Mircom MIX-2351TAPA Advanced Protocol Intelligent Photoelectric and Temperature Sensors Installation Guide
- June 9, 2024
- Mircom
Table of Contents
Mircom MIX-2351TAPA Advanced Protocol Intelligent Photoelectric and
Temperature Sensors
SPECIFICATIONS
- Operating Voltage Range: 15 to 32 VDC
- Operating Current @ 24 VDC: 200 uA (one communication every 5 seconds with green LED blink on communication)
- Maximum Alarm Current: 2 mA @ 24 VDC (one communication every 5 seconds with red LED solid on)
- Maximum Current: 4.5 mA @ 24 VDC (one communication every 5 seconds with amber LED solid on)
- Operating Humidity Range: 10% to 93% Relative Humidity, Non-condensing
- Operating Temperature Range: 32°F to 115°F (0°C to 47°C)
- Air Velocity: 0 to 4000 ft./min. (0 to 1219.2 m/min.)
- Height: 2.0˝ (51 mm) installed in B300A-6 Base
- Diameter: 6.2˝ (156 mm) installed in B300A-6 Base; 4.1˝ (104 mm) installed in B501A Base
- Weight: 3.4 oz. (95 g)
- Isolator Load Rating: 0.0063*
Please refer to your isolator base/module manual for isolator calculation instructions.
CAN/ULC S529 listed for Open Air Protection
CAN/ULC S530 listed for Heat Detectors
This sensor must be installed in compliance with the control panel system
installation manual. The installation must meet the requirements of the
Authority Having Jurisdiction (AHJ). Sensors offer maximum performance when
installed in compliance with CAN/ULC S524.
GENERAL DESCRIPTION
Model MIX-2351TAPA is a plug-in type multi-sensor smoke sensor that combines a photo electronic sensing chamber and 135°F (57.2°C) fixed temperature heat detector across addressable-analog communications. The sensors transmit an analog representation of smoke density over a communication line to a control panel. Rotary dial switches are provided for setting the sensor’s address. (See Figure 1.) The intelligent photoelectric and temperature sensors also transmit an alarm signal due to heat at 135°F (57.2°C) per CAN/ULC S530.
An output is provided for connection to an optional remote LED annunciator
(P/N RA100ZA).
Mircom panels offer different features sets across different models. As a
result, certain features of the photoelectric and temperature sensors may be
available on some control panels, but not on others. MIX-2351TAPA supports
Advanced Protocol and CLIP (Classic Loop Interface Protocol) mode.
The possible features available if supported by the control panel are:
- The sensor’s LEDs can operate in three ways—on, off, and blinking–and they can be set to red, green, or amber. This is controlled by the panel.
- The remote output may be synchronized to the LED operation or controlled independent of the LEDs.
- Devices are point addressable up to 159 addresses.
Please refer to the operation manual for the ULC listed control panel for specific operation. The photoelectric and temperature sensors require compatible addressable communications to function properly. Connect these sensors to listed-compatible control panels only.
SPACING
Mircom recommends spacing sensors in compliance with CAN/ULC S524. In low air
flow applications with smooth ceilings, space sensors 30 feet apart (9.1 m).
When using the photoelectric and temperature sensors as a heat detector in
FM3210 compliant applications, space sensors 20 feet apart (6 m). For specific
information regarding sensor spacing, placement, and special applications,
refer to CAN/ULC S524 or the System Smoke Detector Application Guide,
available from Mircom.
WIRING GUIDE
All wiring must be installed in compliance with the Canadian Electrical Code, applicable local codes, and any special requirements of the Authority Having Jurisdiction. Proper wire gauges should be used. The installation wires should be color-coded to limit wiring mistakes and ease system troubleshooting. Improper connections will prevent a system from responding properly in the event of a fire.
Remove power from the communication line before installing sensors.
- Wire the sensor base (supplied separately) per the wiring diagram, Figure 2.
- Set the desired address on the sensor address switches, see Figure 1.
- Install the sensor into the sensor base. Push the sensor into the base while turning it clockwise to secure it in place.
- After all sensors have been installed, apply power to the control panel and activate the communication line.
- Test the sensor(s) as described in the TESTING section of this manual.
CAUTION
Dust covers provide limited protection against airborne dust particles during
shipping. Dust covers must be removed before the sensors can sense smoke.
Remove sensors prior to heavy remodeling or construction.
CAUTION: Do not loop wire under terminal 1 or 2. Break wire run to supervise connections.
TAMPER-RESISTANCE
Photoelectric and temperature sensors include a tamper-resistant capability
that prevents removal from the base without the use of a tool. Refer to the
base manual for details on making use of this capability.
TESTING
Before testing, notify the proper authorities that the system is undergoing
maintenance, and will temporarily be out of service. Disable the system to
prevent unwanted alarms.
All sensors must be tested after installation and periodically thereafter.
Testing methods must satisfy the Authority Having Jurisdiction (AHJ). Sensors
offer maximum performance when tested and maintained in compliance with
CAN/ULC S536.
The sensor can be tested in the following ways:
-
A. Functional: Magnet Test (P/N M02-04-01 or M02-09-00)
This sensor can be functionally tested with a test magnet. The test magnet electronically simulates smoke in the sensing chamber, testing the sensor electronics and connections to the control panel.- Hold the test magnet in the magnet test area as shown in Figure 3.
- The sensor should alarm the panel.
Two LEDs on the sensor are controlled by the panel to indicate sensor status. Coded signals, transmitted from the panel, can cause the LEDs to blink, latch on, or latch off. Refer to the control panel technical documentation for sensor LED status operation and expected delay to alarm.
-
B. Smoke Entry
Sensitivity readings are available through the FACP. Refer to the manufacturer’s published instructions for proper use.
Additionally, canned aerosol simulated smoke (canned smoke agent) may be used for smoke entry testing of the smoke detector. Tested and approved aerosol smoke products are:
Manufacturer | Model |
---|---|
HSI Fire & Safety | 25S, 30S (PURCHECK) |
SDi | SMOKE CENTURIAN, SOLOA4, SMOKESABRE, TRUTEST |
No Climb | TESTIFIRE 2000 |
When used properly, the canned smoke agent will cause the smoke detector to go
into alarm. Refer to the manufacturer’s published instructions for proper use
of the canned smoke agent.
CAUTION
Canned aerosol simulated smoke (canned smoke agent) formulas will vary by
manufacturer. Misuse or overuse of these products may have long term adverse
effects on the smoke detector. Consult the canned smoke agent manufacturer’s
published instructions for any further warnings or caution statements.
-
C. Direct Heat Method (Hair dryer of 1000-1500 watts).
A hair dryer of 1000-1500 watts should be used to test the thermistors. Direct the heat toward either of the two thermistors, holding the heat source approximately 12 inches (30 cm) from the detector in order to avoid damaging the plastic housing. The detector will reset only after it has had sufficient time to cool. Make sure both thermistors are tested individually. -
D. Multi-Criteria Method.
A Testifire® by SDi provides testing of the smoke and heat sensors. Consult the manufacturer’s published instructions for complete instructions.
A sensor that fails any of these tests may need to be cleaned as described under CLEANING, and retested.
When testing is complete, restore the system to normal operation and notify the proper authorities that the system is back in operation.
CLEANING
Before removing the detector, notify the proper authorities that the smoke detector system is undergoing maintenance and will be temporarily out of service. Disable the zone or system undergoing maintenance to prevent unwanted alarms.
- Remove the sensor to be cleaned from the system.
- Remove the sensor cover by pressing firmly on each of the four removal tabs that hold the cover in place.
- Vacuum the screen carefully without removing it. If further cleaning is required continue with Step 4, otherwise skip to Step 7.
- Remove the chamber cover/screen assembly by pulling it straight out.
- Use a vacuum cleaner or compressed air to remove dust and debris from the sensing chamber.
- Reinstall the chamber cover/screen assembly by sliding the edge over the sensing chamber. Turn until it is firmly in place.
- Replace the cover using the LEDs to align the cover and then gently pushing it until it locks into place. Make sure that the thermistors do not become bent under the cover.
- Reinstall the detector.
- Test the detector as described in TESTING.
- Reconnect disabled circuits.
- Notify the proper authorities that the system is back on line.
SPECIAL NOTE REGARDING SMOKE DETECTOR GUARDS
Smoke detectors are not to be used with detector guards unless the combination
has been evaluated and found suitable for that purpose.
FCC STATEMENT
This device complies with part 15 of the FCC Rules. Operation is subject to
the following two conditions: (1) This device may not cause harmful
interference, and (2) this device must accept any interference received,
including interference that may cause undesired operation.
NOTE: This equipment has been tested and found to comply with the limits
for a Class B digital device, pursuant to Part 15 of the FCC Rules. These
limits are designed to provide reasonable protection against harmful
interference in a residential installation. This equipment generates, uses and
can radiate radio frequency energy and, if not installed and used in
accordance with the instructions, may cause harmful interference to radio
communications. However, there is no guarantee that interference will not
occur in a particular installation. If this equipment does cause harmful
interference to radio or television reception, which can be determined by
turning the equipment off and on, the user is encouraged to try to correct the
interference by one or more of the following measures:
- Reorient or relocate the receiving antenna.
- Increase the separation between the equipment and receiver.
- Connect the equipment into an outlet on a circuit different from that to which the receiver is connected.
- Consult the dealer or an experienced radio/TV technician for help.
This Class B digital apparatus complies with Canadian ICES-003.
DEVICE AND SYSTEM SECURITY
Before installing this product ensure that the tamper seal on the packaging is
present and unbroken and the product has not been tampered with since leaving
the factory. Do not install this product if there are any indications of
tampering. If there are any signs of tampering the product should be returned
to the point of purchase.
It is the responsibility of the system owner to ensure that all system
components, i.e. devices, panels, wiring etc., are adequately protected to
avoid tampering of the system that could result in information disclosure,
spoofing, and integrity violation.
SUPPLEMENTAL INFORMATION
For Limitations of Fire Alarm Systems,
please go to:
http://www.systemsensor.com/en-us/Documents/I56-1558.pdf
Limitations of Fire Alarm Systems
Mircom® is a registered trademark of Mircom Technologies, Ltd. Testifire® is a registered trademark of SDi, LLC.
Mircom Technologies Ltd.
25 Interchange Way, Vaughan ON, L4K 5W3
Tel: 905-660-4655, FAX:
905-660-4113
References
- Fire Alarm Resources | Download fire alarm documents
- System Sensor | Honeywell Building Technologies
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>