Honeywell 5000 Series Thermostat Instruction Manual

June 9, 2024
Honeywell

Honeywell 5000 Series Thermostat

INSTALLER SYSTEM TEST

FocusPRO®5000 Series
  1. To begin, press and hold the ▲ and ▼ buttons until the display changes.
    Installer System Test

  2. Press ▲/▼ to turn system on/off
    Installer System Test

  3. Press NEXT to advance to next test.

  4. Press DONE to terminate system test.

  5. Proceed to Installer System Tests on page 8.

FocusPRO® 6000 Series
  1. To begin, press and hold the ▲ and ▼ buttons until the display changes
    Installer System Test

  2. Press▲/▼t to turn system on/off.
    Installer System Test

  3. Press NEXT to advance to next test.

  4. Press DONE to terminate system test.

  5. Proceed to Installer System Tests on page 8.

INSTALLER SYSTEM TESTS

Test the system’s heating, emergency heat, cooling, and fan.
Available tests vary by thermostat and system type

Table 2. Installer System Test


System Test Number| Test Type| System Status Number and Description
10| Heating system|

  1. Heat and fan off
  2. First stage heat on (Fan turns on if Setup Function 1 is set to 1, 5, 9, or 10 OR setup Function 3 is set to 1)
  3. Second stage heat o
  4. Third stage heat on

20| Emergency heating system|

  1. Heat and fan off
  2. Heat and fan on
  3. Second stage heat (Aux. heat) turns on

30| Cooling system|

  1. Compressor and fan off
  2. Compressor and fan on
  3. Second stage compressor on

40| Fan system|

  1. Off
  2. On

CAUTION
EQUIPMENT DAMAGE HAZARD.
Compressor protection is bypassed during testing.
To prevent equipment damage, avoid cycling the compressor quickly

INSTALLER SETUP

FocusPRO® 5000 Series
  1. To begin, press and hold the ▲ and FAN buttons until the display changes.
    Installer Setup

  2. Press ▲ or ▼to change settings
    Installer Setup

  3. Press NEXT to advance to the next function.

  4. Press DONE to exit and save settings.

  5. Proceed to Installer Setup Functions on page 4.

FocusPRO® 6000 Series
  1. To begin, press and hold the ▲ and FAN buttons until the display changes.
    Installer Setup

  2. Press ▲ or ▲ to change settings.
    Installer Setup

  3. Press NEXT to advance to the next function.

  4. Press DONE to exit and save settings.

  5. Proceed to Installer Setup Functions on page 4.

Table 1. Installer Setup


Setup functions| Setting & Options (factory default in bold)
1| System type|

  1. 1 heat / 1 cool Conv. 1 1 heat / 1 cool heat pump (no Aux. heat)
  2. Heat only (2-wire, 3-wire zone valves [Series 20], and normally open zone valves)
  3. Heat only with fan
  4. Cool only
  5. 2 heat / 1 cool heat pump (with Aux. heat)
  6. 2 heat / 2 cool Conv.
  7. 2 heat / 1 cool Conv.
  8. 1 heat / 2 cool Conv.
  9. 2 heat / 2 cool heat pump (no Aux. heat)
  10. 3 heat / 2 cool heat pump (with Aux. heat)

2| Changeover valve (O/B terminal)|

  1. Controls valve in cooling
  2. Controls valve in heating

3| Fan control (heating)| 0 Gas/Oil heat (equipment controls heating fan) 1 Electric furnace (thermostat controls heating fan)
5| First stage heat cycle rate| 5 Gas or oil furnaces of less than 90% efficiency

1 Steam or gravity
3 Hot water systems or furnaces of 90%+ efficiency
9 Electric furnaces [Other options: 1–12]

6| Second stage heat/Aux heat cycle rate| 5 Gas or oil furnaces of less than 90% efficiency
1 Steam or gravity
3 Hot water systems or furnaces of 90%+ efficiency
9 Electric furnaces [Other options: 1–12]
7| Auxiliary heat cycle rate| 5 Gas or oil furnaces of less than 90% efficiency
1 Steam or gravity
3 Hot water systems or furnaces of 90%+ efficiency
9 Electric furnaces [Other options: 1–12]
8| Emergency heat cycle rate| 9 Electric emergency heat
1 Steam or gravity
3 Hot water systems or furnaces of 90%+ efficiency
5 Gas or oil furnaces of less than 90% efficiency [Other options: 1–12]
---|---|---
9| First stage compressor cycle rate| 3 Recommended [Other options: 1–6
10| Second stage compressor cycle rate| 3 Recommended [Other options: 1–6]
12| Manual/Auto changeover| 0 Manual changeover (Heat/Cool/Off)
1 Auto changeover (Heat/ Cool/Auto/Off)
2 Auto changeover only (Auto)
13| Adaptive Intelligent Recovery TM| 1 On
0 Of
14| Temperature display| 0 Fahrenheit
1 Celsius
15| Compressor protection| 5 5-minute compressor off time
[Other options: 0–4 minutes]
16| Schedule format| 0 5/2 (weekdays and weekends programmable)
1 5/1/1 (weekdays, Saturday, and Sunday programmable)
26| Auxiliary heat control| 0 Comfort
1 Economy
27| Heat temperature range stops| 90 Max. heat temperature setting is 90°F (32°C)
[Other options: 40–89°F (4.5°C to 32°C)]
28| Cool temperature range stop| 50 Min. cool temperature setting is 50°F (10°C)
[Other options: 51–99°F (10.5°C to 37°C)]

Functions 13 and 16 only available on the 6000 series; function 26 only available on the 5000 series

Printed in U.S.A. on recycled paper containing at least 10% post-consumer paper fibers.

Automation and Control Solutions
Honeywell International Inc. 1985 Douglas Drive North Golden Valley, MN 55422

Honeywell Limited-Honeywell Limited
35 Dynamic Drive Toronto, Ontario M1V 4Z9
http://yourhome.honeywell.com

® U.S. Registered Trademark
© 2006 Honeywell International Inc.
US Patent No. 6595430, D509151; other
Patents Pending. All Rights Reserved 69-2026 M.S. 09-06

Documents / Resources

| Honeywell 5000 Series Thermostat [pdf] Instruction Manual
5000 Series Thermostat, 5000 Series, Thermostat
---|---

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Honeywell User Manuals

Related Manuals