REMKO LTE 120 Eco Mobile Dehumidifier Instruction Manual

June 9, 2024
REMKO

LTE 120 Eco Mobile Dehumidifier

Operating and installation instructions
REMKO LTE Eco series Dehumidifier
LTE 120 Eco

0300-2022-04 Edition 1, en_GB

Read the instructions prior to performing any task!

R454C
Refrigerant

Read these operating instructions carefully before commissioning / using this device! These instructions are an integral part of the system and must always be kept near or on the device. Subject to modifications; No liability accepted for errors or misprints!
Translation of the original

Table of contents
1 Safety and usage instructions………………………………………………………………………………………………. 4 1.1 General safety notes……………………………………………………………………………………………………….. 4 1.2 Identification of notes………………………………………………………………………………………………………. 4 1.3 Personnel qualifications…………………………………………………………………………………………………… 4 1.4 Dangers of failure to observe the safety notes…………………………………………………………………….. 4 1.5 Safety-conscious working………………………………………………………………………………………………… 5 1.6 Safety instructions for the operator……………………………………………………………………………………. 5 1.7 Safety notes for installation, maintenance and inspection work……………………………………………… 5 1.8 Unauthorised modification and changes…………………………………………………………………………….. 6 1.9 Intended use………………………………………………………………………………………………………………….. 6 1.10 Warranty………………………………………………………………………………………………………………………. 6 1.11 Transport and packaging………………………………………………………………………………………………… 6 1.12 Environmental protection and recycling……………………………………………………………………………. 7
2 Technical Data……………………………………………………………………………………………………………………… 8 3 Design and function……………………………………………………………………………………………………………. 10
3.1 Air dehumidification – general note…………………………………………………………………………………… 10 3.2 Unit description…………………………………………………………………………………………………………….. 13 4 Assembly…………………………………………………………………………………………………………………………… 15 4.1 Setting up the unit…………………………………………………………………………………………………………. 15 4.2 Unit transport………………………………………………………………………………………………………………… 15 5 Electrical wiring………………………………………………………………………………………………………………….. 16 5.1 General notes……………………………………………………………………………………………………………….. 16 5.2 Electrical wiring diagram………………………………………………………………………………………………… 16 6 Commissioning………………………………………………………………………………………………………………….. 17 7 Condensate removal…………………………………………………………………………………………………………… 22 8 Troubleshooting and customer service……………………………………………………………………………….. 24 9 Shutdown…………………………………………………………………………………………………………………………… 25 10 Care and maintenance………………………………………………………………………………………………………… 26 10.1 Care and maintenance…………………………………………………………………………………………………. 26 10.2 Maintenance protocol…………………………………………………………………………………………………… 28 11 Exploded view of unit and spare parts………………………………………………………………………………… 29 11.1 Exploded view of the unit……………………………………………………………………………………………… 29 11.2 Spare parts list……………………………………………………………………………………………………………. 30 12 Index………………………………………………………………………………………………………………………………….. 32
3

REMKO LTE Eco series

1 Safety and usage instructions
1.1 General safety notes
Carefully read the operating manual before commissioning the units for the first time. It contains useful tips and notes such as hazard warnings to prevent personal injury and material damage. Failure to follow the directions in this manual not only presents a danger to people, the environment and the system itself, but will void any claims for liability.
Keep this operating manual and the refrigerant data sheet near to the units.
The refrigerant used in the system is flammable. If applicable, observe the local safety conditions.

DANGER! This combination of symbol and signal word warns of a situation in which there is immediate danger, which if not avoided may be fatal or cause serious injury.
WARNING! This combination of symbol and signal word warns of a potentially hazardous situation, which if not avoided may be fatal or cause serious injury.

CAUTION!
This combination of symbol and signal word warns of a potentially hazardous situation, which if not avoided may cause injury or material and environmental damage.

Caution, risk of fire
1.2 Identification of notes
This section provides an overview of all important safety aspects for proper protection of people and safe and fault-free operation.The instructions and safety notes contained within this manual must be observed in order to prevent accidents, personal injury and material damage.
Notes attached directly to the units must be observed in their entirety and be kept in a fully legible condition.
Safety notes in this manual are indicated by symbols. Safety notes are introduced with signal words which help to highlight the magnitude of the danger in question.
DANGER!
Contact with live parts poses an immediate danger of death due to electric shock. Damage to the insulation or individual components may pose a danger of death.

NOTICE! This combination of symbol and signal word warns of a potentially hazardous situation, which if not avoided may cause material and environmental damage.
This symbol highlights useful tips and recommendations as well as information for efficient and fault-free operation.
1.3 Personnel qualifications
Personnel responsible for commissioning, operation, maintenance, inspection and installation must be able to demonstrate that they hold a qualification which proves their ability to undertake the work.
1.4 Dangers of failure to observe the safety notes
Failure to observe the safety notes may pose a risk to people, the environment and the units. Failure to observe the safety notes may void any claims for damages.

4

In particular, failure to observe the safety notes may pose the following risks:
n The failure of important unit functions. n The failure of prescribed methods of mainte-
nance and repair. n Danger to people on account of electrical and
mechanical effects.
1.5 Safety-conscious working
The safety notes contained in this manual, the existing national regulations concerning accident prevention as well as any internal company working, operating and safety regulations must be observed.
1.6 Safety instructions for the operator
The operational safety of the units and components is only assured providing they are used as intended and in a fully assembled state.
This unit can be used by children above the age of 8, as well as by people with impaired physical, sensory or mental capabilities or a lack of experience and knowledge if they are supervised or have received instruction in the safe operation of the unit, and if they understand the associated potential hazards. Children must never play with the device. Cleaning and user maintenance must not be carried out by unsupervised children.
n The units and components may only be set up, installed and maintained by qualified personnel.
n If the mains power supply line of this unit is damaged, this must be replaced by the manufacturer or their customer services department or a similarly qualified person in order to avoid any hazard.
n Do not operate units or components with obvious defects or signs of damage.
n The units may not be installed or operated in explosive environments.
n The units must not be installed or operated in atmospheres containing oil, sulphur, chlorine or salt.
n The units must be installed upright and in a stable position.
n The units and components must not be exposed to any mechanical load, extreme levels of humidity or extreme temperatures.
n All housing parts and device openings, e.g. air inlets and outlets, must be free from foreign objects. An unobstructed air inlet and air outlet must be guaranteed at all times.
n The units must not be covered during operation.
n Never stick foreign objects into the units.

n The units must not be transported while they are running.
n The units must only be transported when the condensate container is empty and the evaporator is dry.
n All electrical cables on the outside of the units must be protected against damage (e.g. by animals etc.).
n Before each change of location, the condensate container must be emptied.
n The units must be inspected by a service technician to ensure that they are safe to use and fully functional at least once yearly. Visual inspections and cleaning may be performed by the operator when the units are disconnected from the mains.
n The units shall be installed, operated and stored in a room with a floor area larger than 17 m2.
n The refrigerant R454C fulfils the requirements of the European F-Gas regulation.
n The units must not be burned, drilled or pierced.
n The units may only be operated in well ventilated areas.
NOTICE!
Extensions to the connection cable must only be conducted by authorised specialist electricians, taking into consideration the unit power consumption, cable length and local use.
NOTICE!
Work on the refrigerant system and on the electrical equipment must only be conducted by a specially-authorised specialist!
1.7 Safety notes for installation, maintenance and inspection work
n Appropriate hazard prevention measures must be taken to prevent risks to people when performing installation, repair, maintenance or cleaning work on the units.
n The setup, connection and operation of the units and its components must be undertaken in accordance with the usage and operating conditions stipulated in this manual and comply with all applicable regional regulations.
n If the mains power supply line of this unit is damaged, this must be replaced by the manufacturer or their customer services department or a similarly qualified person in order to avoid any hazard.

5

REMKO LTE Eco series

n The units must be installed upright and in a stable position.
n The units must not be exposed to direct jets of water, e.g. pressure washers etc.
n Safety devices may not be modified or bypassed.
n The units and components may only be set up, installed and maintained by qualified personnel.
n Do not operate units or components with obvious defects or signs of damage.
n The units may not be installed or operated in explosive environments.
n The units must not be installed or operated in atmospheres containing oil, sulphur, chlorine or salt.
n The units and components must not be exposed to any mechanical load, extreme levels of humidity or extreme temperatures.
n All housing parts and device openings, e.g. air inlets and outlets, must be free from foreign objects. An unobstructed air inlet and air outlet must be guaranteed at all times.
n All electrical cables on the outside of the units must be protected against damage (e.g. by animals etc.).
n The units must be inspected by a service technician to ensure that they are safe to use and fully functional at least once yearly. Visual inspections and cleaning may be performed by the operator when the units are disconnected from the mains.
n The refrigerant R454C used in the system is flammable. If applicable, observe the local safety conditions.
n Note that refrigerant may be odourless.
1.8 Unauthorised modification and changes
Modifications or changes to units and components are not permitted and may cause malfunctions. Safety devices may not be modified or bypassed. Original replacement parts and accessories authorised by the manufactured ensure safety. The use of other parts may invalidate liability for resulting consequences.
1.9 Intended use
The units are designed exclusively for drying and dehumidification purposes in industrial or commercial situations on the basis of their structural design and equipment. The units must only be operated by appropriately instructed personnel.

Any different or additional use is a non-intended use. The manufacturer/supplier assumes no liability for damages arising from non- intended use. The user bears the sole risk in such cases. Intended use also includes working in accordance with the operating and installation instructions and complying with the maintenance requirements.
The threshold values specified in the technical data must not be exceeded.
1.10 Warranty
For warranty claims to be considered, it is essential that the ordering party or its representative complete and return the “certificate of warranty” to REMKO GmbH & Co. KG at the time when the units are purchased and commissioned.
The warranty conditions are detailed in the “General business and delivery conditions”. Furthermore, only the parties to a contract can conclude special agreements beyond these conditions. In this case, contact your contractual partner in the first instance.
1.11 Transport and packaging
The devices are supplied in a sturdy shipping container. Please check the equipment immediately upon delivery and note any damage or missing parts on the delivery and inform the shipper and your contractual partner. For later complaints can not be guaranteed.
WARNING!
Plastic films and bags etc. are dangerous toys for children! Why:
– Leave packaging material are not around.
– Packaging material may not be accessible to children!

6

1.12 Environmental protection and recycling
Disposal of packaging All products are packed for transport in environmentally friendly materials. Make a valuable contribution to reducing waste and sustaining raw materials. Only dispose of packaging at approved collection points.
Disposal of equipment and components Only recyclable materials are used in the manufacture of the devices and components. Help protect the environment by ensuring that the devices or components (for example batteries) are not disposed in household waste, but only in accordance with local regulations and in an environmentally safe manner, e.g. using certified firms and recycling specialists or at collection points.
7

REMKO LTE Eco series

2 Technical Data
Unit data
Unit type Operating range, temperature Operating range, humidity Dehumidification capacity max. At 30 °C/80 % RH At 20 °C/70 % RH At 10 °C/60 % RH Max. airflow volume Compressor / condenser – design Refrigerant 2) Refrigerant quantity Power supply Max. rated current consumption Max. power consumption At 20 °C / 70 % RH Customer-provided electrical protection Type of connection Enclosure class Sound pressure level LpA 1 m 3) Sound power level LwA 1 m Electronic start safeguard Operating hours counter Power meters Hot gas defrosting Hygrostat Room temperature sensor Condensate pump, built-in Hose length (condensate pump) Delivery height (condensate pump)

°C % RH l/day l/day (DER) 1) l/day (DER) 1) l/day (DER) 1) m3/h
g V/Hz
A kW kW A
dB(A) dB(A)
m m

LTE 120 Eco 3 to 32
40 to 100 106 92,1 52,3 14,7 960
Rotary piston R454C 1300
230/1~/50 5,3 1,15 0,95 16 Y IPX4 53
61 Series Series Series Series Series Series Option 5 (10 4))
5

8

Unit type Dimensions Depth Width Height Height incl. transportation bracket Weight EDP no. EDP no. Unit with condensate pump

LTE 120 Eco

mm

750

mm

705

mm

964

mm

967

kg

70.0

618910

618915

  1. (DER) = Dehumidification output figure in accordance with DIN EN 810 2) Contains greenhouse gas according to Kyoto protocol 3) Noise level measurement DIN 3744 – KL 2 4) Max. permissible hose length
    We reserve the right to modify the dimensions and design as part of the ongoing technical development process.

9

REMKO LTE Eco series

3 Design and function
3.1 Air dehumidification general note
The correlations occurring when air is dehumidified are based on physical laws. These are depicted here in graphical form in order to provide you with a brief overview of the principles of air dehumidification
The use of REMKO air dehumidifiers
n Even if windows and doors are well insulated, water and moisture are still capable of penetrating thick concrete walls.
n The water required for setting in the production of concrete, mortar and plaster etc. may only be diffused after 1-2 months.
n Even moisture trapped in the masonry after high-water or a flood is released very slowly.
n The same is also true of moisture contained in stored materials for example.
The moisture (water vapour) released from parts of a building or materials is absorbed by the surrounding air. As a result, the moisture content increases, which ultimately gives rise to corrosion, mould, rot, peeling of paint and other unwanted damage. By way of example, the diagram below shows the corrosion rate of metal in different levels of humidity.
A

1. By heating and air exchange: The air in the room is heated in order for moisture to be removed and then this air is fed outside. All of the energy that is involved is lost together with the moist air that is released.
2. By air dehumidification: The moist air that is present within an enclosed space is continuously dehumidified in accordance with the condensation principle.
With regard to energy consumption, air dehumidification has one distinct advantage: Energy expenditure is limited exclusively to the air volumes present. The mechanical heat that is released by the dehumidification process is fed back into the room.
NOTICE! Under normal use, the air dehumidifier uses approximately 25% of the energy that is required for the “heating and ventilating” principle.

B
Fig. 1: Corrosion rate in relation to relative humidity A: Corrosion rate B: Relative humidity [%] It is evident that the corrosion rate below 50% relative humidity (RH) is low, and below 40% is negligible. The corrosion rate increases significantly above 60% RH. This threshold for damage as the result of humidity also applies to other materials, such as powdery substances, packaging, wood and electronic units. Buildings may be dried in a variety of ways:
10

Relative air humidity
Our ambient air is a gaseous mixture which always contains a certain volume of water in the form of water vapour. This volume of water is specified in g per kg of dry air (absolute moisture content).
1m3 of air weighs approx. 1.2 kg at 20 °C
Depending on the temperature, each kg of air is only capable of absorbing a certain volume of water vapour. Once this capacity has been reached, the air is referred to as “saturated” and has a relative humidity (RH) of 100%.
Relative humidity is understood to mean the ratio between the current quantity of water vapour in the air and the maximum possible quantity of water vapour at the same temperature. The ability of the air to absorb water vapour increases as the temperature rises. I.e. the maximum possible (absolute) water content becomes greater as the temperature rises.

Temp.
°C -5 +10 +15 +20 +25 +30

Water vapour content in g/m3 at humidity of

40%

60%

1.3

1.9

3.8

5.6

5.1

7.7

6.9

10.4

9.2

13.8

12.9

18.2

°C

80%

-5

2.6

+10

7.5

+15

10.2

+20

13.8

+25

18.4

+30

24.3

100% 3.3 9.4 12.8 17.3 23.0 30.3

Drying materials Building materials and structures are capable of absorbing considerable volumes of water, such as brick 90-190 l/m³, heavy concrete 140-190 l/m³ and limestone 180-270 l/m³. The drying of moist materials such as masonry is effected as follows: The moisture moves from the inside of the material to its surface.
Fig. 2: Drying damp masonry n Evaporation occurs on the surface = Transfer
of water vapour to the ambient air n The air containing water vapour is constantly
circulated through the REMKO air dehumidifier. The air is dehumidified and, slightly heated, leaves the unit in order to re-absorb water vapour n In this way, the moisture contained in the material is reduced gradually The material is dried! The accumulated condensate is collected in the unit and drained off from there.

Fig. 3: Extracting and collecting condensate

11

REMKO LTE Eco series

Functional principle of the air dehumidifier
As it flows through or over the evaporator, the air stream is cooled to dew point. The water vapour condenses, and is collected in a condensate trap from where it is drained off.

1

2

A

B C

a

Fig. 4: Functional principle of the air dehumidifier
1: Evaporator 2: Condenser A: Air temperature

B: Air direction C: Humidity a: Progression

The condensation of water vapour
Because the capacity for the maximum possible volume of water vapour increases as the air is heated, the volume of water vapour contained remains constant and so relative humidity falls.
In contrast, because the capacity for the maximum possible volume of water vapour decreases as the air is cooled, the volume of water vapour contained remains constant and so relative humidity increases. If the temperature continues to fall, the capacity for the maximum possible volume of water vapour is reduced so much so that it is ultimately equal to the volume of water vapour contained in the air.
This temperature is referred to as the dew point. If the air is cooled to below dew point, the volume of water vapour in the air will become greater than the maximum possible volume of water vapour. At this point, the water vapour begins to precipitate. It then condenses to water. Humidity is then removed from the air.

Examples of condensation include steamed-up window panes in winter, or the moisture on the outside of a cold drinks bottle. As the relative humidity of the air increases, so too does the dew point, making it easier for the temperature to fall below it.
Condensation heat The energy transferred to the air from the condenser consists of: 1. the amount of heat derived beforehand in the
evaporator 2. the electrical drive energy 3. the condensation heat released by the lique-
fying of the water vapour.

12

Energy must be supplied when liquid is converted into a gas. This energy is designated as evaporation heat. It does not cause any increase in temperature, but is required to convert a liquid into a gas. Conversely, energy is released when gas is liquefied, this is designated as condensation heat.
The amount of energy from evaporation heat and condensation heat is the same.
For water, this is: 2250 kJ/kg (4.18 kJ = 1kcal)
From this it is evident that the condensation of water vapour causes a large quantity of energy to be released. With drying operations, a heat cycle is created, whereby heat is consumed for evaporation and released for condensation.
Generally speaking, the time required for the drying process is not only dependent on the output of the unit, but is determined to a greater extent by the speed at which the material or building section loses its moisture.
3.2 Unit description
The units have been designed for universal and straightforward air dehumidification.
Their compact dimensions allow the unit to be transported and set up with ease.
The units operate in accordance with the condensation principle and are equipped with a hermetically sealed refrigerant system, low-noise and lowmaintenance fan, operating hours and energy counter as well as a connection cable with plug. Fully-automatic electronic controller, a condensate container with integrated overflow protection in addition to connection ports for direct condensate drainage help to ensure continuous fault-free operation.
The units conform to the fundamental health and safety requirements of the appropriate EU stipulations. The units are dependable and offer ease of operation.
Locations at which units are used
The units are used in all locations, where dry air is a must and where economic consequential damage (such as that caused by mould) must be prevented.

The units may be used for the drying and dehumidification of areas such as:
n New buildings, industrial buildings n Basements, storage rooms n Archives, laboratories n Weekend homes, caravans n Bathrooms, wash rooms and changing rooms
etc.
Operating sequence
Switching on the unit puts the electrical control into operation. The green “COMP. ON” indicator light on the control panel illuminates. Due to an automatic pressure equalisation, the units start with a time delay of around 10 seconds.
The fan extracts the moist room air through the dust filter, evaporator and the condenser behind.
Heat is removed from the room air on the cold evaporator. The air is then cooled to below dew point. The water vapour contained in the room air is then deposited as condensate or rime on the evaporator fins.
If the temperature sensor here measures a pre-set minimum, it activates a timer with a 30 minute delay. If the evaporator temperature stops increasing during this period, the cooling cycle switches to hot gas defrosting after the timer cycle.
The fan remains out of operation during the defrosting phase.
As soon as the rime (ice) has been defrosted and the temperature at the probe has increased, the unit switches back to normal dehumidification mode.
If the room temperature is sufficiently high, the surface of the fins will not be cold enough for rime formation to occur, rendering defrosting unnecessary. Therefore, the air dehumidifiers work economically.
The cooled and dehumidified air is re-heated by the condenser (heat exchanger), and blown back into the room through the outlet grille. The processed, dry, heated air then re-mixes with the room air.
Continuous circulation of the room air through the unit gradually reduces the relative humidity (% RH) in the room to the desired humidity level. Depending on the room temperature and the humidity, only 30-40 % electrical energy is required, in accordance with the output of the unit.

13

REMKO LTE Eco series

Fig. 5: Air dehumidification operating principle
A: Dehumidified room air B: Moist room air 1: Fan

2: Condenser 3: Evaporator 4: Compressor

14

4 Assembly
4.1 Setting up the unit
For the best economic and safe use of the units, the following notes must be followed in full:
n The units must be set up in an upright and level position, to ensure that the condensate can drain freely
n To ensure optimum air circulation, the units should be set up in the centre of the room, where possible
n It must be ensured that the air can be sucked in on the front of the unit and blown out of the rear of the unit without obstruction
n Observe a minimum clearance of 50 cm from walls at all times
n Units must never be set up in the immediate vicinity of heaters or other sources of heat
n The room being dried or dehumidified must be closed to the surrounding atmosphere
n Air circulation is improved if the unit is set up approx. 1 m above the ground
n Avoid having opened windows and doors etc., and avoid frequent entry to or exit from the room as much as possible
n If the units are to be used in dusty environments, appropriate care and maintenance measures should be taken in accordance with the relevant conditions
n The output of the unit is entirely dependent on the conditions inside the room, room temperature, relative humidity and observance of the set-up instructions
n The units may not be used in environments containing a great deal of dust or chlorine, or in places with atmospheres containing ammonia

NOTES: ­ Keep windows and doors closed! ­ Keep at least 0.5 m away from walls. ­ Maintain adequate clearance from heaters
or other sources of heat.
4.2 Unit transport
For easy transportation, the units are equipped with 2 large wheels and an ergonomic transportation handle and protective frame. This can also be dismantled easily if required. When transporting the units, observe the following: 1. Before each change of location, switch off
the unit and remove the power plug from the mains socket. 2. Only transport the units in an upright position where possible. 3. If the unit was transported on its side, you must wait 1 hour with the unit in an upright position before switching on.
NOTICE! Beware of dripping condensate. After switching off the units, the evaporator may continue to defrost under the influence of the ambient temperature.
WARNING! The mains cable must never be used as a pull cord or fixing device.

Fig. 6: Setting up the unit 15

REMKO LTE Eco series

5 Electrical wiring
5.1 General notes
n The units are operated with 220-240 V/50 Hz alternating current
n The electrical connection is made using a builtin mains cable with earthed safety plug
WARNING!
The electrical connection to the units must be made at feed-points with residual current devices in accordance with VDE 0100, Section 704. When installing the units in extremely damp environments such as laundry rooms, showers etc., the unit must secured with a residual current device provided by the customer in accordance with the regulations.
5.2 Electrical wiring diagram

n Extensions to the connection cable may only be carried out by authorised electricians, subject to the length of the cable, connected load of the unit and taking into consideration how the unit is used at its location
n The LTE 120 Eco is intended for operation on a power supply network with a system impedance Zmax at the transfer point (house connection) of max. 0.45 Ohm. The user must ensure that the unit is only operated on a power supply network that meets these requirements. If necessary, the system impedance can be obtained from the local power supply company
CAUTION!
All cable extensions must only be used in fully un-reeled or reeled off condition.

B C

A
9
10
12 34 56 78

PE PE PE PE

3

5

6

78

11 PE L N

1

2

4

Fig. 7: Electrical wiring diagram

A: Control board B: Display circuit board C: Optional 1: Power supply 2: Compressor 3: Solenoid valve 4: Fan motor

5: Evaporator probe 6: Condenser probe 7: RESET button 8: Humidity probe 9: Fuse 3.15A 250V 10: Fuse 1A 11: Condensate pump

We reserve the right to modify the dimensions and design as part of the ongoing technical development process.

16

6 Commissioning
Before commissioning the unit or if local requirements dictate, the air-inlet grille and air-outlet grille must be checked for contamination.
NOTICE!
A contaminated grille or filter must be cleaned or replaced immediately.
Important notes prior to commissioning n All extensions to the electrical connection must
be of a sufficient cable size and must only be used fully rolled out or unrolled. n Never use the power supply connection cable as a pull cord. n After being switched on, the units operate fullyautomatically until switched off by the float when the condensate container is full. n The condensate container must be inserted properly. n In order to prevent damage to the condenser, the units are equipped with a mechanism that prevents the compressor from being immediately switched back on after it is switched off The compressor only switches back on after a waiting time of approx. 1 minute!
NOTICE!
In room temperatures below 10 °C and relative humidity below 40%, economical use of the unit can no longer be guaranteed.

Starting the unit
Start the unit as follows:
1. Plug the unit’s power plug into a properly installed and fused mains socket (230V/50 Hz).
If you connect the dehumidifier to the mains, the unit should be switched off (not operating). The segment display and LED indicators illuminate for 3 seconds (the humidity display shows “88” and the hour counter display shows “88888.8”). After that the segment display for the humidity [3] shows the environmental humidity and the display for the operating hours counter and the energy counter [6] shows the operating hours counted for the compressor.
2. Set up a collection container or transfer the condensate hose to a suitable drain.
3. Actuate the “ON / OFF” key.
The green “COMP. ON” indicator light illuminates. The unit switches on with a time delay of around 10 seconds and then runs in continuous operating mode.
The unit will now operate fully-automatically until the desired relative humidity (% RH) has been reached.
Automatic restart after power failure:
If the electrical power fails or if the power plug is pulled out during operation, the unit switches off. When the unit is switched back on again or if the power plug is put back in again the unit starts up again automatically after a safety delay time of 70 seconds.

17

REMKO LTE Eco series

Control and display panel:

12 11 10

987

kWh

13

6

5

Fig. 8: Control panel

1 ON / OFF key:
After actuating the ON / OFF key whilst switched off, the unit starts as soon as the humidity in the room (RH) is 4 % higher than the target value set for the humidity in the room. The start sequence is: Fan motor ON solenoid valve ON 10 seconds and then OFF compressor ON. If the room humidity is lower than the target value set for the humidity in the room, then the “COMP. ON” indicator flashes and the unit is in standby mode (not operating).
If the ON / OFF key is actuated during operation, the unit and the COMP ON” display switch off. The ON / OFF delay time of the compressor is 1 minute.

2 SET HUMIDITY – Desired humidity setting:
After the unit is switched on, the target room humidity can be adjusted up or down by pressing the arrow keys. As soon as the room humidity reaches the target humidity set, the compressor and the fan motor stop. The target room humidity set is displayed for 3 seconds during the adjustment and then reverts to the current measured room humidity.

NOTE:
n If the unit is restarted it reverts to the previous setting
n The adjustment steps for the target humidity are 5 % ( RH) per key press. The adjustment range for the target humidity should lie between 30 % and 70 % ( RH)

4

3

2

1

If the humidity lies below the target humidity set (i.e.: rRH < -3%), the compressor and the fan motor stop. If the humidity is higher than the target humidity set (i.e.: rRH > +4%), the unit restarts with a 3 minute delay.
Example: If the target humidity = 50 % RH, but the room humidity is 47 % RH, then the compressor and fan motor stop and the “COMP. ON” indicator flashes (standby display!). While the room humidity rises to 54 % RH, the unit restarts with a 3 minute delay time in accordance with the start function sequence.
The target room humidity value must be set within 3 seconds by pressing the up arrow or down arrow keys. Then the current room humidity is displayed again.
3 Segment display for humidity, room temperature and malfunction code:
The standard display is the current measured room humidity. The humidity value to be changed is displayed for 3 seconds by pressing one of the arrow keys [2] to set the target room humidity. If the ROOM TEMP key is pressed, the current measured room temperature is shown in the display for 5 seconds and then the display automatically switches back to the current measured room humidity.

18

Function or situation Power plug is plugged in, the unit is switched off The unit starts During the adjustment of the target room humidity
Upon actuation of the ROOM TEMP. Key
Is a malfunction is present

Segment display
Current measured room humidity is displayed
Current measured room humidity is displayed The target room humidity set is displayed
The current measured room temperature is displayed for 5 secs Error code is displayed

4 Room temperature key (RT) – To display the room temperature:
By actuating the “ROOM TEMP.” key, the red RT °C indicator illuminates and the current room temperature is displayed for 5 seconds in the segment display [3]. Then the current measured room humidity appears again automatically.
5 COUNTED key – to display the electrical power consumed or the compressor run-time counted:
By actuating the “COUNTED” key, the “kWh” indicator illuminates and the electrical power (kW) consumed by the unit is displayed in the segment display [6].
Actuating the “COUNTED” key again switches off the “kWh” indicator and the operating hours (h) of the compressor are displayed in the segment display [6].
6 Segment display – display of the electrical power consumed or the compressor run-time counted:
In standby mode, the current compressor run-time (h) is displayed in the segment display [6] or, by actuating the “COUNTED” key, the electrical power consumed (kWh).
The segment display [6] shows the operating hours of the compressor or the electrical power consumed by the unit. The display shows values from “0.0” to “99999.9”

7 COMP. ON INDICATOR:
If the compressor is running, this indicator is illuminated. If the compressor is stops, the indicator flashes.
The unit has a 3 minute restart delay for the compressor as a safety function. This means that the compressor requires 3 minutes to restart after it has stopped due to having reached the target room humidity set. The “COMP. ON” indicator flashes during the 3-minute protection period
8 DEFROST INDICATOR:
If the temperature of the evaporator (Te) is <= 1 °C and the compressor runs for more than 5 minutes, the DEFROST indicator flashes and the 30-minute delay timer for the defrost function starts.
Defrost function: Compressor still ON, fan motor OFF, solenoid valve ON, DEFROST indicator illuminates. If the temperature of the evaporator (Te) is >= 3 °C then the defrost function stops and the DEFROST indicator extinguishes.
Function of the unit after defrost: Compressor ON, fan motor ON, solenoid valve OFF, DEFROST indicator off
9 “CHECK” indicator:
If there is an abnormal situation (malfunction), the CHECK indicator [9] illuminates or flashes. If the temperature probe (Te or Tc) or the humidity probe is defective, the unit switches off and the indicator light [9] illuminates. Then the error code (E1, E2, E4 or E5) is displayed in the segment display [3].
If the temperature of the condenser (Tc) is over 50 °C while the unit is running, the indicator light (CHECK) flashes.
There are two types of protective function for the Tc over-temperature (50 °C):

19

REMKO LTE Eco series

If Tc is >50 °C and the compressor runs within 5 minutes, the unit switches off and the error code “E3” is shown in the segment display [3] and the CHECK indicator [9] flashes. In this case, the fault cannot be reset with a key press. The unit power plug must be removed from the socket so that the unit is completely de-energised. Then, the dehumidifier can be restarted after a restart delay of 70 seconds.
If Tc is > 50 °C and the compressor runs over 5 minutes, the compressor stops but the fan motor continues to run for a further 30 minutes. The segment display flashes with fault code E3 during this time. After 30 minutes the unit is restarted for normal function with the previous setting.
NOTE:
n Within this 30 minute protective period, the “ON / OFF” key can be pressed in order to switch the unit off. If the “ON / OFF” key is then pressed, the unit restarts after a delay time of 1 minute.

10 RT °C INDICATOR: If the “ROOM TEMP” key is pressed, the RT indicator [10] illuminates for 5 seconds.
11 “FULL TANK” DISPLAY: Is not used
12 kWh INDICATOR: By actuating the “COUNTED” key, the “kWh” indicator illuminates and the electrical power in kW consumed by the unit is displayed in the segment display [6].
13 kWh key: By pressing the “kWh” key, the control panel can be activated in a de-energised state. This allows the consumed electrical power or the counted compressor running time to be displayed without current.

20

Function table:

Functions
Comp. ON LED Check LED Defrost LED Full Tank LED Solenoid valve
Fan motor
Compressor Humidity segment display [3] Operating hours / power consumption segment display [6]

Power plug inserted OFF
(no operation) OFF OFF OFF
OFF
OFF
OFF

Operating status: Unit operating or in standby

Standby (no operation) r RH <-3 %

The unit starts r RH >+4 %

Flashes OFF

ON OFF

OFF

OFF

OFF OFF OFF

Is not used
ON for 10 sec. then OFF
ON after 10 sec.
ON after 10+0.5 sec

Defrost function

30 min. timer expires if Te<=1 °C ON OFF
Flashes

After the 30 mins. defrost timer function has passed
ON
OFF
ON
If
Te >=3 °C,
then OFF

OFF ON

ON If Te >=3 °C, then OFF OFF If Te >=3 °C, then ON

ON

ON

Current room humidity is displayed

Operating hours or power consumption are displayed (changeover by actuating the “h/kWh” key)

21

REMKO LTE Eco series

7 Condensate removal
Depending on the air temperature and the relative humidity, condensed water will drip into the condensate trap either continuously or only during the defrosting phases and can drain through the hose connection. Unit operation with hose connection Due to its high dehumidification performance, the unit is designed to drain the condensate directly into a suitable collection container via a sloping hose.
NOTICE! There is no overflow protection here.
NOTICE! Be sure to ensure that the edge of the collection container is not higher than the angled probe.
The hose is connected directly to the Ø 14 mm angled probe, which protrudes from the front of the device flap when delivered.

Fig. 10: Angled probe with extension
2. Ensure that there are no kinks in the hose!
In unattended permanent operating mode, the condensate should preferably be drained into a lowerlevel drain. If using a collection container (pan, bucket, etc.), the unit must be placed at a correct height.
Unit operation with condensate pump (optional)
The built-in condensate pump is located in the lower part of the device behind the cover flap. This is already connected via a hose with the shortened angled probe. Due to the shortened angled probe, the rubber passage is now free. The drain hose can be routed either directly through the base plate or over the free rubber passage to the outside.

Fig. 9: Hose connection
Connect the hose as follows:
1. Plug hose with inside diameter 14 mm onto the angled probe and secure this with a hose clamp to prevent it slipping off.

Fig. 11: Drain hose passage through the cover flap

22

Fig. 12: Drain hose passage through the base plate
NOTICE! Unit operation with condensate pump is only possible with units that were shipped with the pump installed.
NOTICE! If the condensate pump runs for an extended period of time, the condensate trap and the hoses must be checked for contamination at regular intervals.
Unit operation without pump is possible at any time.
23

REMKO LTE Eco series

8 Troubleshooting and customer service
The unit and components are manufactured using state-of-the-art production methods and tested several times to verify that they function correctly. However, if malfunctions do occur, please check the functions as detailed in the list below. Please inform your dealer if the unit is still not working correctly after all function checks have been performed!

Operational malfunctions

Malfunction

Remedial measures
Check the setting of the “ON / OFF” switch. The green “COMP. “ON” indicator must illuminate

The unit does not start

Check the power supply and the power fuse provided by the customer 230V/1~/50 Hz
Check the power plug and the cable for damage
Check the setting of the desired humidity. The pre-set value must be lower than the relative humidity in the room

The red CHECK (malfunction) indicator light illuminates

The cooling cycle is overloaded or overheated (see “CHECK” indicator in chapter “Commissioning”)
Before starting the unit again, first identify the cause of the malfunction. (see “CHECK” indicator in chapter “Commissioning”)
Check the room temperature. The operating range of the unit is between 3°C and 32°C

The unit runs but does not form any condensate

Check humidity of the air, min. 40 % RH required
Check the dust filter for contamination and clean or replace if necessary
Check the evaporator and condenser fins for contamination and clean if necessary
Check the evaporator for ice or rime formation. If ice has formed, check the functionality of the automatic defrost and the temperature sensor
If the unit fails to function correctly after the checks have been carried out, contact an authorised specialist

WARNING!
Work on the refrigerant system and on the electrical equipment must only be conducted by a speciallyauthorised specialist!

24

Display of error codes Error codes are displayed in the segment display [1].
1

Fig. 13: Segment display

Error code description:

Error code E1 E2 E3

Error description Evaporator temperature probe (Te) defective Condensate temperature probe (Tc) defective Compressor runs within 5 minutes and the condenser temperature (Tc) > 50 °C

E3 flashes E4 E5

Compressor runs over 5 minutes and the condenser temperature (Tc) > 50 °C Humidity / temperature probe (hygrostat) defective (room humidity measured > 100 % RH) Humidity / temperature probe (room temperature Rt)

9 Shutdown
Actuate the “ON / OFF” key, the “COMP. ON” indicator must extinguish.
If the units are inactive for longer periods, disconnect them from the mains power supply.
Dry the condensate trap with a clean cloth. Remove the hose parts and flush with air.
Beware of dripping condensate!
When storing the unit, cover with a plastic sheet / foil if necessary and store in an upright position in a sheltered and dry location.

The units are not suitable for stacking.

Fig. 14: Do not stack the units!

25

REMKO LTE Eco series

10 Care and maintenance
10.1 Care and maintenance
General notes
Regular care and maintenance is fundamental to a long service life and fault- free operation of the unit.
All moving parts have a low-maintenance permanent coat of lubricant. The refrigerant system is designed as a hermetically sealed system and may only be repaired by a specialist.
DANGER!
Before undertaking any work on the units, the mains plug must be removed from the mains socket.
n Observe the regular care and maintenance intervals
NOTICE! Check the inlet and outlet grille for contamination on a regular basis.
n In accordance with the operating conditions, the units must be checked as and when required, but at least once per year, by a specialist to ensure that they are in a condition that is safe to use
n Keep the units free of dust and other debris n Only clean the units with a dry or moistened
cloth n Never subject to direct jets of water
(e.g. pressure washers etc.) n Never use abrasive or solvent-based cleaners n Even with heavy contamination, use only suit-
able cleaners

Cleaning the dust filter
NOTICE! Check the inlet and outlet grille and the dust filter for contamination on a regular basis.
Pull the protection grid forwards and then remove upwards. Then remove the dust filter which has now been released. Light contamination of the dust filter may be remedied with careful blowing or suction. Heavier contamination may be remedied by rinsing the filter in a lukewarm (max. 40 °C) soap solution. Finally, always rinse the filter carefully with clear water and allow to dry! Before refitting the dust filter, ensure that its fully dry and that no damage has been sustained.
NOTICE! Heavily contaminated dust filters must be replaced with new parts. Only original replacement parts may be used.
The units may only be operated with the dust filter in place.

26

Cleaning the units The unit housing must be opened to allow the inside of the unit to be cleaned and to provide access to electrical components.
NOTICE! Adjustment and maintenance work may only be carried out by authorised qualified technicians.
1. Loosen the two fastening screws [C]. 2. Lift up the service flap and unhook the top
lugs.

4. Clean the evaporator fins, for example with a lukewarm soap solution (or similar).
NOTICE! When cleaning the exchanger, particular care must be taken because the fine aluminium fins bend very easily.
5. Never subject to direct jets of water. 6. Rinse with clean water to remove any
remaining soap. 7. Clean the internal surfaces of the unit and
the fan blade. 8. Clean the condensate trap and the connec-
tion nozzle. 9. Once cleaning has been completed, the unit
should be dried. Take particular care with electrical components! 10. Re- install all dismantled components in reverse order. 11. Carry out a unit function check and electrical safety check.

C
3. Clean the condenser fins by blowing, with suction or using a smooth brush.

WARNING!
An electrical safety check must be carried out in accordance with VDE 0701 after any work on the units.

27

REMKO LTE Eco series

10.2 Maintenance protocol

Unit type: ——————————–

Unit number: —————————————

Unit cleaned – outside Unit cleaned – inside Fan blade cleaned Fan housing cleaned Condenser cleaned Evaporator cleaned Fan function checked Air-inlet grid with filter cleaned Unit checked for damage Safety devices checked All fastening screws checked Electrical safety check Test run

00000000011111111112 12345678901234567890

Comments: ………………………………………………………………………………………………………………………………… ………………………………………………………………………………………………………………………………………………………..

01. Date: …………. …………………………. Signature

02. Date: …………. …………………………. Signature

03. Date: …………. …………………………. Signature

04. Date: …………. …………………………. Signature

05. Date: …………. …………………………. Signature

06. Date: ………… …………………………. Signature

07. Date: …………. …………………………. Signature

08. Date: …………. …………………………. Signature

09. Date: …………. …………………………. Signature

10. Date: …………. …………………………. Signature

11. Date: ………… …………………………. Signature

12. Date: …………. …………………………. Signature

13. Date: …………. …………………………. Signature

14. Date: …………. …………………………. Signature

15. Date: …………. …………………………. Signature

16. Date: ………… …………………………. Signature

17. Date: …………. …………………………. Signature

18. Date: …………. …………………………. Signature

19. Date: …………. …………………………. Signature

20. Date: …………. …………………………. Signature

Unit to be maintained only by authorised specialists in accordance with the statutory regulations.

28

30 29
49

17

41 51

28 45 46 47 48

16

27

26

14

52

25

44

42 43

24

13 12

10

41

50

11

23

8 9

11 Exploded view of unit and spare parts
11.1 Exploded view of the unit
We reserve the right to modify the dimensions and design as part of the ongoing technical development process.
29

40

37

39

36 35

38

33

34

6 7

22

5

21

20

4

32

3

18 19 31

2

1

REMKO LTE Eco series
11.2 Spare parts list
No. Designation 1 Lock for sealing flap 2 Protective intake grille 3 Dust filter 4 Unit housing 5 Control panel 6 Filter grill, interior 7 Evaporator fin package cpl. 8 NTC evaporator probe 9 NTC condenser probe 10 Top separating panel 11 Reinforcement plate above, left 12 Carrier frame above 13 Reinforcement plate above, right 14 Drying filter 16 Solenoid valve 17 Side covering, right 18 Rubber ring for condensate passage 19 Sealing flap 20 Angled probe 21 Extension for angled probe 22 Condensate tray 23 Reinforcement plate below, left 24 Carrier frame below 25 Reinforcement plate below, right 26 Fan blade 27 Engine mounting cpl. 28 Drive clutch 29 Fan motor 30 Transportation bracket 31 Stand 32 Rubber stopper, stand (2 pieces / set) 33 Side covering, left 34 Humidity / temp. probe cover 35 Humidity / temp. probe

LTE 120 Eco
On request by providing the serial number

30

No. Designation 36 Humidity / temp. probe holder 37 Base plate 38 Hub cover cap 39 Wheel screw 40 Wheel 41 Wheel 42 Axle 43 Axle fastening 44 Compressor, cpl. 45 Housing cover 46 Operating condenser 47 Control board 48 Switch cabinet housing 49 Rear wall, housing parts 50 Strain relief 51 Mains cable with plug 52 Vapor-liquid separator
Spare parts not illustrated Condensate pump Fuse holder for 5 x 20 mm fuse Fuse 5 x 20 mm, 1A Condensate hose 45 cm Hose clip Condensate hose 5 m

LTE 120 Eco
On request by providing the serial number
On request by providing the serial number

To ensure the correct delivery of spare parts, please always provide the unit type with its corresponding serial number (see name plate).

31

REMKO LTE Eco series

12 Index
A
Air dehumidification, description . . . . . . . . . . . . 10 Automatic restart after power failure . . . . . . . . . 17
C
Care . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26 Care and maintenance . . . . . . . . . . . . . . . . . . . 26 Clean dust filter . . . . . . . . . . . . . . . . . . . . . . . . . 26 Clean units . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27 Cleaning the dust filter . . . . . . . . . . . . . . . . . . . 26 Cleaning the units . . . . . . . . . . . . . . . . . . . . . . . 27 Commissioning . . . . . . . . . . . . . . . . . . . . . . . . . 17 Condensate removal . . . . . . . . . . . . . . . . . . . . . 22 Condensate trap, function . . . . . . . . . . . . . . . . . 12 Condensation heat . . . . . . . . . . . . . . . . . . . . . . 12 Condensation of water vapour . . . . . . . . . . . . . . 12 Control and display panel: . . . . . . . . . . . . . . . . . 18 Customer service . . . . . . . . . . . . . . . . . . . . . . . 24
D
Display of error codes . . . . . . . . . . . . . . . . . . . . 25 Disposal of equipment . . . . . . . . . . . . . . . . . . . . . 7 Drying materials . . . . . . . . . . . . . . . . . . . . . . . . 11
E
Electrical wiring . . . . . . . . . . . . . . . . . . . . . . . . . 16 Electrical wiring diagram . . . . . . . . . . . . . . . . . . 16 Environmental protection . . . . . . . . . . . . . . . . . . . 7 Error codes, display and description . . . . . . . . . 25 Exploded view drawing . . . . . . . . . . . . . . . . . . . 29 Exploded view of the unit . . . . . . . . . . . . . . . . . 29
L
Locations for use . . . . . . . . . . . . . . . . . . . . . . . . 13
M
Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . 26 Malfunction . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24

O
Operating sequence . . . . . . . . . . . . . . . . . . . . . 13 Operational malfunctions . . . . . . . . . . . . . . . . . . 24 Ordering spare parts . . . . . . . . . . . . . . . . . . . . . 30
R
Relative air humidity . . . . . . . . . . . . . . . . . . . . . 11
S
Safety Dangers of failure to observe the safety notes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 Identification of notes . . . . . . . . . . . . . . . . . . . 4 Instructions for the operator . . . . . . . . . . . . . . 5 Note for inspection work . . . . . . . . . . . . . . . . . 5 Note for installation work . . . . . . . . . . . . . . . . 5 Note for maintenance work . . . . . . . . . . . . . . 5 Personnel qualifications . . . . . . . . . . . . . . . . . 4 Safety-conscious working . . . . . . . . . . . . . . . . 5 Unauthorised modification . . . . . . . . . . . . . . . 6 Unauthorised replacement part manufacture . 6
Setting up the unit . . . . . . . . . . . . . . . . . . . . . . . 15 Shutdown . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25 Spare parts list . . . . . . . . . . . . . . . . . . . . . . . . . 30 Starting the unit . . . . . . . . . . . . . . . . . . . . . . . . . 17
T
Transporting the unit . . . . . . . . . . . . . . . . . . . . . 15 Troubleshooting and customer service . . . . . . . 24
U
Unit transport . . . . . . . . . . . . . . . . . . . . . . . . . . 15
W
Warranty . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 Water vapour content . . . . . . . . . . . . . . . . . . . . 11 Water vapour, condensation . . . . . . . . . . . . . . . 12

32

33

REMKO LTE Eco series
34

REMKO QUALITY WITH SYSTEMS
Air-Conditioning | Heating | New Energies

REMKO GmbH & Co. KG Klima- und Wärmetechnik
Im Seelenkamp 12 32791 Lage

Telephone +49 (0) 5232 606-0 Telefax +49 (0) 5232 606-260

E-mail URL

info@remko.de www.remko.de

Hotline within Germany +49 (0) 5232 6 06-0
Hotline International +49 (0) 5232 606-130

We reserve the right to make technical changes, and provide no guarantee as to the accuracy of this data!

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Related Manuals