Mircom MIX-M500RAP Relay Control Module Instruction Manual
- June 9, 2024
- Mircom
Table of Contents
INSTALLATION AND MAINTENANCE INSTRUCTIONS
25 Interchange Way, Vaughan Ontario, L4K 5W3
Phone: 905.660.4655; Fax: 905.660.4113
MIX-M500RAP Relay Control Module
Specifications
Normal Operating Voltage: | 15 to 32 VDC |
---|---|
Maximum Alarm Current: | 6.5mA (LED on) |
Average Operating Current: | 300 µA, 1 communication every 5 seconds |
EOL Resistance: | Not used |
Temperature Range: | 32˚F to 120˚F (0˚C to 49˚C) |
Humidity: | 10% to 93% Non-condensing |
Dimensions: 4 | 4½˝ H x 4˝ W x 1 ¼˝ D (Mounts to a 4˝ square by 2 ¹⁄8˝ deep |
box.)
Accessories:| SMB500 Electrical Box; CB500 Barrier
BEFORE INSTALLING
This information is included as a quick reference installation guide. Refer to
the control panel installation manual for detailed system information. If the
modules will be installed in an existing operational system, inform the
operator and local authority that the system will be temporarily out of
service.
Disconnect power to the control panel before installing the modules.
NOTICE: This manual should be left with the owner/user of this equipment.
GENERAL DESCRIPTION
The MIX-M500RAP Relay Control Module is intended for use in intelligent, two-
wire systems, where the individual address of each module is selected using
the built-in rotary decade switches. It allows a compatible control panel to
switch discrete contacts by code command. The relay contains two isolated sets
of Form-C contacts, which operate as a DPDT switch and are rated in accordance
with the table in the manual. Circuit connections to the relay contacts are
not supervised by the module.
The module also has a panel controlled LED indicator.
COMPATIBILITY REQUIREMENTS
To ensure proper operation, these modules shall be connected to listed
compatible system control panels only.
MOUNTING
The MIX-M500RAP mounts directly to 4˝ square electrical boxes (see Figure 2A).
The box must have a minimum depth of 2 /8˝. Surface mounted electrical boxes
(SMB500) are available from System Sensor.
WARING
NOTE: All wiring must conform to applicable local codes, ordinances, and
regulations. When using control modules in non power limited applications, the
System Sensor CB500 Module Barrier must be used to meet UL requirements for
the separation of power-limited and non power-limited terminals and wiring.
The barrier must be inserted into a 4˝x4˝x21/8˝ junction box, and the control
module must be placed into the barrier and attached to the junction box
(Figure 2A). the power-limited wiring must be placed into the isolated
quadrant of the module barrier (Figure 2B).
- Install module wiring in accordance with the job draw sings and appropriate wiring diagrams.
- Set the address on the module per job drawings.
- Secure module to electrical box (supplied by installer), as shown in Figure 2A.
RELAT CONTACT RATINGS:
CURRENT RATINg| MAXIMUM VOLTAgE| LOAD DESCRIPTION|
APPLICATION
---|---|---|---
3:00 AM| 30 VDC| Resistive| Non-coded
2:00 AM| 30 VDC| Resistive| Coded
0.46 A| 30 VDC| (L/R= 20ms)| Non-coded
0.9 A| 125 VDC| Resistive| Non-coded
0.5 A| 125VAC| (PF=0.75)| Non-coded
0.3 A| 125 VAC| (PF=0.35)| Non-coded
0.7 A| 70.7 VAC| (PF=0.35)| Non-coded
0.2 A| 25 VAC| (PF=0.35)| Non-coded
WARNING
All relay switch contacts are shipped in the standby (open) state, but may
have transferred to the activated (closed) state during shipping. To ensure
that the switch contacts are in their correct state, modules must be made to
communicate with the panel before connecting circuits controlled by the
module.
FIGURE 3. RELAY MODULE WIRING DIAGRAM:
*NOTE: ANY FAULT IN THE POWER SUPPLY IS LIMITED TO THAT ZONE AND DOES NOT RESULT IN A FAULT IN A SEPARATE ZONE.
MC-460-011 2 I56-3317-000