SIEMENS GPC166.1P Damper Actuator Instruction Manual

June 9, 2024
SIEMENS

SIEMENS-LOGO

SIEMENS GPC166.1P Damper Actuator

SIEMENS-GPC166-1P-Damper-Actuator-PRODUCT

Contents

SIEMENS-GPC166-1P-Damper-Actuator-FIG-1

  • a. Actuator
  • b. Mounting bracket
  • c. Mounting screws
  • d. 3 mm hex key

Hints/Warnings

  • Store these instructions with the actuator or with the plant documentation.

Warning

  • Do not open the actuator!
  • Only authorized personnel are to connect actuators.
  • Do not expose the actuator’s connecting cables to water or lay the cables in water.
  • The device of protection class II (protective insulation)
  • The device of protection class III (protective insulation)
  • For wiring and commissioning, see Technical Instructions 155-782.

Adapter Mounting

SIEMENS-GPC166-1P-Damper-Actuator-
FIG-2

Shaft Mounting

SIEMENS-GPC166-1P-Damper-Actuator-
FIG-3

Manual Override

SIEMENS-GPC166-1P-Damper-Actuator-
FIG-4

  • winding
  • positioner
  • posicionar

Wiring Diagrams

SIEMENS-GPC166-1P-Damper-Actuator-
FIG-5

  • GPC12x.1P
  • 2-Position: 24 Vac/dc
  • GPC13x.1P
  • Floating: 24 Vac/dc
  • GPC16x.1P
  • Modulating: 24 Vac/dc
  • GPC32x.1U
  • 2-Position: 100 to 240 Vac

Auxiliary Switches

SIEMENS-GPC166-1P-Damper-Actuator-
FIG-6

Actuator Position| Switch A Common S1 Connected to| Switch B Common S4 Connected to
---|---|---
0° to 5°| S3| S6
5° to 85°| S2| S6
85° to 90°| S2| S5

CAUTION:

  • Mixed switch operation to the switching outputs of both dual-end switches (5° and 85°) is not permitted.
  • Either AC line voltage from the same phase must be applied to all six outputs of the fixed dual-end switches, or UL-Class 2 voltage must be applied to all six outputs.

DIP Switches

NOTE: The black position indicates the active switch setting.SIEMENS-
GPC166-1P-Damper-Actuator-FIG-7

Control Signal Selection

  • Selects the control and feedback signals
  • Input Signal Inversion Allows inverting the control input signal
  • The arrow direction indicates opening or closing (closing or opening) when operating an actuator with a given control signal.
  • Direct acting (Factory setting)
  • Input signal 0 Vdc ► fail-safe position
  • Inverse acting
  • Input signal 10 Vdc ► fail-safe position

Wire Designations

Table 1.


Connecting

| Standard Symbol| ****

Function

| ****

Color

| Color Symbol
---|---|---|---|---




24 Vac/dc Actuator

| 1| Supply (SP)| Red| RD
2| System Neutral| Black| BK
6| Control signal clockwise| Violet| VT
7| Control signal counterclockwise| Orange| OG
8| Input Signal: 0 (2) to 10 Vdc or 10 to 0 (2) Vdc (GPC16x)| Gray| GY
9| Position Output: 0 (2) to 10 Vdc or 10 to 0 (2) Vdc (GPC16x)| Pink| PK
120 Vac| 3| Supply| Black| BK
4| Neutral| White| WH



Auxiliary Switches

| 1| Switch A – Common| S1| Gray/red
2| Switch A – N.O.| S2| Gray/blue
3| Switch A – N.C.| S3| Gray/pink
4| Switch B – Common| S4| Black/red
5| Switch B – N.O.| S5| Black/blue
6| Switch B – N.C.| S6| Black/pink

Retrofit Wiring

SIEMENS-GPC166-1P-Damper-Actuator-
FIG-12

Dimensions

in Inches (mm)SIEMENS-GPC166-1P-Damper-Actuator-
FIG-13

Information in this publication is based on current specifications.
The company reserves the right to make changes in specifications and models as design improvements are introduced.
OpenAir is a registered trademark of Siemens Schweiz, AG.
Other product or company names mentioned herein may be the trademarks of their respective owners.

  • © 2019 Siemens Industry, Inc.
  • Siemens Industry, Inc.
  • Building Technologies Division
  • 1000 Deerfield Parkway
  • Buffalo Grove, IL 60089-4513
  • USA
  • Tel. +1-847-215-1000
  • Your feedback is important to us.
  • If you have comments about this document, please send them to sbt_technical.editor.us.sbt@siemens.com
  • Document No. 129-585
  • Printed in the USA

Documents / Resources

| SIEMENS GPC166.1P Damper Actuator [pdf] Instruction Manual
GPC166.1P Damper Actuator, GPC166.1P, Damper Actuator, Actuator
---|---

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals