KSRLIGHTING KSRFRD350EM 3000K LED Dimmable Downlight Instructions
- June 9, 2024
- KSRLIGHTING
Table of Contents
KSRFRD350EM 3000K LED Dimmable
Downlight Instructions
KSRFRD350EM/351EM
KSRFRD350EM 3000K LED Dimmable Downlight
Read these instructions before commencing installation. Please give these instructions to the owner/occupier after installation to retain for future reference/maintenance.
Important Information
It is recommended that these luminaires are installed and fitted by a
qualified electrician ensuring the installation complies with current IEE
wiring regulations & local building control. These products are designed for
connection to a 240V~50Hz supply.
Any faulty, broken or damaged luminaires should be replaced immediately.
KSR will not accept responsibility for any claims arising from a poor
installation.
Please Note: The limited warranty shall be deemed null and void in the
following circumstances: Failure by the installer, end user or any third party
to exercise caution to protect any covered product or part from outside
damage, adverse temperature (normal operating ambient temperature 0°C –
+35°C), humidity conditions, fluctuations in the electrical system or
physical abuse as well as failure related to workmanship in the installation
of the products or parts.
Important User Advice
Always switch off mains supply before installing/servicing.
*Due to the components used in the driver these are not compatible with earlier versions of the Qr10 downlights and should not be mixed on the same circuit.
This luminaire is suitable for indoor use only and should not be fitted to
damp or wet surfaces such as freshly plastered or painted ceilings. To prevent
damage to the driver, do not mix with conventional magnetic ballasts on the
same electrical circuit. At the end of life the luminaire is classed as WEEE
under directive 2014/30/EU and should be disposed of in accordance with local
legislation
Installation Procedure
KSR recommends that a sample hole is cut in some scrap material to familiarize
yourself with the installation. Once you are completely satisfied:
Locate the area’s suitable to install these luminaires.
Cut a 72mm round hole in the ceiling and ensure sufficient ceiling void
without infringing on joists, water pipes or electrical cables.
Connect the mains supply to the emergency pack/LED Driver as below. Earth
terminals are provided for earth continuity only. The LED driver allows for
mains loop in/loop out connections, if not looping through either of the L,E
& N inputs can be used.
Press springs back and push luminaire body into aperture.
This luminaire is suitable for installations where vapor permeable membranes
are installed. Fit this product as per illustration shown in Fig.1
If you are installing one of the KSR detachable rims remove the standard white
rim by pulling the trim off of the main fitting, do not twist the trim and
attach new trim by pushing and clicking it into place. Ensure there is
adequate free air ventilation around the driver and emergency control pack.
the head unit can be covered in mineral wool insulation.
Turn on the mains supply to test the luminaire.
This downlight is designed with a Isolator switch (Fig.2) to allow for High voltage insulation resistance testing, without having to remove the luminaire/driver from the circuit just switch all isolation switches to off, test then switch back to on for normal operation.
An initial 24 hour charge period will be required prior to conducting any
emergency lighting tests, the reafteperiodic testing should be carried out in
line with current regulations.
Please note: Depending on the amount of Qr10 fittings on a circuit you may have to upgrade the breaker a ‘C’ or ‘D’ type due to the way electronic LED drivers start up with higher inrush currents compared to halogen lighting.
3 Hour Emergency Downlight Qr10 COB
Available Rim Finishes: White, Chrome, Satin Chrome, Brass Antique Brass,
Copper, Black or Stainless Steel
Part “C”
Compliant Stops moisture & air flow through the luminaire Please Note: The isolation switch needs to be in the On ( I )
position during normal operation
| Ø Rim Size| Ø Cut out| Void Depth Read| L ED
Wattage/ Colour/Lumens
---|---|---|---|---
KSRFRD350EM| 85mm| 72mm| 90mm| 8.8W – 3000K (825 lumens)
KSRFRD351EM| 85mm| 72mm| 90mm| 8.8W – 4000K (855 lumens)
Installation Sheet
Installation Particulars For End User
Installation Procedure
Familiarize yourself with the installation procedure and ensure the power is
safely isolated before installing the Emergency pack.
Ensure the LED luminaire is within the specification 9-55VDC or 55-80VDC, if
55-80VDC voltage range is required please remove the jumper as stated on the
casing.
Wire as required (Fig.1):
Non-Maintained Emergency
Connect the mains input Unstitched Live (EM_L), Neutral (EN_N). The low
voltage side just requires output to the LED luminaire positive (+) and
negative (-). Then connect the battery. Install the LED indicators in a
suitable location.
Maintained Emergency
Connect the mains input Unstitched Live (EM_L), Neutral (EN_N) and Switch Live
(SW_L). Connect the Live out (Drill) and Neutral out (Drink) to the driver
mains input. The low voltage side connect the output from the LED driver to
the from LED Driver positive (D+) and Negative (D-) luminaire output to the
LED luminaire positive (+) and negative (-). Then connect the battery.
Install the LED indicators in a suitable location.
Please note: For manual testing purposes a provision is made inside the
cover of the low voltage side of the driver (Fig.1) marked as Test on the
casing. See overleaf for details on manual testing.
Install emergency label supplied on luminaire to be visible in normal use.
Turn on the power and ensure that the module is showing charge indicator.
This fitting requires a minimum 24 Hour initial charge period prior to any
manual emergency testing, please see overleaf for testing routine, write on
the battery label in permanent ink the date of commissioning. All results
must be recorded and left with the end user.
The battery has a rated duration of at least 4 years but should be replaced if
the duration of operation is less than 3 hours after a 24hr charge time with
no interrupted supply.
Warranty
The LED luminaire comes complete with a 36 month warranty from date of
purchase unless otherwise stated. Please note that the emergency packs and
batteries come with a 36 month fixed warranty. Should any claim be made
against battery failure within the warranty period, full and complete
maintenance test reports must be provided.
Self Test Emergency Inspection/Testing Instructions
All full duration tests should be where possible be undertaken at times of low
risk adjacent emergency luminaires we recommend that you you reset the inbuilt
timer or run a
manual 30 day test on alternate emergency luminaires to stagger testing times.
Once commissioned fill in the date of the first test/install date this will
allow the end user to monitor and record subsequent test information on the
supplied report. All tests with the exception of the visual inspection will be
completed automatically at the relevant times including battery charge
condition and lamp status.
Daily:
Visual inspection of the battery charge LED.
Automatic Monthly (Every 30 Days): (in addition to the daily check) The
results of the short duration test shall be recorded.
Automatic Annually (Every 180 & 360 Days): (in addition to the daily
check) The results of the full duration tests shall be recorded.
A copy of this report must accompany any emergency pack returned to KSR Lighting for any reason.
Performance Indicators
Normal Operation| Red LED off, Green LED Solid
Automatic 30 Day Test| Red LED off, Green LED flashing once a second
Automatic 180/360 Day Test| Red LED off, Green LED flashing twice a second
Manual Simulated Power Failure| Red LED off, Green LED off
Manual 30 Day Test| Red LED off, Green LED flashing once a second
Manual 180/360 Day Test| Red LED off, Green LED flashing twice a second
Manual Fast Test (24 minutes)| Red LED off, Green LED four teems a second
M anual Testing – C a n o n l y be
completed under mains conditions
Manual Simulated Power Failure| Hold test button until you hear 1 beep
Manual 30 Day Test| Hold test button until you hear 2 beeps
Manual 180/360 Day Test| Hold test button until you hear 3 beeps
Manual Fast Test (24 minutes)| Hold test button until you hear 4 beeps
Abort Test| Hold test button for 1 second
Reset Inbuilt Timer| Hold test button for 15 seconds long beep
Fault Indicators
Battery/Charging Fault| Red LED flashing once a second, Green LED off, Beeps
twice every minute until fault rectified
Lamp Fault| Red LED flashing twice a second, Green LED off, Beeps twice every
minute until fault rectified
Failed Duration Test| Red LED solid, Green LED off, Beeps twice every minute
until fault rectified
KSR Lighting Self Test Emergency Install/Inspection/Test Record
Product Code: | Product Description: |
---|
Product Location:
Commissioning Date:| Commissioned By:
Month| ****
Test
| Year:| Year:| Year:| Year:| Year:
---|---|---|---|---|---|---
Sign| Date| Sign| Date| Sign| Date| Sign| Date| Sign| Date
01| Function| | | | | | | | | |
02| Function| | | | | | | | | |
03| Function| | | | | | | | | |
04| Function| | | | | | | | | |
05| Function| | | | | | | | | |
06| Duration| | | | | | | | | |
07| Function| | | | | | | | | |
08| Function| | | | | | | | | |
09| Function| | | | | | | | | |
10| Function| | | | | | | | | |
11| Function| | | | | | | | | |
12| Duration| | | | | | | | | |