BELIMO PMBUP-MFT-T PKB and PMB Actuators
Near Field Communication
(NFC) allows fast programming, commissioning and troubleshooting – even when the actuator is not powered it can be programmed.
ZIP-BT-NFC
Belimo Assistant App
Direct Coupling Or Remote Mounting
Retrofit Form Required
** Note: Signal will be overridden with hand crank engaged in the port located closest to junction box. Position of actuator can be manually adjusted with hand crank. After use, make sure caps are fastened back on securely after use.
½” NPT adapters supplied. Move as needed for desired location
For NPT adaptor, suitable UL Listed, ½ inch, conduit fitting shall be used in accordance with NFPA 70 and rated for the environmental conditions of the product. See Manufacturers recommendation for torque.
WARNING: The wiring technician must be trained and experienced with electronic circuits. Disconnect power supply before attempting any wiring connections or changes. Make all connections in accordance with wiring diagrams and follow all applicable local and national codes. Provide disconnect and overload protection as required. Use copper, twisted pair, conductors only. If using electrical conduit, the attachment to the actuator must be made with flexible conduit.
WIRING DIAGRAMS
PR/PM… and PKR/PK… Actuators
Notes:
- Meets cULus requirements without the need of an electrical ground connection.
- Provide overload protection and disconnect as required.
- Only connect common to neg. (-) leg of control circuits.
- Two built-in auxiliary switches (2x SPDT), for end position indication, interlock control, fan startup, etc.
- Actuators may be controlled in parallel. Current draw and input impedance must be observed.
- Universal Power Supply (UP) models can be supplied with 24 VAC up to 240 VAC, or 24 VDC up to 125 VDC.
- During installation, testing, servicing and troubleshooting of this product, it may be necessary to work with live electrical components. Have a qualified licensed electrician or other individual who has been properly trained in handling live electrical components perform these tasks. Failure to follow all electrical safety precautions when exposed to live electrical components could result in death or serious injury.
**Control type, direction and fail position changes can be made via Belimo Selection Tools, i.e. ZTH, PC-Tool and App.
Optional: end switch adjustment
Disconnect power.
-
Gear disengagement
Open the manual override cover and insert the hand crank. Manual override is possible. -
Manual override
Turn the hand crank until indicates the desired switching position and then remove the crank. -
Auxiliary switch
Open the auxiliary switch adjustment cover and properly seat the hand crank into the actuator. Turn the crank until the arrow points to the vertical line. -
Terminals
Connect continuity tester to S4 + S5 or to S4 + S6. If the auxiliary switch should switch in the opposite direction, rotate the hand crank by 180˚. -
LED Display Green
Off: No power supply or malfunction, On: In operation
Press button: Triggers test run, followed by standard mode. -
LED Display Yellow
Off: Standard mode,
On: Test run active.