legrand LMPS-6000 Wattstopper DLM Skylight Photocell Instruction Manual
- June 9, 2024
- Legrand
Table of Contents
legrand LMPS-6000 Wattstopper DLM Skylight Photocell
This unit is pre-set for Plug n’ Go™ operation, adjustment is optional.
For full operational details, adjustment and more features of the product, see the DLM System Installation Guide provided with Wattstopper room controllers, and also available at www.legrand.us/wattstopper.
Installation shall be in accordance with all applicable regulations, local and
NEC codes. Wire connections shall be rated suitable for the wire size (lead
and building wiring) employed.
For Class 2 DLM devices and device wiring: To be connected to a Class 2 power
source only. Do not reclassify and install as Class 1, or Power and Lighting
Wiring.
SPECIFICATIONS
Footcandle range LMPS-6000 | 24 – 6000 fc |
---|---|
Calibration | None, controlled by system software |
Input voltage | 24VDC |
Sensor output | 1-10VDC |
Peak current | 4.5 mA Maximum |
Slew rate | 1 minute full scale response time filter |
Operating temperature | -40rF to 140rF (-40rC to 60rC) |
Wire color code
Red| .Input Voltage +24 VDC
Black| Input Return/Output Common
Yellow| 1-10VDC Output Signal
Housing| UV stabilized plastic with dome lens
Mounting| ½” NPT x .69″ stem
Overall dimensions| 2.55″L x 1.28″D
DESCRIPTION
The LMPS-6000 is a daylight sensor specifically designed to be used in conjunction with an LMIN-104 Digital Interface Module or LMIO-301 DLM Photocell Input Module. The LMIN-104/LMIO-301 converts the 10 VDC signal from the photocell sensor to a digital signal that is shared across the DLM Local Network. The signal is forwarded as a BACnet object via a DLM network bridge to the segment network for load control via a DLM segment manager or BACnet compatible Building Automation System (BAS).
INSTALLATION
Install the sensor on the side wall of the skylight well as shown in the Wiring diagram. The sensor housing is equipped with a ½” NPT nipple and will thread into any suitable box or fitting, or mount into a ½” knockout. This sensor is also suitable for use in atrium or clerestory applications where high sunlight levels are common.
WIRING
Connect the sensor to the LMIN-104 or LMIO-301 as shown.
DLM SYSTEM CONNECTION
MAINTENANCE
At least once every two months wipe the lens clean with a non-scratching clean cloth. Check the housing for damage, and be certain that no moisture has penetrated the sensor, as this will likely render it inoperable.
WARRANTY INFORMATION
Wattstopper warranties its products to be free of defects in materials and workmanship for a period of five (5) years. There are no obligations or liabilities on the part of Wattstopper for consequential damages arising out of, or in connection with, the use or performance of this product or other indirect damages with respect to loss of property, revenue or profit, or cost of removal, installation or reinstallation.
CUSTOMER SUPPORT
© Copyright 2022 Legrand All Rights Reserved
800.879.8585
www.legrand.us/wattstopper
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>