FocusPRO® 5000 Series
Non-Programmable Digital
Thermostat
Installation Instructions
Wallplate installation
Remove the wallplate from the thermostat, then follow directions below for mounting.
- Remove battery holder.
- Pull here to remove wallplate from new thermostat.
- Pull wires through wire hole.
- Position wallplate on wall, level and mark hole positions with pencil.
- Drill holes at marked positions as shown below, then tap in supplied wall anchors.
- Place wallplate over anchors, insert and tighten mounting screws.
Power options
Wiring terminal designations
Shaded areas below apply only to TH5320U/TH5220D or as otherwise noted.
Conventional Terminals:
Rc 24VAC power from cooling transformer
R 24VAC power from heating transformer
W Heat relay (stage 1)
W2 Heat relay (stage 2)
Y Compressor contactor (stage 1)
Y2 Compressor contactor (stage 2)
G Fan relay
C 24VAC common. For 2 transformersystems, use common wire from cooling
transformer.
Heat Pump Terminals:
Rc 24VAC power from cooling transformer
R 24VAC power from heating transformer
O/B Changeover valve
Y Compressor contactor
Y2 Compressor contactor (stage 2) -TH5320U only
G Fan relay
Aux/E Auxiliary/Emergency heat relay
L Sends output when set to Em. Heat
C 24VAC common
Wiring conventional systems
Shaded areas below apply only to TH5320U/TH5220D or as otherwise noted.
1H/1C System (1 transformer)
Rc Power [1] R [R+Rc joined by jumper] Y Compressor contactor
C 24VAC common [3] W Heat relay
G Fan relay
Heat-only System
Rc Power [1] R [R+Rc joined by jumper] C 24VAC common [3] W
Heat relay
Heat-only System (Series 20) [5]
Rc [R+Rc joined by jumper] R Series 20 valve terminal “R” [1] Y
Series 20 valve terminal “W”
C 24VAC common [3] W Series 20 valve terminal “B”
Heat-only System (normally open zone valve) [5]
Rc [R+Rc joined by jumper] R Power [1] Y Normally open zone valve
C 24VAC common [3] 1H/1C System (2 transformers)
Rc Power (cooling transformer) [1, 2] R Power (heating transformer)
[1, 2] Y Compressor contactor
C 24VAC common [3, 4] W Heat relay
G Fan relay
Heat-only System with Fan
Rc Power [1] R [R+Rc joined by jumper] C 24VAC common [3] W
Heat relay
G Fan relay
Cool-only System
Rc Power [1] R [R+Rc joined by jumper] Y Compressor contactor
C 24VAC common [3] G Fan relay
2H/2C System (1 transformer) [6]
Rc Power [1] R [R+Rc joined by jumper] Y Compressor contactor
(stage 1)
C 24VAC common [3] W Heat relay (stage 1)
G Fan relay
W2 Heat relay (stage 2)
Y2 Compressor contactor (stage 2)
2H/2C System (2 transformers) [6]
Rc Power (cooling transformer) [1, 2] R Power (heating transformer)
[1, 2] Y Compressor contactor (stage 1)
C 24VAC common [3, 4] W Heat relay (stage 1)
G Fan relay
W2 Heat relay (stage 2)
Y2 Compressor contactor (stage 2)
NOTES
Wire specifications:
Use 18- to 22-gauge thermostat wire. Shielded cable is not required.
- Power supply. Provide disconnect means and overload protection as required.
- Remove jumper for 2-transformer systems.
- Optional 24VAC common connection.
- Common connection must come from cooling transformer.
- In Installer Setup, set system type to Heat Only.
- In Installer Setup, set system type to 2Heat/2Cool Conventional.
- In Installer Setup, set changeover valve to O or B.
- In Installer Setup, set system type to 2Heat/1Cool Heat Pump.
- n Installer Setup, set system type to 2Heat/2Cool Heat Pump.
- In Installer Setup, set system type to 3Heat/2Cool Heat Pump.
- L terminal sends a continuous output when thermostat is set to Em. Heat. Connect to Honeywell zoning panels to switch the panel to Emergency Heat.
Wiring heat pump systems
Shaded areas below apply only to TH5320U/TH5220D or as otherwise noted.
1H/1C Heat Pump System Rc Power [1] R [R+Rc joined by jumper] Y
Compressor contactor
C 24VAC common [3] O/B Changeover valve [7] G Fan relay
2H/1C Heat Pump System (TH5220D only) [8]
E Rc Power [1] R [R+Rc joined by jumper] Y Compressor contactor
C 24VAC common [3] O/B Changeover valve [7] G Fan relay
Aux/E Auxiliary/Emergency heat relay
L Sends output when set to Em. Heat [11] 2H/1C Heat Pump System
(TH5320U only) [8]
Rc Power [1] R [R+Rc joined by jumper] Y Compressor contactor
C 24VAC common [3] O/B Changeover valve [7] G Fan relay
Aux/E Auxiliary/Emergency heat relay
L Sends output when set to Em. Heat [11] 2H/2C Heat Pump System
(TH5320U only) [9]
Rc Power [1] R [R+Rc joined by jumper] Y Compressor contactor
(stage 1)
C 24VAC common [3] O/B Changeover valve [7] G Fan relay
Y2 Compressor contactor (stage 2)
L Sends output when set to Em. Heat [11] 3H/2C Heat Pump System
(TH5320U only) [10]
Rc Power [1] R [R+Rc joined by jumper] Y Compressor contactor (stage
- C 24VAC common [3] O/B Changeover valve [7] G Fan relay
Aux/E Auxiliary/Emergency heat relay
Y2 Compressor contactor (stage 2)
L Sends output when set to Em. Heat [11] See Notes on page 3.
Thermostat mounting
- Push excess wire back into the wall opening.
- Plug wall opening with nonflammable insulation.
- Align the 4 tabs on the wallplate with corresponding slots on the back of the thermostat.
- Push gently until the thermostat snaps in place.
Installer setup
Follow the procedure below to configure the thermostat to match the installed heating/cooling system, and customize feature operation as desired.
- To begin, press and hold the and FAN buttons until the display changes.
- Press or to change settings.
- Press NEXT to advance to next function.
- Press DONE to exit and save settings.
Setup function Settings & options (factory default in bold)
Shaded areas below apply only to TH5320U/TH5220D or as otherwise noted.
1 System type | 0 | 1 heat/1 cool conventional |
---|---|---|
1 | 1 heat/1 cool heat pump (no aux. heat) | |
2 | Heat only — 2-wire systems, 3-wire zone valves (Series 20),and normally |
open zone valves
3| Heat only with fan
4| Cool only
5| 2 heat/1 cool heat pump (with aux. heat)
6| 2 heat/2 cool conventional
7| 2 heat/1 cool conventional
8| 1 heat/2 cool conventional
9| 2 heat/2 cool heat pump (no aux. heat) – TH5320U only
10| 3 heat/2 cool heat pump (with aux. heat) – TH5320U only
2 Changeover valve (O/B terminal)| 0| Changeover valve (O/B terminal
energized in cooling)
---|---|---
1| Changeover valve (O/B terminal energized in heating)
3 Fan control (heating)| 0| Gas or oil furnace — equipment controls fan in
heating
1| Electric furnace — thermostat controls fan in heating
5 Stage 1 heat cycle rate
(CPH: cycles/hour)| 5| For gas or oil furnaces of less than 90% efficiency
1| For steam or gravity systems
3| For hot water systems & furnaces of over 90% efficiency
9| For electric furnaces
6 Stage 2 heat cycle rate/Auxiliary heat
cycle rate (CPH)| 5| For gas or oil furnaces of less than 90% efficiency
1| For steam or gravity systems
3| For hot water systems & furnaces of over 90% efficiency
9| For electric furnaces
7 Auxiliary heat cycle rate (CPH)*
Only TH5320U for 3H/2C Heat
Pumps| 5| For gas or oil furnaces of less than 90% efficiency
1| For steam or gravity systems
3| For hot water systems & furnaces of over 90% efficiency
9| For electric furnaces
*[Other cycle rate options: 2, 4, 6, 7, 8, 10, 11 or 12 CPH] Setup
function Settings & options (factory default in bold)
Shaded areas below apply only to TH5320U/TH5220D or as otherwise noted.
9 Stage 1 compressor cycle rate (CPH)| 3| Recommended for most compressors
[Other cycle rate options: 1, 2, 4, 5 or 6 CPH]
---|---|---
10 Stage 2 compressor cycle rate (CPH)| 3| Recommended for most compressors
[Other cycle rate options: 1, 2, 4, 5 or 6 CPH]
12 Manual/Auto changeover| 0| Manual changeover (Heat/Cool/Off)
1| Auto changeover (Heat/Cool/Auto/Off)
2| Auto changeover only (Auto)
14 Temperature display| 0| Fahrenheit
1| Celsius
15 Compressor protection| 5| Five-minute compressor off time
[Other options: 0, 1, 2, 3 or 4-minute off time]
26 Auxiliary heat control| 0| Comfort
1| Economy
27 Heat temperature range stops| 90| Max. heat temperature setting is 90 °F
(32 °C)
[Other options: 40 °F to 89 °F (4.5 °C to 31.5 °C)]
28 Cool temperature range stops| 50| Min. cool temperature setting is 50 °F
(10 °C)
[Other options: 51 °F to 99 °F (10.5 °C to 37 °C)]
Special function
Auxiliary heat control (Setup Function 26):
Comfort Setting: The thermostat will prioritize comfort over economy
depending on heat pump performance, load conditions and whether the thermostat
is calling for the heat pump. Raising the temperature just a few degrees will
often activate the auxiliary heat.
Economy Setting: The thermostat will attempt to reach the temperature
setting without activating the auxiliary heat. The thermostat will wait to
activate the auxiliary heat depending on heat pump performance, load
conditions and how many degrees the temperature setting is changed.
Installer system test
- To begin, press and hold the and t buttons until the display changes.
- Press / to turn system on/off.
- Press NEXT to advance to next test
- Press DONE to terminate system test.
System test System status
Shaded areas below apply only to TH5320U/TH5220D or as otherwise noted.
10 Heating system | 0 | Heat and fan turn off. |
---|---|---|
1 | Stage 1 heat turns on. Fan turns on if Setup Function 1 is |
set to 1, 5, 9 or 10 OR Setup Function 3 is set to 1
2| Stage 2 heat turns on
3| Stage 3 heat turns on – TH5320U only
20 Emergency heating system| 0| Heat and fan turn off
1| Heat and fan turn on
30 Cooling system| 0| Compressor and fan turn off
1| Compressor and fan turn on
2| Stage 2 compressor turns on
40 Fan system| 0| Fan turns off
1| Fan turns on
Specifications
Temperature Ranges
Heat: 40° to 90°F (4.5° to 32°C)
Cool: 50° to 99°F (10° to 37°C)
Operating Ambient Temperature
32° to 120°F (0° to 48.9°C)
Shipping Temperature
-20° to 120°F (-28.9° to 48.9°C)
Operating Relative Humidity
5% to 90% (non-condensing)
Physical Dimensions
TH5220D
3-9/16” H x 5-13/16” W x 1-1/2” D
91 mm H x 147 mm W x 38 mm D
TH5220D
3-7/16” H x 4-1/2” W x 1-5/16” D
86 mm H x 114 mm W x 33 mm D
Electrical Ratings
Terminal | Voltage (50/60Hz) | Running Current |
---|---|---|
W Heating | 20-30 Vac | 0.02-1.0 A |
(Powerpile) | 750 mV DC | 100 mA DC |
W2 (Aux/E) Heating | 20-30 Vac | 0.02-1.0 A |
Y Cooling | 20-30 Vac | 0.02-1.0 A |
Y2 Cooling | 20-30 Vac | 0.02-1.0 A |
G Fan | 20-30 Vac | 0.02-0.5 A |
O/B Changeover | 20-30 Vac | 0.02-0.5 A |
L Output | 20-30 Vac | 0.02-0.5 A |
Customer assistance
For assistance with this product, please visit customer.honeywell.com.
Or call Honeywell Customer Care tollfree at
1-800-468-1502.
CAUTION:
EQUIPMENT DAMAGE HAZARD
Compressor protection is bypassed during testing. To prevent equipment damage,
avoid cycling the compressor quickly.
CAUTION:
ELECTRICAL HAZARD
Can cause electrical shock or equipment damage. Disconnect power before
beginning installation.
CAUTION:
MERCURY NOTICE
If this product is replacing a control that contains mercury in a sealed tube,
do not place the old control in the trash. Contact your local waste management
authority for
instructions regarding recycling and proper disposal.
Automation and Control Solutions
Honeywell International Inc.
1985 Douglas Drive North
Golden Valley, MN 55422
Honeywell Ltd
705 Montrichard Avenue
Saint-Jean-sur-Richelieu, Québec
J2X 5K8
customer.honeywell.com
® U.S. Registered Trademark.
© 2013 Honeywell International Inc.
69-2698EFS—03 M.S. Rev. 07-13
Printed in U.S.A.
Documents / Resources
|
Honeywell FocusPRO 5000 Series Non-Programmable Digital
Thermostat
[pdf] User Manual
FocusPRO 5000 Series Non-Programmable Digital Thermostat, FocusPRO 5000
Series, Non-Programmable Digital Thermostat, Digital Thermostat
---|---
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>