POTTER LED-16 LED Annunciator Instruction Manual
- June 9, 2024
- POTTER
Table of Contents
POTTER LED-16 LED Annunciator Instruction Manual
NOTICE TO THE INSTALLER
This manual provides an overview and the installation instructions for the LED-16 module.
All terminals are power limited and should be wired in accordance with the requirements of NFPA 70 (NEC) and NFPA 72 (National Fire Alarm Code). Failure to follow the wiring diagrams in the following pages will cause the system to not operate as intended. For further information, refer to the control panel installation instructions.
The module shall only be installed with listed control panels. Refer to the control panel installation manual for proper system operation.
Description
The LED-16 is a LED remote annunciator. LED-16 communicates using a RS-485 connection to the main panel providing zone specific indication of Alarm Supervisory, and Trouble conditions. The module mounts on either a 4″ square or double gang box.
The LED-16 features 2 slide-in labels allowing each of the 16 zones to be customized for any application. It can be mounted on a single gang electrical box or a four-square electrical box. The annunciator utilizes a sheet metal enclosure secured with a Potter lock
Setting the Address
Each P-Link device has a five (5) position dip switch which is used to program the device address ranging from one (1) to thirty-one (31). The table below may be used to set dip switches when addressing any P-Link module:
Figure 1. Dip Switch Settings Table (Addresses 1–31)
Note: Each “gray” box indicates that the dip switch is “On,” and each “white” box indicates “Off.”
The examples shown below illustrate a P-Link’s dip switch settings: the 1st example shows a P-Link module not addressed where all dip switch settings are in the default “Off” position, the 2nd illustrates an addressed P-Link module via the dip switch settings.
Figure 2. Examples of P-Link Module Showing Default Dip Switch Setting (Unaddressed) & Addressed
All dip switches are shown in the “Off” position.
Example shows this P-Link module address = 10. Dip switches #2 & 8 are in the “On” position.
Before connecting a device to the RS-485, take the following precautions to prevent potential damage to the RS-485 connection or P-Link or device.
INSTALLATION MANUAL: LED-16 LED ANNUNCIATOR
- Power to the LED-16 is removed.
- Field wiring on module is correctly installed.
- Field wiring has no open or short circuits.
Technical Specifications
- P-Link Alarm Current: 25 mA
- P-Link Standby Current: 25 mA
- LED PWR Maximum Standby Current: 15 mA
- LED PWR Alarm Current: 210 mA
- Operating Temperature Range: 32°F to 120°F (0°C to 49°C)
- Maximum # of Annunciators: 31
- Dimensions (WxHxD): 10″x7 7/8″x1 5/8″
- Operating Humidity Range: 10%-93% (non-condensing)
- Maximum Wire Length: 6500 ft
- Wire Gauge: 12 AWG to 18 AWG
Note: LED PWR can be provided by any fire listed source. Output power must be 16 VDC – 33 VDC and must be power limited.
Installation
The LED-16 is connected to the fire alarm control panel using a four wire RS-485 connection. The connection is power limited and supervised. Up to 31 LED-16 LED annunciators can be connected. Refer to the illustrations below for a front panel and board view.
Wiring Diagram
The following wiring diagrams illustrate how to wire a LED-16 to Control Panel or Auxiliary Power.
Figure 4. Wiring LED-16 to Control Panel or Auxiliary Power Example
Notes:
-
RS-485 supports the Class A, and Class B.
-
RS-485 connection is power limited and supervised.
-
All wiring is between #12 (max.) and #18 (min.).
-
Wire Preparation – Strip all wires 1/4 inch from their edges as shown here:
- Stripping too much insulation may cause a ground fault.
- Stripping too little may cause a poor connection and subsequently an open circuit.
These instructions do not purport to cover all the details or variations in the equipment described, nor provide for every possible contingency to be met in connection with installation, operation and maintenance.
Specifications subject to change without prior notification.
For Technical Assistance contact Potter Electric Signal Company at 866-956-1211.
Actual performance is based on proper application of the product by a qualified professional.
Should further information be desired or should particular problems arise, which are not covered sufficiently for the purchaser’s purpose, the matter should be referred to a distributor in your region.
Potter Electric Signal Company, LLC
St. Louis, MO
Phone: 800-325-3936
www.pottersignal.com
References
- Fire Alarm Resources | Download fire alarm documents
- Potter Electric: Fire Alarms & Fire Sprinkler Systems
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>