SIEMENS 7KT0110 SMART 7KT Discrete Panel Meter Instruction Manual

June 9, 2024
SIEMENS

SIEMENS 7KT0110 SMART 7KT Discrete Panel Meter

Introduction

Purpose of this document
This present manual describes the SMART 7KT discrete panel meter. It is intended for the use of:

  • Planners
  • Plant operators
  • Commissioning engineers
  • Service and maintenance personnel

Required basic knowledge
A general knowledge of the field of electrical engineering is required to understand this manual. Knowledge of the relevant safety regulations and standards is required for installing and connecting the device.

Components of the product
The carton for the products contain

  • 1 SMART 7KT meter
  • 1 set of clamps (4 clamps) for mounting the meter on the panel door
  • 1 Gasket
  • 1 Operating instruction

7KT0110SIEMENS-7KT0110-SMART-7KT-Discrete-Panel-Meter-
\(1\)

7KT0120SIEMENS-7KT0110-SMART-7KT-Discrete-Panel-Meter-
\(2\)

Safety precautions

DANGER Hazardous voltage will cause death or serious injury. Turn off and lock out all power supply before working on this device.

NOTICE
Installation and maintenance must be carried out by qualified personnel. This product has been designed for environment A. Use of this product in environment B may cause unwanted electromagnetic disturbances in which case the user may require to take adequate mitigation measures.
Risk of damage: Please ensure the proper isolation of meter during the IR (Meggering) test.

All safety related codifications, symbols and instructions that appear in this operating manual or on the equipment must be strictly followed to ensure the safety of the operating personnel as well as the instrument. If the equipment is not used in a manner specified by the manufacturer it might impair the protection provided by the equipment.
Do not use the equipment if there is any mechanical damage. Ensure that the equipment is supplied with correct voltage.

CAUTION:

  1. Read complete instructions prior to installation and operation of the unit.
  2. Risk of electric shock.
  3. The equipment in its installed state must not come in close proximity to any heating sources, oils, steam, caustic vapors or another unwanted process by-products.

Technical specification

| 7KT0110 (VA meter)| 7KT0120 (VAF meter)
---|---|---
| Power Monitoring Device Panel instrument for voltage and current LED display Vaux: 95V to 240V AC x/1 or 5 A, Class 1| Power Monitoring Device Panel instrument for voltage, current and frequency LED display Vaux: 95V to 240V AC x/1 or 5 A,

Class 1

Measurements
measuring procedure| |
•  for voltage measurement| True RMS| True RMS
•  for current measurement| True RMS| True RMS
type of measured value detection| complete| complete
voltage curve| Sinusoidal or distorted| Sinusoidal or distorted
measurable line frequency| |
•  initial value| 45 Hz| 45 Hz
•  full-scale value| 65 Hz| 65 Hz
operating mode for measured value detection automatic line frequency detection| –| Yes
Supply voltage
design of the power supply| SMPS power supply| SMPS power supply
type of voltage of the supply voltage| AC| AC
Degree of protection class
protection class IP on the front| IP54| IP54
protection class IP of the terminal| IP20| IP20
Suitability
suitability for operation| Installation in stationary panels in closed rooms| Installation in stationary panels in closed rooms
Product Functions
product function| |
•  voltage measurement| Yes| Yes
•  current measurement| Yes| Yes
•  frequency measurement| –| Yes
Display and operation
design of the display| LED| LED
height of the display| 39 mm| 50 mm
width of the display| 40.5 mm| 45.4 mm
color of the background of the display| Black| Black
national language on the display screen is supported| EN| EN
number of keys| 2| 2
Fault limits
reference condition for metering accuracy| In accordance with IEC61557-12| In accordance with IEC61557-12
formula for relative total measurement inaccuracy| |
•  for measured variable voltage| Class 1 as per IEC 61557-12| Class 1 as per IEC 61557-12
•  for measured variable current| Class 1 as per IEC 61557-12| Class 1 as per IEC 61557-12
•  for measured variable frequency| –| Class 0.1 as per IEC 61557-12
| 7KT0110 (VA meter)| 7KT0120 (VAF meter)
---|---|---
Measuring inputs
measurable supply voltage between L and N at AC maximum rated value| 240 V| 240 V
measurable supply voltage between L and N at AC| |
•  minimum| 11 V| 11 V
•  maximum| 300 V| 300 V
measurable supply voltage between the line conductors at AC maximum rated value| 415 V| 415 V
measurable supply voltage between the line conductors at AC| |
•  minimum| 19 V| 19 V
•  maximum| 519 V| 519 V
voltage measuring range extension with external voltage transformers| up to 500kV| up to 500kV
line conductors and neutral conductors internal resistance for voltage

measurement

| 1.12 MΩ| 1.12 MΩ
measuring category for voltage measurement| CAT III| CAT III
measurable current| 1A / 5A| 1A / 5A
relative measurable current at AC| |
•  minimum| 1 %| 1 %
•  maximum| 120 %| 120 %
current measuring range extension with external current transformers| Up to 10kA| Up to 10kA
measuring category for current measurement| CAT III| CAT III
measurable line frequency| –| 45…65 Hz
Connections
type of electrical connection| |
•  at the measurement inputs for voltage| screw-type terminals| screw-type terminals
•  at the measurement inputs for current| screw-type terminals| screw-type terminals
Mechanical Design
mounting| flush panel-door mounted| flush panel-door mounted
size of Power Monitoring Device| size 96| size 96
height| 99 mm| 99 mm
width| 99 mm| 99 mm
cut-out| 91.5 mm x 91.5 mm| 91.5 mm x 91.5 mm
depth| 52 mm| 52 mm
installation depth| 49 mm| 49 mm
net weight| 207 g| 223 g
mounting position| Vertical| Vertical
Environmental conditions
ambient temperature during operation| |
•  minimum| -10 °C| -10 °C
•  maximum| 55 °C| 55 °C
ambient temperature during storage| |
•  minimum| -20 °C| -20 °C
•  maximum| 75 °C| 75 °C
relative humidity at 25 °C without condensation during operation

maximum

| 85 %| 85 %
installation altitude at height above sea level maximum| 2 000 m| 2 000 m
degree of pollution| 2| 2

IEC Standards

Description Standard
Accuracy IEC 61557-12
EMC requirements IEC 61326-1
Degree of protection test (IP) IEC 60529
Safety requirements IEC 61010-1 and

IEC 61010-2-030

Certifications
SMART 7KT discrete panel meter conforms to IEC standards, IPC electronics assembly standard and

Assembly

Installation
For installing the meter
Prepare the panel cutout with proper dimensions as shown below.SIEMENS-
7KT0110-SMART-7KT-Discrete-Panel-Meter- \(3\) SIEMENS-7KT0110-SMART-7KT-Discrete-Panel-Meter- \(4\)

Installation Guidelines

  1. This equipment, being built-in-type, normally becomes a part of main control panel and in such case the terminals do not remain accessible to the end user after installation and internal wiring.
  2. Conductors must not come in contact with the internal circuitry of the equipment or else it may lead to a safety hazard that may in turn endanger life or cause electrical shock to the operator.
  3. Circuit breaker or mains switch must be installed between power source and supply terminals to facilitate power ‘ON’ or ‘OFF’ function. However this switch or breaker must be installed in a convenient position normally accessible to the operator.
  4. Before disconnecting the secondary of the external current transformer from the equipment, make sure that the current transformer is short circuited to avoid risk of electrical shock and injury.
  5. The equipment shall not be installed in environmental conditions other than those mentioned in this manual.
  6. The equipment does not have a built-in-type fuse. Installation of external fuse of 0.5 A, Class gG type for electrical circuitry is highly recommended.
  7. Remove the scratch-guard from the meter display during commissioning of the panel.

Wiring Guidelines

  1. To prevent the risk of electric shock, power supply to the equipment must be kept OFF while doing the wiring arrangement.
  2. Wiring shall be done strictly according to the terminal layout. Confirm that all connections are correct.
  3. Use lugged terminals.
  4. To reduce electromagnetic interference use of wires with adequate ratings and twists of the same in equal size shall be made with shortest connections.
  5. Layout of connecting cables shall be away from any internal EMI source.
  6. Cable used for connection to power source, must have a cross-section of 1mm2 to 2.5mm2. These wires shall have current carrying capacity of 6A.
  7. Copper cable should be used (Stranded or Single core cable).

For demounting the meterSIEMENS-7KT0110-SMART-7KT-Discrete-Panel-Meter-
\(5\)

Connection

Typical Wiring Diagram – SMART 7KT0110SIEMENS-7KT0110-SMART-7KT-Discrete-
Panel-Meter- \(6\) SIEMENS-7KT0110-SMART-7KT-
Discrete-Panel-Meter- \(7\)

Typical Wiring Diagram – SMART 7KT0110

Terminal Connections – SMART 7KT0110

Typical Wiring Diagram – SMART 7KT0120SIEMENS-7KT0110-SMART-7KT-Discrete-
Panel-Meter- \(10\)SIEMENS-7KT0110-SMART-7KT-
Discrete-Panel-Meter- \(11\)

Terminal Connections – SMART 7KT0120

Configuration

There are 2 dedicated function keys labelled as F1 and F2. Use these 2 keys to read meter parameters. Use the soft-touch keys to read the parameters. The keys have multiple assignments. Function assignments and key labelling change according to the context of operator input. A short touch on the key triggers the function once. Touching the key for longer switches on the autorepeat function after approximately 1 s. The function of the key is triggered repeatedly while the key is touched. Autorepeat is useful, for example, for fast incrementing of values when parameterizing the device.SIEMENS-7KT0110
-SMART-7KT-Discrete-Panel-Meter- \(14\)

SMART 7KT0110
Serial Number Description:
Touch F1 for 10-15 secs to display 8 digit Serial number in 2 row & 2 pages. For Eg., 22010001
For the configuration setting mode:

  • Touch & Hold F1 + F2 key for 5 sec to enter and exit from configuration menu.
  • Touch F1 key to increment the configuration pages.
  • Use F2 key to edit the value and shift the cursor for next digit to edit.
  • Touch & Hold F2 key for 2 sec to save the parameter value.
  • Touch and hold F1 Key for 5 second to set CT/PT primary values in kilo from normal and vice versa.

E.g.: If 1300 is to be set, first set the left most digit to 1, then hold the key for 2 sec to shift to kilo. The display will show 1.00k. The change the value after the decimal point to 3 to get the value of 1.3k. the hold the key for 2 sec to save the parameter.

Config. Page.| Function| Range or Selection| Factory Setting
---|---|---|---
1| Password| 000-999| 100
2| Change password| YES/NO| No
3| New Password| 000-999| 000
4| Network selection| 3P4W, 3P3W, 1P2W| 3P3
5| CT Primary #| 1 to 10K, If CT Sec 1 5 to 10K, If CT Sec 5| 5
6| CT Secondary| 1 or 5| 5
7| PT Primary #| 100 to 500K| 350
8| PT Secondary| 100 to 500| 350
11| Page Scrolling mode| auto (AUT), manual (MNL)| AUT
112| Factory default| YES/NO| NO

Serial Number Description:
Touch F1 and hold the key for 10sec to display 8 digit Serial number in 3 row
For Eg., 22010001

For the configuration setting mode:

  • Touch & Hold F1 + F2 key for 5 sec to enter and exit from configuration menu.
  • Use F1 key to increment the configuration pages .
  • Touch F2 key to edit the value and shift the cursor for next digit to edit.
  • Use F2 key for 2 sec save the parameter value .
  • Press F1 Key for 5 second to set CT/PT primary values in Kilo from normal and vice versa.

E.g.: If 1300 is to be set, first set the left most digit to 1, then hold the key for 2 sec to shift to kilo. The display will show 1.00k. The change the value after the decimal point to 3 to get the value of 1.3k. the hold the key for 2 sec to save the parameter.

Config. Page.| Function| Range or Selection| Factory default Setting
---|---|---|---
1| Password| 000-999| 100
2| Change password| YES/NO| NO
3| New Password| 000-999| 000
4| Network selection| 3P4,3P3, 1P2| 3P4
5| CT Primary#| 1 to 10K, If CT Sec 1 5 to 10K, If CT Sec 5| 5
6| CT Secondary| 1/5| 5
7| PT Primary#| 100 to 500K| 350
8| PT Secondary| 100 to 500| 350
9| Number of Poles| 0 to 98| 2
10| Reset Run & On hour| YES/NO| NO
11| Page Scrolling mode| auto (AUT), manual (MNL)| AUT
12| Factory default| YES/NO| NO

Reading of parameters- SMART 7KT0110 (VA meter)

Online Page Description
There are two dedicated keys labelled as F1 and F2. Use these 2 keys to read parameters. Touch these keys to read the parameters. Units of corresponding parameters on display will glow automatically.

  • Key F1: To Increment Main Page.
  • Key F2: To Increment subpages of respective Main Page
Touch Key Screen Online Page Description

For 3P4W
Touch F1| 1st main page| Displays Line to Neutral voltage (L1-N) & 1st phase current.
Touch F2| 1st sub page| Displays Line to Neutral voltage (L2-N) & 2nd phase current.
Touch F2| 2nd sub page| Displays Line to Neutral voltage (L3-N) & 3rd phase current.
Touch F2| 3rd sub page| Displays Line to Line voltage (L1-L2) & 1st phase current.
Touch F2| 4th sub page| Displays Line to Line voltage (L2-L3) & 2nd phase current.
Touch F2| 5th sub page| Displays Line to Line voltage (L1-L3) & 3rd phase current.
Touch F2| 6th sub page| Displays Average value of Line to Line voltage, Current of three phase
Touch F2| 7th sub page| Displays Average value of Line to Neutral voltage, Current of three phase
Touch F1| 2nd main page| Displays Maximum & Minimum Line to Neutral voltage(L1-N) .
Touch F2| 1st sub page| Displays Maximum & Minimum Line to Neutral voltage (L2-N).
Touch F2| 2nd sub page| Displays Maximum & Minimum Line to Neutral voltage (L3-N) .
Touch F1| 3rd main page| Displays Maximum & Minimum Line to Line voltage(L1-L2) .
Touch F2| 1st sub page| Displays Maximum & Minimum Line to Line voltage (L2-L3).
Touch F2| 2nd sub page| Displays Maximum & Minimum Line to Line voltage (L1-L3) .
Touch F1| 4th main page| Displays Maximum & Minimum current of 1st phase.
Touch F2| 1st sub page| Displays Maximum & Minimum current of 2nd phase.
Touch F2| 2nd sub page| Displays Maximum & Minimum current of 3rd phase.
For 3P3W
Touch F1| 1st main page| Displays Line to Line voltage (L1-L2) & 1st phase current.
Touch F2| 1st sub page| Displays Line to Line voltage (L2-L3) & 2nd phase current.
Touch F2| 2nd sub page| Displays Line to Line voltage (L1-L3) & 3rd phase current.
Touch F2| 3rd sub page| Displays Average value of Line to Line voltage, Current of three phase
Touch F1| 2nd main page| Displays Maximum & Minimum Line to Line voltage(L1-L2) .
Touch F2| 1st sub page| Displays Maximum & Minimum Line to Line voltage (L2-L3).
Touch F2| 2nd sub page| Displays Maximum & Minimum Line to Line voltage (L1-L3) .
Touch F1| 3rd main page| Displays Maximum & Minimum current of 1st phase.
Touch F2| 1st sub page| Displays Maximum & Minimum current of 2nd phase.
Touch F2| 2nd sub page| Displays Maximum & Minimum current of 3rd phase.
For 1P2W
Touch F1| 1st main page| Displays Line to Neutral voltage (L1-N) & 1st phase current.
Touch F2| 1st sub page| Displays Maximum & Minimum Line to Neutral voltage(L1-N) .
Touch F2| 2nd sub page| Displays Maximum & Minimum current of 1st phase.

Reading of parameters- SMART 7KT0120 (VAF meter)

Online Page Description
There are two dedicated keys labelled as F1 and F2. Use these 2 keys to read parameters. Touch these keys to read the parameters. Units of corresponding parameters on display will glow automatically.

  • Key F1: To Increment Main Page.
  • Key F2: To Increment subpages of respective Main Page
Touch Key Screen Online Page Description

For 3P4W
Touch F1| 1st main page| Displays Line to Neutral voltage of three phase
Touch F2| 1st sub page| Displays Line to Line voltage of three phase
Touch F2| 2nd sub page| Displays Minimum Line to Neutral voltage of three phase
Touch F2| 3rd sub page| Displays Maximum Line to Neutral voltage of three phase
Touch F2| 4th sub page| Displays Minimum Line to Line voltage of three phase
Touch F2| 5th sub page| Displays Maximum Line to Line voltage of three phase
Touch F1| 2nd main page| Displays Current of three phase
Touch F2| 1st sub page| Displays Minimum Current of three phase
Touch F2| 2nd sub page| Displays Maximum Current of three phase
Touch F2| 3rd sub page| Displays RPM
Touch F2| 4th sub page| Displays Run hour
Touch F1| 3rd main page| Displays Average value of Line to Neutral voltage, Current of three phase and frequency.
Touch F2| 1st sub page| Displays Average value of Line to Line voltage, Current of three phase and frequency.
Touch F2| 2nd sub page| Displays ON hour
For 3P3W
Touch F1| 1st main page| Displays Line to Line voltage of three phase
Touch F2| 1st sub page| Displays Minimum Line to Line voltage of three phase
Touch F2| 2nd sub page| Displays Maximum Line to Line voltage of three phase
Touch F1| 2nd main page| Displays Current of three phase
Touch F2| 1st sub page| Displays Minimum Current of three phase
Touch F2| 2nd sub page| Displays Maximum Current of three phase
Touch F2| 3rd sub page| Displays RPM

Touch F2| 4th sub page| Displays Run hour
Touch F1| 3rd main page| Displays Average value of Line to Line voltage, Current of three phase and frequency.
Touch F2| 1st sub page| Displays ON hour
For 1P2W
Touch F1| 1st main page| Displays Line to Neutral voltage of 1st phase
Touch F2| 1st sub page| Displays Minimum Line to Neutral voltage of 1st phase
Touch F2| 2nd sub page| Displays Maximum Line to Neutral voltage of 1st phase
Touch F1| 2nd main page| Displays Current of 1st phase
Touch F2| 1st sub page| Displays Minimum Current of 1st phase
Touch F2| 2nd sub page| Displays Maximum Current of 1st phase
Touch F2| 3rd sub page| Displays RPM*
Touch F2| 4th sub page| Displays Run hour
Touch F1| 3rd main page| Displays Line to Neutral voltage, Current of 1st phase and frequency.
Touch F2| 1st sub page| Displays ON hour

Maintenance

Guidelines

  • The equipment should be cleaned regularly to avoid blockage of ventilating parts.
  • Clean the equipment with a clean dry or damp cloth. Do not use any cleaning agent other than water.

Disposal and recycling
Dispose of or recycle the module in accordance with the applicable laws and regulations in your country.

These instructions do not purport to cover all details or variations in equipment, or to provide for every possible contingency in connection with installation, operation, or maintenance. Should additional information be desired, please contact the local Siemens sales office. The contents of this instruction manual shall not become part of or modify any prior or existing agreement, commitment, or relationship. The sales contract contains the entire obligation of Siemens. The warranty contained in the contract between the parties is the sole warranty of Siemens. Any statements contained herein do not create new warranties or modify the existing warranty. Trademarks – Unless otherwise noted, all names identified by ® are registered trademarks of Siemens AG or Siemens Industry, Inc. The remaining trademarks in this publication may be trademarks whose use by third parties for their own purposes could violate the rights of the owner.