Safety notes
Ensure that the electrical lines are de-energized before installation. Installation is only permitted by electricians in compliance with local legislation.
Installation
-
Placement
The detector responds to movements and heat in its environment. Avoid an installation in close proximity to stoves, electrical heaters, fans or other moveable objects as they may trigger an unintended activation (2). The presence detector is designed for ceiling mounting. -
Range
To reduce the detection area the enclosed half-shells can be clamped between lens and cover. The detector’s recommended mounting height is 2 to 3,5 m (1). The range of the presence detector may be increased with up to 10 secondary presence detectors edition UP Art. No 41752 or edition AP Art. No 41753.Ensure an approximate 30% overlap of the detection areas for disruption-free detection when using several detectors. -
Wiring
Wire the presence detector according to the wiring diagram (5). All DALI devices are wired in parallel. The Master device automatically recognises connected DALI devices. Do not connect additional DALI power supplies nor multiple Master devices as it would damage the DALI coils as well as the presence detectors.
The presence detector contains an in-built DALI power supply. Do not connect an external DALI power supply.
Setup mode «Out of the box»
Connect the presence detector to mains voltage only after the installation is
completely wired. Respect an approx. 40 s warm-up delay after mains connection
for the detector be operational. The DALI ballasts willl be automatically
recognised by the presence detector. As soon as the detector is connected to
mains voltage, all connected lights switch on and the presence detector works
in On/Off mode. The delay time is set to 15 min. All zones may be switched on
and off via the connected 230 V push buttons or via the P-IR remote control.
All 230 V push buttons will have the same functionality.
Note: All LEDs (red, blue, yellow, green) flash alternately, showing that
the presence detector is in «Out-of the- box» mode.
- Commissioning and programming are described in the operating instructions.
Technical Data
- Supply voltage 230 V / 50 Hz
- Standby power 0,45 W
- Switching power 2300 W / 10 A resistive (cos ϕ 1,0) 1200 VA / 5,2 A inductive (cos ϕ 0,5) 350 VA / 1,5 A LED
- DALI devices 1–64
- DALI power supply max. 200 mA
- DALI cable length
- Ø2.5 mm2 < 300 m
- Ø1.5 mm2 < 150 m
- Ø1.0 mm2 < 100 m
- Max. no. of secondary detectors 10
- Detection area 360°
- Detection range max. Ø 6 m presence, approx. Ø 24 m at a height of 3 m
- Installation height 2–3,5 m
- Lux level control 100–2000 lx
- Timer control 5 min to ∞
- Standby lighting Off, 5 min to ∞, level 0.1 to 51%.
- Protection class IP54
- Temperature range -5 bis +50 °C
- Dimensions
- Edition UP: Ø 100×46.4 mm (visible dimensions)
- Edition AP: Ø 117.3×45.9 mm (visible dimensions)
- Flush-mount drilling Ø 90 mm
- Colour RAL9010
Warnings regarding installation
The installation of products that will permanently be part of the electrical installation and which include dangerous voltages, should be carried out by a qualified installer and in accordance with the applicable regulations. This user manual must be presented to the user. It should be included in the electrical installation file and it should be passed on to any new owners. Additional copies are available on the Niko website or via Niko customer services.
CE marking
This product complies with all of the relevant European guidelines and
regulations. For radio equipment Niko llc declares that the radio equipment in
this manual conforms with the 2014/53/EU directive. The full text of the EU
declaration of conformity is available at www.niko.eu
under the product reference, if applicable.
Environment
This product and/or the batteries provided cannot be disposited in non-
recyclable waste. take your discarded product to a recognised collection
point. Just like producers and importers, you too play an important role in
the promotion of sorting, recycling and reuse of discarded electrical and
electronic equipment. To finance the rubbish collection and waste treatment,
the government levies recycling charges in certain cases (included in the
price of this product).
Support & contact
nv Niko sa
Industriepark West 40
9100 Sint-Niklaas, Belgium
www.niko.eu
+32 3 778 90 80
support@niko.eu
Niko prepares its manuals with the greatest care and strives to make them as complete, correct and up-to-date as possible. Nevertheless, some deficiencies may subsist. Niko cannot be held responsible for this, other than within the legal limits. Please inform us of any deficiencies in the manuals by contacting Niko customer services at support@niko.eu.
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>