Honeywell PRO3000 Series Non-Programmable Digital Thermostat Instruction Manual

June 9, 2024
Honeywell

Honeywell PRO3000 Series Non-Programmable Digital Thermostat

Wallplate installation

Remove the wall plate from the thermostat by pulling from the bottom, then follow directions below for mounting.

  1. Pull wires through wire hole.
  2. Position wall plate on wall, level and mark hole positions with pencil.
  3. Drill holes at marked positions as shown below, then tap in supplied wall anchors.
  4. Place wall plate over anchors, insert and tighten mounting screws.Honeywell PRO3000 Series Non-Programmable Digital Thermostat 2

Power options

Honeywell PRO3000 Series Non-Programmable Digital Thermostat
3

Wiring terminal designations

TH3110D

  • C 24 Vac common. For 2 transformer systems, use common wire from cooling transformer.
  • B Changeover valve energized in heating
  • R 24 Vac power from heating transformer
  • Rc 24 Vac power from cooling transformer
  • O Changeover valve energized in cooling
  • G Fan relay
  • Y Compressor contactor
  • W Heat relay

TH3210D

  • C  24 Vac common
  • B Changeover valve energized in heating
  • R 24 Vac power
  • L Sends output when set to Em.
  • O Heat Changeover valve energized in cooling
  • G Fan relay
  • Y Compressor contactor
  • Aux Auxiliary heat relay
  • E Emergency heat relay

2H/1C Heat Pump System TH3210D

  • C 24 Vac common [3]
  • B Changeover valve energized in heating [5]
  • R Power [1]
  • L Sends output when set to Em. Heat [8]
  • O Changeover valve energized in cooling [5]
  • G Fan relay
  • Y Compressor contactor
  • Aux Auxiliary heat relay
  • E Emergency heat relay

1H/1C System TH3110D (1 transformer)

  • C 24 Vac common [3]
  • R [R+Rc joined by jumper]
  • Rc Power [1]
  • G Fan relay
  • Y Compressor contactor
  • W Heat relay

1H/1C System TH3110D (2 transformers)

  • C 24 Vac common [3, 4]
  • R Power (heating transformer) [1, 2]
  • Rc Power (cooling transformer) [1, 2]
  • G Fan relay
  • Y Compressor contactor
  • W Heat relay

1H/1C Heat Pump System TH3110D [7]

  • C 24 Vac common [3]
  • B Changeover valve energized in heating [5]
  • R [R+Rc joined by jumper]
  • Rc Power [1]
  • O Changeover valve energized in cooling [5]
  • G Fan relay
  • Y Compressor contactor [6]
  • W [W+Y joined by jumper]

Heat Only System TH3110D

  • C 24 Vac common [3]
  • R [R+Rc joined by jumper]
  • Rc Power [1]
  • W Heat relay

Heat Only System with Fan TH3110D

  • C 24 Vac common [3]
  • R [R+Rc joined by jumper]
  • Rc Power [1]
  • G Fan relay
  • W Heat relay

Cool Only System TH3110D

  • C 24 Vac common [3]
  • R [R+Rc joined by jumper]
  • Rc Power [1]
  • G Fan relay
  • Y Compressor contactor

NOTES
Wire specifications:
Use 18- to 22-gauge thermostat wire. Shielded cable is not required.

  1. Power supply. Provide disconnect means and overload protection as required.

  2. Remove jumper for 2-transformer systems.

  3. Optional 24 Vac common connection.

  4. Common connection must come from cooling transformer.

  5. Use either O or B terminals for changeover valve.

  6. Use a small piece of wire (not supplied) to connect W and Y terminals.

  7. Set fan operation switch to Heat Pump (see page 5) and configure system type for heat pump (see page 6).

  8. L terminal sends a continuous output when thermostat is set to Em. Heat. Connect
    to Honeywell zoning panels to switch the panel to Emergency Heat.

  9. Install field jumper between Aux and E if there is no emergency heat relay.

Fan operation settings

(TH3110D only)
Gas or Oil: For gas or oil heating systems, leave the fan operation switch in this factory-set position. (This setting is for systems that control the fan in a call for heat.)
Electric or Heat Pump: Change the switch to this setting for heat pump or electric heat systems. (This setting is for systems that allow the thermostat to control the fan in a call for heat, if a fan wire is connected to the G terminal.)

Thermostat mounting

  1. Align the 4 tabs on the wall plate with corresponding slots on the back of the thermostat.
  2. Push gently until the thermostat snaps in place.
  3. Push excess wire back into the wall opening.
  4. Plug wall opening with non-flammable insulation.

Installer Setup

Follow the procedure below to configure the thermostat to match the installed heating/cooling system, and customize feature operation as desired.
To begin, press and hold the s and t buttons until the display changes.

  1. Press t to change settings.
  2. Press s to advance to next function.
  3. Press and hold ts to exit and save settings.
    Honeywell PRO3000 Series Non-Programmable Digital Thermostat
17

Compressor Protection (Setup Function 15) : Forces the compressor to wait a few minutes before restarting, to prevent damage. During the wait time, the message Cool On or Heat On (heat pumps only) will flash on the display.

Installer system test
  1. Set SYSTEM switch to Heat.
  2. Press t to turn on and check systems (see table, below).
  3. Press t until systems turn off.
  4. Set SYSTEM switch to Em Heat and repeat steps 2-3 above (TH3210D only).
  5. Set SYSTEM switch to Cool and repeat steps 2-3 above.
  6. Press and hold ts to terminate test at any time.
    Honeywell PRO3000 Series Non-Programmable Digital Thermostat
18

Troubleshooting

If you have difficulty with your thermostat, please try the following suggestions. Most problems can be corrected quickly and easily.

Display is blank

  • Check circuit breaker and reset if necessary.
  • Make sure power switch at heating & cooling system is on.
  • Make sure furnace door is closed securely.
  • Make sure fresh AA alkaline batteries are correctly installed (see page 2).

Heating or cooling system does not respond

  • Set system switch to Heat. Make sure the temperature is set higher than the Inside temperature.
  • Set system switch to Cool. Make sure the temperature is set lower than the Inside temperature.
  • Wait 5 minutes for the system to respond.

Temperature settings do not change

  • Make sure heating and cooling temperatures are set to acceptable ranges:
    • Heat: 40° to 90°F (4.5° to 32°C).
    • Cool: 50° to 99°F (10° to 37°C).

“Cool On” or “Heat On” is flashing

  • Compressor protection feature is engaged. Wait 5 minutes for the system to restart safely, without damage to the compressor.

“Heat On” is not displayed

  • Set the System switch to Heat, and set the temperature level above the current room temperature.

“Cool On” is not displayed

  • Set the System switch to Cool, and set the temperature level below the current room temperature.

Specifications

  • Temperature Ranges
    • Heat: 40° to 90°F (4.5° to 32°C)
    • Cool: 50° to 99°F (10° to 37°C)
  • Operating Ambient Temperature
    • 32° to 120°F (0° to 48.9°C)
  • Shipping Temperature
    • -20° to 120°F (-28.9° to 48.9°C)
  • Operating Relative Humidity
    • 5% to 90% (non-condensing)
  • Physical Dimensions
    • 3-13/16” H x 5-3/8” W x 1-1/4” D
    • 97 mm H x 137 mm W x 32 mm D

Electrical Ratings
System                     Voltage (50/60Hz)           Running Current

  • Heat (1st stage)            20-30 Vac                        0.02-1.0 A
  • (Power pile)                  750 mV DC                    100 mA DC
  • Emergency heat            20-30 Vac                        0.02-1.0 A
  • Auxiliary heat                20-30 Vac                        0.02-1.0 A
  • Cooling                          20-30 Vac                        0.02-1.0 A

Need Help?
For assistance with this product, please visit customer.honeywell.com.
Or call Honeywell Customer Care toll-free at 1-800-468-1502. CAUTION:
EQUIPMENT DAMAGE HAZARD
Compressor protection is bypassed during testing. To prevent equipment damage, avoid cycling the compressor quickly.
CAUTION:
ELECTRICAL HAZARD
Can cause electrical shock or equipment damage. Disconnect power before beginning installation.
CAUTION:
MERCURY NOTICE
If this product is replacing a control that contains mercury in a sealed tube, do not place the old control in the trash. Contact your local waste management authority for instructions regarding recycling and proper disposal.
Automation and Control Solutions
Honeywell International Inc.
1985 Douglas Drive North
Golden Valley, MN 55422 customer.honeywell.com
® U.S. Registered Trademark.
© 2013 Honeywell International Inc.
69-1929EFS—03 M.S. Rev. 04-13
Printed in U.S.A.

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Honeywell User Manuals

Related Manuals