Honeywell SD500-SDM Two-Wire Smoke Module Instructions

June 9, 2024
Honeywell

Honeywell logoHoneywell SD500-LED LED Driver Module logo
1 SD500-SDM Two-Wire Smoke Module
InstructionsHoneywell SD500-SDM Two-Wire Smoke
Module Converts a conventional
smoke loop to an SLC loop.

SD500-SDM Two-Wire Smoke Module

SSDD550000–SSDDMM
Two–Wire Smoke Module
The SD500-SDM allows you to assign an address to a loop of conventional detection devices. These devices can be dry contacts such as pull stations and heat detectors, or 2-wire smoke detectors. This means you can retrofit an existing building and utilize existing conventional devices. The SD500SDM uses a 24VDC auxiliary power input to power the conventional loop, and is connected to the SLC loop via two wires. The conventional loop can be configured as Class A or Class B giving you the flexibility to handle any job.

Features

  • Converts a conventional two-wire loop to an SLC loop
  • Fully supervised
  • Compatible with Class B (Style 4) and Class A (Style 6) loops
  • Listed for use with most major two-wire detectors
  • UL Listed

Specifications

Operating Voltage:

SLC:| 32 VDC
Aux Power:| 24 VDC
Aux.Power Current:
Standby:| 20 mA
Alarm:| 106 mA
SLC Current:
Alarm/Standby:| .55 mA
Max. SLC Loop Resistance:| 50Ω
Max. 2-Wire Conventional Smoke
Loop Resistance:| 50Ω
Dimensions:
Length:| 4-7/8”
Width:| 4-7/8”
Depth:| 7/8”
Operating Temperature:| 32ºF to 120ºF (0ºC to 49ºC)
Humidity:| 10 to 85% RH

Indoor Use Only

Dimensions

Honeywell SD500-SDM Two-Wire Smoke Module - fig 1 Connections to FACPHoneywell SD500-SDM Two-Wire Smoke Module - fig
2

Honeywell SD500-SDM Two-Wire Smoke Module - fig 3

7550 Meridian Circle
Maple Grove, Mn 55369-4927
612-493-6455
1-800-328-0103
Fax: 612-493-7475
P/N 350235, 01/00
Copyright © 2000 Silent Knight
firealarmresources.com