Albeo® LED RoundHigh Bay IP65 Luminaire
ARC Series
Installation Guide
ALB086 | A-1010914
ARC Series Albeo LED Round High Bay IP65 Luminaire
BEFORE YOU BEGIN
Read these instructions completely and carefully.
WARNING
RISK OF ELECTRIC SHOCK
- Turn power off before inspection, installation or removal.
- Properly ground electrical enclosure.
RISK OF FIRE
- Follow all NEC and local codes.
- Use only UL approved wire for input / output connections. Minimum size 18 AWG.
Save These Instructions
Use only in the manner intended by the manufacturer.
If you have any questions, contact the manufacturer at
LightingProdInfo@gecurrent.com.
This device complies with Part 15 of the FCC Rules. Operation is subject to
the following two conditions: (1) This device may not cause harmful
interference, and (2) this device must accept any interference received,
including interference that may cause undesired operation. CAN
ICES-005(A)/NMB-005(A)
Note: This equipment has been tested and found to comply with the limits
for a Class A digital device, pursuant to part 15 of the FCC Rules. These
limits are designed to provide reasonable protection against harmful
interference when the equipment is operated in a commercial environment. This
equipment generates, uses, and can radiate radio frequency energy and, if not
installed and used in accordance with the instruction manual, may cause
harmful interference to radio communications. Operation of this equipment in a
residential area is likely to cause harmful interference in which case the
user will be required to correct the interference at his own expense.
IP rating: IP65, can be used in wet locations.
Do not use fixture in any corrosive environments.
Do not operate outside rated fixture voltage.
Prepare Electrical Wiring
Electrical Requirements
- The LED luminaire must be connected to the mains supply according to its ratings on the product label
- Class 1 wiring should be in accordance with NEC.
Grounding Instructions
- The grounding and bonding of the overall system shall be done in accordance to local electric code of the country where the luminaire is installed.
-
Screw in hook and tighten lock screw. Base is 1/2” NPT.
-
Hang fixture and lock hook screw to secure.
-
Turn off power, connect AC wire. Black wire to L, white wire to N, green wire to GND.
To access dimming leads, pre-wired sensor connection must be severed.
Sensor Installation -
For sensor installation: Remove cover cap. Twist in sensor.
-
Finished installation – sensor pre-wired for plug-and-play, internal wiring diagram shown
-
Optional: Secure tether to the fixture
-
Optional: Secure refractor to the fixture
-
Optional: Secure wireguard to fixture
-
Optional: Secure drop lens to refractor
Option: Connecting with 0-10V Dimmer
- Fixture with sensor.
- Cut the dimming wire which has been connected with sensor base and driver.
- Pull out the dimming wire and peel off the jacket for appropriate length
- Connect the dimming wires with other dimmer or sensor. Gray wire to DIM-, Purple wire to DIM+, Pink wire to sensor input.
Note: the pink wire can only connect with 12V sensor. If external sensor is not needed, pink wire should be well isolated.
Option: Battery Backup Installation
How to confirm the dimming wire version of high bay you received before installation:
- High bays with Date Code ”21-46” and before come with dimming wire version.
- High bays with Date Code later than “21-46”come with below two dimming wire versions.
Installation Steps
- Tighten the hooks. Fix the junction box via the lower hook.
- Connect the input wire of backup battery into the junction box via the gray port, then tighten the nut. Tighten the screws for securing both hooks.
- In a visible location on the fixture, attach the label: “ASSEMBLE PART YH27FA-40WL, ONLY WITH PART ARC014abccQVddAQe,ARC021abccQVddAQe , ARC028abccQVddAQe,ARC033abccQVddAQe.” This label is provided together with this instruction sheet.
- Cut the dimming wire that was connected with fixture sensor base and driver. Reserve as much as possible the length of the dimming wire end that is connected to the driver. Then open or isolated another end that is connected with sensor base.
- Hang up the fixture and the backup battery, then tighten the hook screws.
- Cut-off the 12V aux wire(black-white/pink) in dimming cable which was connected with driver.
- Loosen the water proof connector, also the screws in connector by Ph0 screwdriver, then connect the dimming wires as below diagram.
- Open the junction box, connect fixture’s input wires with backup battery driver’s output wires. Then fasten with wire nuts.
- Through the AC wire into the junction box; Connect the input wire of backup battery with AC wires, as below diagram.
- nstall the satety tether. Lock the junction box cover and enter different mode by operate test switch or remote controller.
Notification for test switch, remote controller and LED indicator.
Test Switch:
Backup conversion kit will go into backup mode if test switch is pressed
when main supply is on, while it goes into charging mode if test switch is not
pressed. In backup mode, press the test switch for 3 seconds to end the backup
mode test.
Remote Controller Test:
Carry out 5S emergency mode test after pressing the test button once.
Press the H-T: button to enter hold test mode and press again to exit the
test.
LED Indicate:
Red Led always on: charging mode or charging full.
Red off: main power off or discharging mode
Red flash: 0.5 second fast flash-represents failure.
2 second slow flash-represents low battery voltage and needs recharging.
Wiring Diagram
www.gecurrent.com
© 2021 Current Lighting Solutions, LLC. All rights reserved. GE and the GE
monogram are trademarks of the
General Electric Company and are used under license. Information provided
is subject to change without
notice. All values are design or typical values when measured under
laboratory conditions.
ALB086 (Rev 08/24/21) Enovia – A-1010914
Documents / Resources
| GE
current ARC Series Albeo LED Round High Bay IP65
Luminaire
[pdf] Installation Guide
ALB086, A-1010914, ARC Series Albeo LED Round High Bay IP65 Luminaire, ARC
Series, Albeo LED Round High Bay IP65 Luminaire, LED Round High Bay IP65
Luminaire, Round High Bay IP65 Luminaire, High Bay IP65 Luminaire, IP65
Luminaire, Luminaire
---|---
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>