iSMA CONTROLLI SFAR-S-16DO Room Controllers iSMA Installation Guide

June 9, 2024
iSMA CONTROLLI

iSMA CONTROLLI SFAR-S-16DO Room Controllers iSMA Installation Guide

SPECIFICATION

Power supply| Voltage| 10-38 V DC; 10-28 V AC
Power consumption| 2,4 W @ 24 V DC 3 VA @ 24 V AC
Digital outputs| Transistor output max voltage 30 V DC max current 500 mA
Output protection| Output O1-O8 polymer fuse 4 A;
Output O9-O16 polymer fuse 4 A;
Galvanic isolation| Max 1500 Vrms
Interface| RS485, up to 128 devices on the bus
Baudrate| From 2400 to 115200 bps
Ingress protection| IP40 – for indoor installation
Temperature| Operating -10°C – +50°C; Storage – 40°C – +85°C
Relative humidity| 5 to 95% RH (without condensation)
Relative humidity| 5 to 95% RH (without condensation)
---|---
Connectors| Max 2.5 mm2
Dimension| 119,1 mm x 101 mm x 22,6 mm
Mounting| DIN rail mounting (DIN EN 50022)
Housing material| Plastic, self-extinguishing PC/ABS

TOP PANEL

TOP PANEL

DIGITAL OUTPUTS

DIGITAL OUTPUTS

COMMUNICATIONC

COMMUNICATION

POWER SUPPLY

POWER SUPPLY

POWER SUPPLY

WARNING

  • Note, an incorrect wiring of this product can damage it and lead to
    other hazards. Make sure the product has been correctly wired before turning the power ON.

  • Before wiring, or removing/mounting the product, be sure to turn the power OFF. Failure to do so might cause electric shock.

  • Do not touch electrically charged parts such as the power terminals. Doing so might cause electric shock.

  • Do not disassemble the product. Doing so might cause electric shock or faulty operation.

  • Use the product within the operating ranges recommended in the specification (temperature, humidity, voltage, shock, mounting direction, atmosphere etc.). Failure to do so might cause fire or faulty operation.

  • Firmly tighten the wires to the terminal. Insufficient tightening of the wires to the terminal might cause fire

TERMINALS OF THE DEVICE

TERMINALS OF THE DEVICE

iSMA CONTROLLI S.p.A. – Via Carlo Levi 52, 16010 Sant’Olcese (GE) – Italy | support@ismacontrolli.com

Modbus Dec Hex Register Name Access Description
30001 0 0x00 Version/Type Read Version and Type of the device
30002 1 0x01 Switches Read Switches state
40003 2 0x02 Baud rate Read & Write RS485 baud rate
40004 3 0x03 Stop Bits & Data Bits Read & Write No of Stop bits & Data

Bits (see 3.5.3)
40005| 4| 0x04| Parity| Read & Write| Parity bit
40006| 5| 0x05| Response Delay| Read & Write| Response delay in ms
40007| 6| 0x06| Modbus Mode`| Read & Write| Modbus Mode (ASCII or RTU)
40009| 8| 0x08| Watchdog| Read & Write| Watchdog
40013| 12| 0x0C| Default Output State| Read & Write| Default output state (after power on or watchdog reset)
40033| 32| 0x20| Received packets LSR (Least Significant Reg.)| Read & Write| **** No of received packets
40034| 33| 0x21| Received packets MSR (Most Significant Reg.)| Read & Write
40035| 34| 0x22| Incorrect packets LSR| Read & Write| No of received packets with error
40036| 35| 0x23| Incorrect packets MSR| Read & Write
40037| 36| 0x24| Sent packets LSR| Read & Write|
No of sent packets
40038| 37| 0x25| Sent packets MSR| Read & Write
40052| 51| 0x33| Outputs| Read & Write| Output state

INSTALLATION GUIDELINE

Please read the instruction before use or operating the device. In case of any questions after reading this document, please contact the iSMA CONTROLLI Support Team (support@ismacontrolli.com).

  • Before wiring or removing/mounting the product, make sure to turn the power off. Failure to do so might cause an electric shock.

  • Improper wiring of the product can damage it and lead to other hazards. Make sure that the product has been correctly wired before turning the power on.

  • Do not touch electrically charged parts such as power terminals. Doing so might cause an electric shock.

  • Do not disassemble the product. Doing so might cause an electric  shock or faulty operation.

  • Use the product only within the operating ranges recommended in the specification (temperature, humidity, voltage, shock, mounting direction, atmosphere, etc.). Failure to do so might cause a fire or faulty operation.

  • Firmly tighten the wires to the terminal. Failure to do so might cause a fire.

  • Avoid installing the product in close proximity to high-power electrical devices and cables, inductive loads, and switching devices. Proximity of such objects may cause an uncontrolled interference, resulting in an instable operation of the product.

  • Proper arrangement of the power and signal cabling affects the operation of the entire control system. Avoid laying the power and signal wiring in parallel cable trays. It can cause interferences in monitored and control signals.

  • It is recommended to power controllers/modules with AC/DC power suppliers. They provide better and more stable insulation for
    devices compared to AC/AC transformer systems, which transmit disturbances and transient phenomena like surges and bursts to devices. They also isolate products from inductive phenomena from other transformers and loads.

  • Power supply systems for the product should be protected by external devices limiting overvoltage and effects of lightning discharges.

  • Avoid powering the product and its controlled/monitored devices, especially high power and inductive loads, from a single power source. Powering devices from a single power source causes a risk of introducing disturbances from the loads to the control devices.

  • If an AC/AC transformer is used to supply control devices, it is strongly recommended to use a maximum 100 VA Class 2
    transformer to avoid unwanted inductive effects, which are dangerous for devices.

  • Long monitoring and control lines may cause loops in connection with the shared power supply, causing disturbances in the operation of devices, including external communication. It is recommended to use galvanic separators.

  • To protect signal and communication lines against external electromagnetic interferences, use properly grounded shielded cables and ferrite beads.

  • Switching the digital output relays of large (exceeding specification) inductive loads can cause interference pulses to the electronics installed inside the product. Therefore, it is recommended to use external relays/contactors, etc. to switch such loads. The use of controllers with triac outputs also limits similar overvoltage phenomena.

  • Many cases of disturbances and overvoltage in control systems are generated by switched, inductive loads supplied by alternating mains voltage (AC 120/230 V). If they do not have appropriate built-in noise reduction circuits, it is recommended to use external circuits such as snubbers, varistors, or protection diodes to limit these effects.

Electrical installation of this product must be done in accordance with national wiring codes and conform to local regulations.

iSMA CONTROLLI S.p.A. – Via Carlo Levi 52, 16010 Sant’Olcese (GE) – Italy | support@ismacontrolli.com

www.ismacontrolli.com
Installation Guideline Issue rev. 1 | 05/2022