optional Supervisory Circuit
Application (Wiring Diagram 2) for connection detail.
OPERATION
In normal standby the Green LED will remain on.
In alarm condition the Red LED will remain on as long as the unit is in alarm.
Green LED will also remain on.
Alarm Sequence Factory settings:
Alarm Tone – Alarm Signal 5 seconds / Digital Message plays / Alarm Signal 5
seconds / Digital Message plays / Alarm Signal 5 seconds / Digital Message
plays / unit reverts to Alarm Signal until alarm condition is cleared. If the
Mic is keyed it will override both the tone and the message so a direct
broadcast may be made. If this occurs during the initial sequence the digital
message will be reset and will not play.
When the Mic is keyed or when the message is played the Green LED will dim.
The intensity of the Green LED will vary with the level of the broadcast
audio. This is true in Alarm condition as well.
Under a fault condition, the Yellow LED will remain on. The Green LED will
flash. The number of flashes display a code depending on the specific type of
fault. When there is a fault condition the contact connecting the FACP signal
circuit to the EOLR will open indicating the fault to the panel which will
provide annunciation. During a ground fault condition, Yellow LED 4 will
illuminate.
SPECIFICATIONS:
Input Voltage
Input Current
Current (Battery)
Output power
Freq. Response
Output Voltage
*Optional 24 VDC input| FNV 25
120 VAC at 60 Hz
1.4 A @ 120 VAC
0.18 A Standby
1.0 AAlarm
0.31 A Standby w/Aux Load
25 Watt
800 – 2800 Hz
25/70 VRMS Selectable
0.6 A Standby
1.0 A Alarm
2.9 A Sine| FNV 50
120 VAC at 60 Hz
0.8 A @ 120 VAC
0.13 A Standby
1.0 AAlarm
0.26 A Standby w/Aux Load
50 Watt
400 – 4000 Hz
25/70 VRMS Selectable
0.6 A Standby
1.0 A Alarm
3.4 A Sine| FNV 100
120 VAC at 60 Hz
1.2 A @ 120 VAC
0.18 AStandby
2.60 AAlarm
1.20 Astandby w Aux load
100 Watt
400 – 4000 Hz
25/70 VRMS Selectable
0.18 A standby
2.50 A Alarm
6.4A Sine
---|---|---|---
Output Protection Power Limited, Open and Short Circuit protected
100 watt MODELS
The FNV-100 is a complete Voice Evacuation Module. It is not equipped with a
power transformer or a cabinet.
The FNV 100 is a complete Voice Evacuation Panel. It is equipped with a power
transformer and a cabinet.
The FNV-100E is a complete slave amplifier with built-in tone generator. It is
capable of operating as a slave amplifier when connected to the fFNV-100,
which supplies source audio to the slave. It is also capable of operating as a
stand-alone Voice Evacuation System with only tone and microphone
amplification.
Different Model numbers are derived from the amplifier sizes used together:
These multiple amplifier configurations are Factory setup and pre-wired. The
following are in their own cabinet with power transformers. They are complete
Panels.
FNV 100
FNV 150
FNV 200
FNV 100E
FNV 150E
FNV 200E| Contains: 1) FNV-100
Contains: 1) FNV-100 and 1) FNV-50E
Contains: 1)FNV-100 and 1) FNV-100E
Contains: 1) FNV-100E
Contains: 1) FNV-100E and 1) FNV-50E
Contains: 2) FNV-100E| 1) Speaker Circuit
2) Speaker Circuits
2) Speaker Circuits
- Speaker Circuit
- Speaker Circuits
- Speaker Circuits
---|---|---
*Input current measurements are determined by test conditions under UL 1711. Sine represents measurements made while unit produces a continuous non-distorted sine wave of 1 Khz into the rated load of 25/50/100W at rated output voltage. Alarm is the average current the unit experiences delivering an alarm signal, Temporal Whoop, to the rated load. Standby is the current draw of the unit with all normal power on and aux. terminals fully loaded. Battery Standby is current draw from the batteries on loss of power and otherwise normal standby.
TYPICAL INSTALLATION
CABINET LAYOUT
OPTIONAL SUPERVISORY CIRCUIT APPLICATION
ADDRESSABLE SYSTEM
APPLICATION
MULTIPLE UNIT CONNECTION DETAIL
AUX AUDIO ENABLE
CONNECTION DETAIL
SWITCH SETTINGS
SN2 Default = 0/0/0/0/0/0/1/1
SW 1/2/3 Sets the evac tone.
8 Settings: 0/0/0 Temporal slow whoop
1/0/0 Hi Lo
0/1/0 Horn
1/1/0 Bell
0/0/1 Empty
1/0/1 Chime
0/1/1 None
1/1/1 1kHz Sine
SW 4 Sets the diagnostics mode.
2 Settings: 0 Diagnostics off
1 Diagnostics on
SW 5 NA
SW 6 AC power failure report delay.
2 Settings: 0 No delay
1 6 hour delay
SW 7 Batteries.
2 Settings: 0 Batteries are not connected
1 Batteries are connected
SW 8 Microphone.
2 Settings: 0 Microphone is not connected| SN1 Default = 0/1/0/1/0/1/0/1
SW 1/2/3 Sets the initial delay before the message starts to play. Tone sounds
during delays.
8 Settings:
0/0/0 No delay
1/0/0 4 second delay
0/1/0 8 second delay
1/1/0 12 second delay
0/0/1 16 second delay
1/0/1 20 second delay
0/1/1 24 second delay
1/1/1 28 second delay
SW 4/5 Sets the delay between repeats of the message.
4 Settings:
0/0 4 second delay
0/1 8 second delay
1/0 12 second delay
1/1 16 second delay
SW 6 Sets the message play.
2 Settings: 0 Message off
1 Message on
SW 7/8 Sets the number of times the message plays.
4 Settings: 0/0 1 play
0/1 3 plays
1/0 2 plays
---|---
TROUBLE CODES
When a unit goes into a Trouble Condition, the Yellow LED wil remain on until
the trouble is cleared.
The Green LED will flash a Code to indicate the type of Trouble Condition.
There will be a pause between repeats of the code. When multiple Trouble
Conditions occur at the same time, the codes will add together.
The number of flashes and associated Trouble Condition are listed below.
Code | Trouble | Code | Trouble |
---|
1
2
4| Power Failure
Open Speaker Circuit
Shorted Speaker Circuit| 8
16
32| Amplifier Trouble
Microphone Trouble
Battery Trouble
- 6 flashes typically indicates “External Trouble”, such as an EVX-RM. If LED 4 is on, the 6 flash indicates a ground fault.
If both a ground fault condition and an external trouble occur simultaneously, the fault codes will not combine for 12 flash.
END OF LINE RESISTORS
NOTE 1: If the Fire Alarm Signal
Circuit requires a 4.7K end-of-line resistor, then R1 must be a 4.7K.
Normally, this resistor is connected to the Signal Circuit through a closed
Trouble contact. When the FNV 25/50/100 goes into Trouble, the contact opens,
producing an “Open” on that Signal Circuit, notifying the FACP.
NOTE 2: R2 and R3 must match each other. R2 “Sets” what the value of R3
needs to be. R2 tells the FNV 25/50/100 what to expect on the end of the
Speaker Circuit. If a Speaker EOLR (R3) already exists, simply match that
value for R2.
P/N H-5001 REV. F
7051 Village Drive, Suite 100
Buena Park, CA 90621-2268
800.845.6692 Technical Support
firealarmresources.com
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>