Mircom D4120 Innovairflex 4 Wire Photoelectric Duct Detector
Description
The InnovairFlex D4120 4-wire photoelectric duct smoke detector features a
pivoting housing that fits both square and rectangular footprints and mounts to
round or rectangular ductwork. This unit senses smoke in the most challenging
conditions, operating in airflow speeds of 100 to 4,000 feet per minute,
temperatures of –4°F to 158°F, and a humidity range of 0 to 95 percent (non-
condensing). A plug-in sensor head offers improved false alarm immunity and
simple installation, testing, and maintenance. An improved cover design
isolates the sensor head from the low-flow feature for simple maintenance. The
InnovairFlex housing provides ample wiring space, a ¾-inch conduit knockout,
and built-in short circuit protection to prevent damage to sensitive
components during installation. High contrast terminal designations make
wiring easy. With its 2:1 sensor-to-power capability, the power board of the
D4120 may be used to monitor a second sensor, D4S, simultaneously (i.e.,
supply and return side). As many as 50 InnovairFlex detectors can be
interconnected. When one unit senses smoke, all interconnected detectors will
switch their relays; only the detector sensing smoke will go into alarm, thus
pinpointing the fire source. An easy-access Test/Reset button makes it possible
to test the unit with the cover on. Three DIP switches can be used to configure
field selectable settings: cover tamper delay, number of sensors to be
controlled, and shut down on trouble option. Each power board has two LEDs
that can be used to indicate the status of connected sensors, and a quick
reference imprinted on the cover explains the LED status indications (Standby,
Maintenance, Trouble, and Alarm). The InnovairFlex duct smoke detector can be
customized to meet local codes and specifications without additional wiring.
The new InnovairFlex product line is compatible with all previous Innovair
models, including remote test accessories.
WARNING: Duct smoke detectors have specific limitations.
DUCT SMOKE DETECTORS ARE:
- NOT a substitute for an open area smoke detector,
- NOT a substitute for early warning detection, and
- NOT a replacement for a building’s regular fire detection system. Refer to NFPA 72, 90A and CAN/ULC S524 for additional duct smoke detector application information.
Features
- Photoelectric, integrated low-flow technology
- Air velocity rating from 100 ft/min to 4,000 ft/min (0.5 m/s to 20.32 m/sec)
- Versatile mounting options in square or rectangular configuration with modular construction
- Plug-in sensor offers superb false alarm immunity and the latest sensor technology
- Broad ranges for operating temperature (-4ºF to 158ºF) and humidity (0% to 95% non-condensing)
- Patented sampling tube installs from front or back of the detector with no tools required
- Increased wiring space with a newly added ¾ inch conduit knockout
- One easy-access Test/Reset button and improved LED status
- Patented interconnect feature for multi-fan shutdown
- New high contrast terminal designations
- Built-in short circuit protection from operator wiring errors
- Field selectable settings for configuring the detector
- Two DPDT Form-C relay contacts
- 24 VAC/DC or 120 VAC
- Backward compatibility with existing Innovair products, including remote accessories
Architectural/Engineering Specifications
The air duct smoke detector shall be a System Sensor InnovairFlex™ D4120(A) Photoelectric Duct Smoke Detector. The detector housing shall be UL listed per UL 268A or ULC listed specifically for use in air handling systems. The flexible housing of the duct smoke detector fits both square and rectangular footprints. The detector shall operate at air velocities of 100 ft/min to 4000 ft/min (0.5 m/sec to 20.32 m/sec). The unit shall be capable of controlling up to 50 air handling systems when interconnected with other detectors. The detector shall be capable of providing a trouble signal in the event that the front cover is removed. It shall be capable of local testing via magnetic switch or remote testing using the RTS451KEY(A) remote test station. Terminal connections shall be of the strip and clamp method suitable for 12–18 AWG wiring.
Wiring for 4-wire Duct Smoke Detector and Accessories
NOTE 1: 24V Power Inputs accept a non-polarized 24VDC or 24VAC 50-60Hz.
120VAC Power Inputs accept only 120VAC 50-60Hz. Connect power source to
appropriate terminals of each detector. See specifications for additional power
supply information.
NOTE 2: Auxiliary contacts shown in standby position. Contacts switch
during alarm as indicated by arrows. Auxiliary contacts are not to be used for
connection to the control panel. See specifications for contact ratings.
NOTE 3: Supervisory contacts shown in standby position. Open contacts
indicate a trouble condition to the panel. See specifications for contact
ratings.
NOTE 4: Alarm Initiation contacts shown in standby position. Closed
contacts indicate an alarm condition to the panel. See specifications for
contact ratings.
*Please refer to the corresponding installation manual for accessory wiring diagrams.
Accessory Current Loads at 24 VDC
Device| Standby| Alarm
RA100Z| 0 mA| 12 mA Max.
RTS151| 0 mA| 12 mA Max.
RTS151KEY| 12 mA| 12 mA Max.
Electrical Ratings
Power supply voltage:| 20–29 VDC| 24 VAC 50–60 Hz| 120 VAC 50–60 Hz
Input capacitance:| 270 μF max.| 270 μF max.| N/A
Reset voltage:| 3.0 VDC min.| 2.0 VAC min.| 10 VAC min.
Reset time: (with RTS451)| .03 to 0.3 sec.| .03 to 0.3 sec.| .03 to 0.3 sec.
Reset time: (by power down)| 0.6 sec. max.| 0.6 sec. max.| 0.6 sec. max.
Power up time:| 35 sec. max.| 35 sec. max.| 35 sec. max.
Alarm response time:| 15 sec.| 15 sec.| 15 sec.
Sensitivity Test:| See detector label| See detector label| See detector label
Current Requirements: (Using No Accessories)
Max. standby current:| 21 mA @ 24VDC| 65 mA RMS @ 24VAC 60Hz| 20 mA RMS @
120VAC 60Hz
Max. alarm current:| 65 mA @ 24VDC| 135 mA RMS @ 24VAC 60Hz| 35 mA RMS @
120VAC 60Hz
Physical Specifications
Size: (Rectangular)| 14.38 in (37 cm) Length; 5 in (12.7 cm) Width;
2.5 in (6.36 cm) Depth
Size: (Square)| 7.75 in (19.7 cm) Length; 9 in (22.9 cm) Width; 2.5 in
(6.35 cm) Depth
Weight:| 2.5 lb (1.14 kg)
Operating Temp. Range:| D4120 & D4S: -4°F to 158°F (-20°C to
70°C)
D4P120: -40°F to 158°F ) -40C° to 70°C)
Storage Temp. Range:| D4120 & D4S: –22°F to 158°F (–30° to 70°C)
D4P120: -40°F to 158°F ) -40C° to 70°C)
Operating Humidity Range:| 0% to 95% relative humidity non-condensing
Air Duct Velocity:| 100 to 4000 ft/min (0.5 to 20.32 m/sec)
Contact Ratings
Alarm initiation contacts: (SPST)| 2.0A @ 30 VDC (resistive)
Alarm auxiliary
contacts: (DPDT)
| 10A @ 30 VDC (resistive); 10A @ 250 VAC (resistive);
½ HP @ 240 VAC ; ¼ HP @ 120 VAC
Note: Alarm auxiliary contacts shall not be connected to initiating circuits of control panels. Use the alarm initiation contact for this purpose.
Supervisory contacts: (SPDT)| 2.0A @ 30 VDC (resistive); 2.0A @ 125 VAC
(resistive)
Model| Description
---|---
D4120| 4-wire photoelectric low-flow duct smoke detector
Accessories
D4S| 4-wire photoelectric sensor component only
D4P120| 4-wire photoelectric power board component only, 24 VAC/DC, 120 VAC
2D51| 4-wire conventional photoelectric sensor head
DST1| Metal sampling tube duct width up to 1ft (0.3m)
DST1.5| Metal sampling tube duct widths 1 ft to 2 ft (0.3 to 0.6 m)
DST3| Metal sampling tube duct widths 2 ft to 4 ft (0.6 to 1.2 m)
DST5| Metal sampling tube duct widths 4 ft to 8 ft (1.2 to 2.4 m)
DST10| Metal sampling tube duct widths 8 ft to 12 ft (2.4 to 3.7 m)
ETX| Metal exhaust tube duct width 1ft (0.3m)
RA-100Z| Remote annunciator alarm LED
RTS151| Remote test station
RTS151KEY| Remote test station with key lock
Canada
25 Interchange Way Vaughan, Ontario L4K 5W3 Telephone:
905-660-4655 Fax:
905-660-4113
U.S.A.
4575 Witmer Industrial Estates Niagara Falls, NY 14305 Toll Free:
888-660-4655 Fax Toll Free:
888-660-4113
Web page: http://www.mircom.com
Email: mail@mircom.com
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>