Haier AV16IMAURA MRV-5-RC Heat Recovery Outdoor 45kW User Guide
- June 9, 2024
- Haier
Table of Contents
Haier AV16IMAURA MRV-5-RC Heat Recovery Outdoor 45kW
- Haier’s heat recovery outdoor unit and new valve box offer simultaneous cooling and heating in one system, with multiple indoor unit choices.
- Three-pipe full DC inverter heat recovery system
- Heating and cooling, with an operational range from -23°C to 50°C Outdoor units can work in parallel to power a range of indoor units
- Total connected pipe length up to 1000m with 110m lift height
DIMENSIONS
- Height 1690 mm
- Width 1410 mm
- Depth 750 mm
FEATURES & BENEFITS
Commercial scale solutions
- Outdoor units can work in parallel, providing combined cooling or heating capacity up to 224kW and connecting to up to 64 indoor units of varying capacity and style.
Heat recovery
- The MRV-5-RC outdoor unit and three-pipe valve box can heat and cool simultaneously using heat recovery. In a three-pipe system, heat absorbed from a cooling indoor unit can be recovered and used by another indoor unit for heating, and vice versa.
Efficiency
- With full DC-inverter technology and a new four-way heat exchanger, MRV-5-RC is designed to heat and cool large spaces efficiently.
Choose your indoor unit
- Choose from our wall mount, slim duct, high static duct, compact cassette, and large cassette indoor air conditioner units to suit your environment.
Simple maintenance
- The electrical control box is designed with a hinge to easily lift and swing open for faster servicing and diagnostics.
Optional central controller
- For personalized control of the whole system, a wall-mounted controller lets you manage individual indoor units, groups, or zones from a single point.
SPECIFICATIONS
Capacity
- Cooling capacity (kW) 45kW
- Heating capacity (kW) 50kW
Consumption
- COP 3.77
- EER 3.53
Features
- Compressor type DC INV. SCROLL
- Inverter controlled compressor
Installation
- Connectible indoor unit ratio 50-130%
- Liquid line 12.7mm
- Maximum number of indoor units 27
- Suction line 28.6mm
Performance
- R410a refrigerant
- Sound power SWL (outdoor) 88dBA
- Working temperature cooling -5°C ~ +50°C
- Working temperature heating -23°C ~ +21°C
Power Requirements
- Power phase 3
- Power supply 50Hz
- Supply voltage 400V
Product dimensions
-
Depth 750 mm
-
QUICK REFERENCE GUIDE > AV16IMAURA
-
Height 1690 mm
-
Net weight 385kg mm
-
Width 1410 mm
-
SKU 51530
-
The product dimensions and specifications on this page apply to the specific product and model.
-
Under our policy of continuous improvement, these dimensions and specifications may change at any time.
-
You should therefore check with Fisher & Paykel’s Customer Care Centre to ensure this page correctly describes the model currently available. ? 2020 Haier Inc. All rights reserved
-
Other product downloads available at haier.com
-
User Guide Outdoor Unit
-
User Guide Valve Box 1×1
-
User Guide- Valve Box 1×4
-
User Guide – Wired Controller YR-E17A
-
User Guide – Wired Controller YR-E16B
-
Installation Guide Outdoor Unit
-
Installation Guide Valve Box 1×1
-
Installation Guide Valve Box 1×4
-
Installation Guide Wired Controller YR-E17A
-
Installation Guide Wired Controller YR-E16B
-
Install Drawing
-
A PEACE OF MIND SALE
-
24 Hours 7 Days a Week Customer Support
-
T 0800 372273www.haier.com
-
Date: 25.01.2023 > 2
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>