POTTER SR-SFG Waterflow Alarm Switch with Glue In Union Owner’s Manual
- June 9, 2024
- POTTER
Table of Contents
POTTER SR-SFG Waterflow Alarm Switch with Glue In Union Owner’s Manual
-
Stock No. 1113555 1113600 W/TSK
-
Service Use:
Automatic Sprinkler NFPA-13
One or two family dwelling NFPA-13D
Residential occupancy up to four stories NFPA-13R
National Fire Alarm Code NFPA-72 -
CUL, UL and CSFM Listed, CE Marked, NYMEA ACCEPTED
-
Service Pressure:
Up to 175 PSI (12,07 BAR) -
Minimum Flow Rate for Alarm:
8-10 GPM (30-38 LPM) -
Maximum Surge:
18 FPS (5,5 m/s) -
Enclosure :
Die-cast, red powdercoat fi nish -
No. 1113555:
Cover held in place with tamper resistant screws -
No. 1113600 –
Tamper: Cover incorporates micro-switch.
Cover Tamper: Activated by cover removal.
Cover Tamper SwitchContacts: One set SPDT, Rated at 250VAC.
Cover Tamper Switch Terminations: 8″ 22AWG wire leads. -
Contact Ratings:
Two sets of SPDT (Form C) 15.0 Amps at 125/250 VAC 2.0 Amps at 30 VDC -
Conduit Entrances:
Two knockouts provided for 1/2″ conduit. -
Usage:
Listed CPVC plastic piping systems manufactured by Central Sprinkler Corp., Grinnell Sprinkler Corp., Spears Manufacturing Co., and IPEX (Scepter).
Fits pipe sizes – 1″, 1-1/4″, 1-1/2″ and 2″ -
Environmental Specifi cations:
- Suitable for indoor or outdoor use with factory installed gasket and die-cast housing.
- For NEMA 4/IP55 rated enclosure – use with appropriate conduit fi tting and/or plugs.
- Temperature range: 40° F to 120° F (4,5° C to 49° C)
-
Caution:
This device is not intended for applications in explosive environments
The Model VSR-SFG is a vane type waterfl ow switch for use on wet sprinkler systems using CPVC plastic fi ttings manufactured by Central Sprinkler Corp., Grinnell Sprinkler Corp., Spears Manufacturing Co., and IPEX (Scepter) that use 1″, 1-1/4″, 1-1/2″ or 2″ pipe sizes. It is equipped with a union to accommodate installation in confi ned spaces.
The unit contains two single pole double throw snap action switches and an adjustable, instantly recycling pneumatic retard. The switches are actuated when a fl ow of 8-10 gallons per minute (30-38 liters per minute) or more occurs downstream of the device. The fl ow condition must exist for a period of time necessary to overcome the selected retard period.
INSTALLATION: These devices may be mounted on horizontal or vertical pipe. On horizontal pipe they should be installed on the top side of the pipe where they will be accessible. The units should not be installed within 6″ (15 cm) of a valve, drain or fi tting which changes the direction of the waterfl ow. The unit has a 1″ male fi tting for gluing into a CPVC plastic TEE.
Loosen the union nut and separate the 1″ male fi tting from the VSR-SFG. Glue the 1″ male fi tting into the TEE following the TEE manufacturer’s instructions for preparation and gluing of CPVC piping systems. (NOTE: The 1″ male fi tting must bottom out on the stop of the TEE for proper operation of the VSR-SFG. See Fig. 1.) Wait 2 to 4 hours to allow the glue to dry before attaching the VSR-SFG to the 1″ male fi tting. Select the proper paddle for the pipe size and type of TEE used. See Fig. 3 and Fig. 5 for instructions on how to change paddle. Verify that the o-ring is properly positioned in its groove. Hand tighten the nut on the union after orienting thedevice in the appropriate direction to detect waterfl ow as shown in Fig. 2.
CAUTION: Do not over-tighten the union nut, hand tighten only!
The vane must not rub the inside of the TEE or bind in any way. The stem should move freely when operated by hand.
INSPECTION AND TESTING : Check the operation of the unit by opening the inspector’s test valve at the end of the sprinkler line or the drain and test connection, if an inspector’s test valve is not provided.
If there are no provisions for testing the operation of the fl ow detection device on the system, application of the VSR-SFG is not recommended or advisable.
The frequency of the inspection and testing and its associated protective monitoring system should be in accordance with the applicable NFPA Codes and Standards and/or authority having jurisdiction (manufacturer recommends quarterly or more frequently).
Fitting Instructions
Glue the 1″ male fitting into the TEE following the TEE manufacturer’s instructions for preparation and gluing of CPVC piping systems. Wait 2 to 4 hours to allow the glue to dry before attaching the VSR-SFG to the 1″ male fitting.
Retard Adjustment
To change time, turn knob (either direction) for desired time delay. Use the minimum amount of retard necessary to prevent false alarms. A “B” setting is usually adequate for this. Factory set at “B”
APPROX. RETARD SETTINGS (IN SEC.)
0| A| B| C| D| E
0| 10-25| 20-40| 35-55| 50-70| 60-90
Shown with optional Cover Tamper Switch Kit
Important
7 paddles are furnished with each unit to accommodate the various sizes and
manufacturers of TEES. The paddles have raised lettering that show the pipe
size and the TEE manufacturer they are to be used with. The proper paddle must
be used. The paddle must be properly attached (see Fig. 3) and the screw that
holds the paddle must be securely tightened.
TYPICAL ELECTRICAL CONNECTIONS
2 SETS OF NORMALLY OPEN CONTACTS CLOSE ON ALARM
THE N.C. AND N.O. MARKINGS ON THE SWITCH ARE FOR AN ALARM CONDITION
THE CONTACTS ARE REVERSED WHEN THE DEVICE IS IN THE NORMAL CONDITION.
NOTES
- The model VSR-SFG has two switches, one can be used to operate a central station, proprietary or remote signaling unit, while the other is used to operate a local audible or visual annunciator.
- For supervised circuits see “Switch Terminal Connections” drawing and caution note (Fig. 6)
COVER TAMPER SWITCH
**(SHOWN WITH COVER IN PLACE)
**
GRINNELL TEE
NOTICE:
As of 5/99 Grinnell has changed the design of their TEE fi ttings. The new
fi ttings will require the use of the standard paddle, while you will still be
required to use the paddle marked Grinnell on all fi ttings manufactured prior
to this date. Failure to install the correct paddle could cause the device to
malfunction or operate improperly
TEE’s manufactured prior
TEE’s manufactured
SWITCH TERMINAL CONNECTIONS CLAMPING PLATE TERMINAL
APPLICATION WARNING!
Due to the possibility of unintended discharges caused by pressure surges,
trapped air, or short retard times, waterfl ow switches that are monitoring
wet pipe sprinkler systems should not be used as the sole initiating device to
discharge AFFF, deluge, or chemical suppression systems.
Support
Potter Electric Signal Company
- 2081 Craig Road, St. Louis, MO, 63146-4161
- Phone: 800-325-3936/Canada 888-882-1833
- www.pottersignal.com
PRINTED IN USA
MKT. #8800009 – REV P
MFG. #5401062 – 11/05