POTTER DSD-P Conventional Duct Smoke Detector Owner’s Manual
- June 9, 2024
- POTTER
Table of Contents
POTTER DSD-P Conventional Duct Smoke Detector Owner’s Manual
Features
- Detect and limit the spread of smoke throughout building HVAC ducts
- Compatible with building automation and fire alarm system
- Installs quickly and easily – Duct Housing Cover does not need to be removed before installation to duct
- Interchangeable “Plug-In” photoelectric or ionization heads
- No screens or filters to clean
- Cover provides magnet window and placement guide for go/no-go operational testing with out disassembly
- Rugged gray steel back box with clear cover
- Accessories – Remote power, remote alarm indication capability and remote, horn/piezo capability
- Meets UL 268A Requirements
Application
The Potter Electric DSD-P duct smoke detector provides early detection of
smoke and products of combustion present in air moving through HVAC ducts in
commercial, industrial and residential applications.
The DSD is designed to prevent the recirculation of smoke in areas by the air
handling systems, fans and blowers.
Complete systems may be shut down in the event of smoke detection.
The DSD-P operates on 115 VAC, 24 VAC and 24 VDC.
Product Description
The DSD-Pis designed and built to meet all local requirements, as well as the
NFPA regulations regarding duct smoke detectors.
Output terminals are provided for remote accessories such as a horn, strobe,
remote status indicators and reset key switches or push buttons.
Air sampling is accomplished by two tubes which protrude into the duct.
An exhaust tube of one standard length (7.5″) is supplied in the installation
kit with the smoke duct unit.
Once the duct width has been determined the air intake sampling tubes must be
ordered.
Sampling tubes are supplied in three standard lengths 2.5 ft., 5 ft. and 10
ft. and cut to size to fit the duct.
Mounting the duct smoke unit is accomplished by the use of a template and 4
sheet metal screws, which are provided.
Mounting can be achieved without the removal of the clear cover which is
secured by 4 capture screws.
The compact DSD contains 3 sets of alarm contacts, 1 set of form “C” contacts
rated at 10 amps, 1 set of form “A” contacts rated at 10 amps, 1 set of form
“A” contacts rated at 1 amp.
There is also 1 set of form “C” 10 amp trouble contacts for monitoring
detector head removal, and the failure of the input supply voltage.
The pilot and alarm visual indicators provided on the front of the DSD duct
unit, signal the operating status of the device.
A manual test/reset switch is located along side the visual indicators.
This switch can be defeated by cutting a jumper on the PCB.
Duct Detector Model # | DSD-P |
---|---|
Operating Voltage | 115V AC, 24V C/DC |
Detector Head Model | SLR-24DH |
Detector Head Type | Conventional Photoelectric |
Power Requirements Standby | 230 VAC |
115 VAC | 14mA |
24 VAC | 20mA |
24 VDC | 13mA |
Power Requirements Alarm | 230VAC |
115 VAC | 28mA |
24 VAC | 95mA |
24 VDC | 60mA |
Alarm Contacts | 1 form “C” and 1 form “A” rated at 10 amps at 115 VAC |
Detection Loop | 1 form A (1A) |
Trouble Contacts | 1 form “C” |
Sensitivity Test Method | Self diagnostic test |
Remote Indication Capability (Refer to DSD Accessories Data Sheet for
Specifications)| Power, Alarm, Horn, Piezo, Test
Air Velocity| 300 to 4000 ft./min
Ambient Temperature| 32°F to 120°F (0°C to 49°C)
Humidity| 10% to 85% Relative humidity (non- condensing)
Housing Material| 18 G.A. steel backbox, clear plastic cover
Finish| Grey paint
Dimensions| 9 1/8″L x 7 1/4″ W x 2 1/4″ H
Maximum Net Weight| 3 lbs.
Sampling Tubes| 2.5 ft., 5 ft., or 10 ft.
Radioactive Element| DSD-I only: Americium 24I 0.5 micro-curie
Engineering Specifications
Air duct smoke detectors shall be Potter Electric DSD Series.
The detectors shall be listed by Underwriters Laboratories per UL 268A.
The detectors shall operate at air velocities from 300 feet per minute to 4000
feet per minute.
The duct detector housings shall be of metal construction and complete
mechanical installation may be performed without removal of detector cover.
Visual indication of alarm and power must be provided on detector front.
A manual reset switch shall be located on front of the device.
Detector heads shall not require additional filters or screens which must be
maintained.
The housing shall contain a detector base which will accept photoelectric or
ionization detector heads.
Terminal connections shall be of the screw type and be a minimum of # 6 screw.
Terminals shall be provided for remote pilot, remote alarm indication,
strobe/horn and remote key switch.
All wiring must comply with local codes and regulations.
Wiring Diagrams
CUSTOMER SUPPORT
Potter Electric Signal Company
St. Louis, MO, 63042
Phone: 866-956-1211/Canada
888-882-1833
Web: www.pottersignal.com