niko 353-650021 Presence Detector Instruction Manual

June 4, 2024
niko

Manual
Presence detector
353-650021
niko 353-650021 Presence Detector 4 Year warranty

Presence detector P46MR, DALI-2, secondary and BMS, 12-13 m, 360°, for flush- mounting box

Wiring
**** 230 V/DALI power – OFF

Secondary

niko 353-650021 Presence Detector - fig2

Dimensions

Installation

230 V/DALI power – OFF

Installatie

niko 353-650021 Presence Detector - fig1

niko 353-650021 Presence Detector - fig5| niko
353-650021 Presence Detector - fig6
---|---

App settings

230 V/DALI power – ON

| Sensitivity
---|---
Factory Settings| High

niko 353-650021 Presence Detector - fig8

Settings by BMS software

Table memory bank 2

Address Description Default value Memory type
0x00 Address and last accessible memory location 0x03 ROM
0x01 Indicator byte (manufacture definable) 0x00 any
0x02 60 mm

Memory bank lock byte (◇0x55 = Read Only else
Read/ Write)| 0xFF| RAM
0x03| 79 mm
PIR sensitivity segment A (MR, LR and HC detectors)
4 = MAX  3 = HIGH  2 = LOW  1 = MIN  0 = OFF| 0x03| NVM
0x04| PIR sensitivity segment B (LR and HC detectors)
4 = MAX  3 = HIGH  2 = LOW  1 = MIN   0 = OFF| 0x03| NVM
0x05| PIR sensitivity segment C (LR and HC detectors)
4 = MAX  3 = HIGH  2 = LOW  1 = MIN   0 = OFF| 0x03| NVM
0x06| LUX range
0 = NORMAL 0 – 1023 lux, 10-bit
1 = HIGH 0 – 10360 lux, 14 bit| | NVM

LED behavior

****230 V/DALI power – ON

Green LED continuously on| | Connection OK|
---|---|---|---
Green LED flashing| | Warming up| Wait
Red LED continuously on| | Error| More info –>
Blue LED flashing| | Walk test active

Detection area

niko 353-650021 Presence Detector - fig9

Troubleshooting

Problem Possible cause Proposed solution
Load does not turn on The wiring is not correct Check the wiring scheme
Load does not turn off The detector receives false triggers Check for any

objects that may cause false triggering and remove them from the detection range or lower the sensitivity
App cannot connect to
the detector| Bluetooth®  has been disabled on your mobile device| Enable Bluetooth®  on your mobile device

Specifications

Article number 353-650021
Configuration DALI-2 secondary/BMS
Input voltage via the DALI bus
Maximum current consumption 28.1 mA
Nominal current consumption (12 V, 25°C) 8.1 mA
Maximum startup time DALI < 1200 ms
Maximum PIR detection startup time 70 s
Light intensity range 0 – 10360 lux (see DALI BMS settings)
Detection angle 360°
Detection range (PIR) ø 12 m from a height of 3 m
Ambient temperature -25 – +40 °C
Mounting method flush-mounting box
Mounting height 2 – 3.5 m
Colour white (RAL 9010)
Dimensions visible (HxWxD) 100 x 100 x 9.5 mm
Dimensions (HxWxD) 100 x 100 x 44.5 mm
Wire capacity 1.5/2.5 mm²
Protection degree IP20
Impact resistance IK02
Modification of settings app (iOS/Android) and 2-way Bluetooth®

communication/BMS software
Maximum range Bluetooth®  (free field, depending on the device)| 50 m
Operating frequency| 2.4 GHz
Maximum radio frequency power|  -2 dBm
Halogen-free| yes
Marking| CE

Support & contact

nv Niko sa
Industriepark West 40
9100 Sint-Niklaas, Belgium
www.niko.eu
+32 3 778 90 80
support@niko.eu

Niko prepares its manuals with the greatest care and strives to make them as complete, correct and up to date as possible. Nevertheless, some deficiencies may subsist. Niko
cannot be held responsible for this, other than within the legal limits. Please inform us of any deficiencies in the manuals by contacting Niko customer services at support@niko.eu.

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals