iSMA CONTROLLI SfAR-S-6RO 6 Relay Outputs Expansion Module User Manual

June 9, 2024
iSMA CONTROLLI

iSMA CONTROLLI SfAR-S-6RO 6 Relay Outputs Expansion Module User Manual
iSMA CONTROLLI SfAR-S-6RO 6 Relay Outputs Expansion
Module

Introduction

Thank you for choosing our product.
This manual will help you with proper handling and operating of the device. The information included in this manual have been prepared with utmost care by our professionals and serve as a description of the product without incurring any liability for the purposes of commercial law. This information does not discharge you from the liability of your own judgement and verification. We reserve the right to change product specifications without notice.
Please read the instructions carefully and follow the recommendations concluded therein.

WARNING!
Failure to follow instructions can result in equipment damage or impede the use of the hardware or software.

Revision History

Rev. Date Description
3.2 25 May 2022 Rebranded

Safety Rules

  • Improper wiring of the product can damage it and lead to other hazards. Make sure that the product has been correctly wired before turning the power on.
  • Before wiring or removing/mounting the product, make sure to turn the power off.
  • Failure to do so might cause an electric shock.
  • Do not touch electrically charged parts such as power terminals. Doing so might cause an electric shock.
  • Do not disassemble the product. Doing so might cause an electric shock or faulty operation.
  • Use the product only within the operating ranges recommended in the specification (temperature, humidity, voltage, shock, mounting direction, atmosphere, etc.). Failure to do so might cause a fire or faulty operation.
  • Firmly tighten the wires to the terminal. Failure to do so might cause a fire.
  • Avoid installing the product in close proximity to high-power electrical devices and cables, inductive loads, and switching devices. Proximity of such objects may cause an uncontrolled interference, resulting in an instable operation of the product.
  • Proper arrangement of the power and signal cabling affects the operation of the entire control system. Avoid laying the power and signal wiring in parallel cable trays. It can cause interferences in monitored and control signals.
  • It is recommended to power controllers/modules with AC/DC power suppliers. They provide better and more stable insulation for devices compared to AC/AC transformer systems, which transmit disturbances and transient phenomena like surges and bursts to devices. They also isolate products from inductive phenomena from other transformers and loads.
  • Power supply systems for the product should be protected by external devices limiting overvoltage and effects of lightning discharges.
  • Avoid powering the product and its controlled/monitored devices, especially high power and inductive loads, from a single power source. Powering devices from a single power source causes a risk of introducing disturbances from the loads to the control devices.
  • If an AC/AC transformer is used to supply control devices, it is strongly recommended to use a maximum 100 VA Class 2 transformer to avoid unwanted inductive effects,which are dangerous for devices.
  • Long monitoring and control lines may cause loops in connection with the shared power supply, causing disturbances in the operation of devices, including external communication. It is recommended to use galvanic separators.
  • To protect signal and communication lines against external electromagnetic interferences, use properly grounded shielded cables and ferrite beads.
  • Switching the digital output relays of large (exceeding specification) inductive loads can cause interference pulses to the electronics installed inside the product. Therefore, it is recommended to use external relays/contactors, etc. to switch such loads. The use of controllers with triac outputs also limits similar overvoltage phenomena.
  • Many cases of disturbances and overvoltage in control systems are generated by switched, inductive loads supplied by alternating mains voltage (AC 120/230 V). If they do not have appropriate built-in noise reduction circuits, it is recommended to use external circuits such as snubbers, varistors, or protection diodes to limit these effects.

Module Features

Purpose and Description of the Module
The SfAR-S-6RO module is an innovative device that provides a simple and cost effective extension of the number of lines of output with high current- carrying capacity.
The module has 6 relay outputs. Each relay has three terminals: common (COM), normally open (NO), or normally closed (NC), which makes the unit very flexible.
This module is connected to the RS485 bus with a twisted-pair wire. Communication is via
Modbus RTU or Modbus ASCII. The use of 32-bit ARM core processor provides fast processing and quick communication. The baud rate is configurable from 2400 to 115200.
The module is designed for mounting on a DIN rail in accordance with DIN EN 5002.
The module is equipped with a set of LEDs to indicate the status of inputs and outputs, power supply, and communication, which is useful for diagnostic purposes and helping to find errors.
Module configuration is done via USB by using a dedicated computer program. It also allows for changing the parameters using the Modbus protocol or setting the Modbus address using the DIP switches under the front panel.

Technical Specification

Power Supply Voltage 10-38 V DC; 10-28 V AC

Power consumption (with active Modbus transmission and high state on all outputs)| 4.8 W at 24 V DC
6 VA at 24 V AC
Relay Outputs| No. of outputs| 6
Resistive load| AC1: 8 A @ 230 V AC or 8 A @ 30 V DC
Inductive load| AC3: 360 V A @ 230 V AC or 60 W @ 30 V DC
Isolation| 1000 V AC
Temperature| Work| -10 °C to +50°C (14°F to 122°F)
Storage| -40 °C to +85°C (-40°F to 185°F)
Connectors| Power supply| 2 pins
Communication| 3 pins
Outputs| 2x 10 pins
Quick connector| IDC10
Configuration| mini USB
Size| Height| 119.1 mm (4.689 in)
---|---|---
Length| 110.9 mm (4.366 in)
Width| 22.7 mm (0.894 in)
Interface| RS485| Up to 128 devices

Dimensions
The appearance and dimensions of the module are shown below. The module is mounted directly to the rail in the DIN industry standard. Power connectors, communication, and I/Os are at the bottom and top of the module. USB connector configuration and indicators are located on the front of the module.

Communication

Grounding and Shielding
In most cases, I/O modules will be installed in an enclosure along with other devices, which generate electromagnetic radiation. Relays, contactors, transformers, motor controllers, etc. are examples of such devices. Radiation can induce electrical noise into both power and signal lines, as well as direct radiation into the module. Whether or not the SfAR modules are immune to such effects, the interferences must be suppressed at their source if possible to ensure the proper functioning of the entire system.
Appropriate grounding, shielding and other protective steps should be taken at the installation stage to prevent these effects. It is recommended to at least follow the rules below:

  • line power cables must be routed with spatial separation from signal and data transmission cables;
  • analog and digital signal cables should also be separated;
  • it is recommended to use shielded cables for analog signals, cable shields should not be interrupted by intermediate terminals;
  • the shielding should be earthed directly after the cable enters the cabinet.
    It is recommended to install interference suppressors when switching inductive loads (e.g., coils of contactors, relays, solenoid valves). RC snubbers or varistors are suitable for AC voltage and freewheeling diodes for DC voltage loads. The suppressing elements must be connected as close to the coil as possible.

Network Termination
Transmission line effects often represent the problem of data communication networks. These problems include reflections and signal attenuation. To eliminate the presence of reflections at the end of the cable, the cable must be terminated at both ends with a resistor across the line adequate to its characteristic impedance. Both ends must be terminated since the direction of propagation is bidirectional. In case of RS485 twisted pair cable, this termination is typically 120 Ω.

Setting Module Address in RS485 Modbus Network
The following table shows how to set DIP switch to determine the address of the module. The module address is set with the switches in the range of 0 to 31. Addresses from 32 to 255 can be set via RS485 or USB and using dedicated software tool.

Addr SW1 SW2 SW3 SW4 SW5
0 OFF OFF OFF OFF OFF
1 ON OFF OFF OFF OFF
2 OFF ON OFF OFF OFF
3 ON ON OFF OFF OFF
4 OFF OFF ON OFF OFF
Addr SW1 SW2 SW3 SW4 SW5
--- --- --- --- --- ---
5 ON OFF ON OFF OFF
6 OFF ON ON OFF OFF
7 ON ON ON OFF OFF
8 OFF OFF OFF ON OFF
9 ON OFF OFF ON OFF
10 OFF ON OFF ON OFF
11 ON ON OFF ON OFF
12 OFF OFF ON ON OFF
13 ON OFF ON ON OFF
14 OFF ON ON ON OFF
15 ON ON ON ON OFF
16 OFF OFF OFF OFF ON
17 ON OFF OFF OFF ON
18 OFF ON OFF OFF ON
19 ON ON OFF OFF ON
20 OFF OFF ON OFF ON
21 ON OFF ON OFF ON
22 OFF ON ON OFF ON
23 ON ON ON OFF ON
24 OFF OFF OFF ON ON
25 ON OFF OFF ON ON
26 OFF ON OFF ON ON
27 ON ON OFF ON ON
28 OFF OFF ON ON ON
29 ON OFF ON ON ON
30 OFF ON ON ON ON
Addr SW1 SW2 SW3 SW4 SW5
--- --- --- --- --- ---
31 ON ON ON ON ON

Setting module address in RS485 Modbus network using DIP switch

Types of Modbus Functions
There are 4 types of Modbus functions supported by the SfAR modules:

Type Beginning Address Variable Access Modbus Command
1 00001 Digital Outputs Bit Read/write 1, 5, 15
2 10001 Digital Inputs Bit Read 2
3 30001 Input Registers Registered Read 3
4 40001 Output Registers Registered Read/write 4, 6, 16

Communication Settings
The data stored in the module’s memory is given in the 16-bit registers. The access to registers is via Modbus RTU or Modbus ASCII.

Default Settings
The default configuration can be restored with the DIP switch SW6.

Baud Rate 19200
Parity No
Data Bits 8
Stop Bits 1
Reply Delay [ms] 0
Modbus Mode RTU

Restore Default Configuration
To restore the default configuration, follow the steps below:

  • turn the power off;
  • turn the DIP switch SW6 on;
  • turn the power on;
  • when power and communication LED is lit, turn the switch SW6 off.

WARNING! After restoring the default configuration all values stored in the registers will be cleared as well.

Configuration Registers

Modbus Address Decimal Address Hex Address Name Values
40003 2 0x02 Baud Rate 0 – 24001 – 48002 – 96003 – 192004 – 384005 –

576006 – 115200other – value * 10
40005| 4| 0x04| Parity| 0  – none1  – odd2  – even3  – always 04  – always
40004| 3| 0x03| Stop Bits| 1 – one stop bit 2 – two stop bits
40004| 3| 0x03| Data Bits| 7  – 7 data bits8  – 8 data bits
40006| 5| 0x05| Response Delay| Time in ms
40007| 6| 0x06| Modbus Mode| 0  – RTU1  – ASCII

Watchdog
This 16-bits register specifies the time in milliseconds to watchdog reset. If the module does not receive any valid message within this time, all digital and analog outputs will be set to the default state. This feature is useful if there is an interruption in data transmission and for security reasons. Output states must be set to the appropriate state in order to reassure the safety of persons or property. The default value is 0 milliseconds, which means the watchdog function is disabled.

Indicators

Indicators

Indicator Description
Power Supply The LED indicates that the module is correctly powered
Communication The LED lights up when the unit received the correct packet and

sends the answer
Outputs State| The LED indicates that the output is on

Connections

Block Diagram

Power Supply Connection

DC Power Connection

AC Power Connection

Communication Bus Connection

Connection of Relay Outputs

Connection of Resistive Load

Connection of Resistive Load

Connection of Electrovalve

Connection of Electrovalve

Quick Connector
The Quick Connector is an unique feature of modules that allows for quickly connecting a group of devices with a flat ribbon cable.
Thanks to this solution, it is enough to connect the power supply and RS485
communication to one of the devices in the group, and the others will be powered and communicated with ribbon cable.
The Quick Connector is sufficient to connect up to 10 devices next to each other. It is important that the various types of modules in the SfAR-S family can be connected with the ribbon cable.

Quick Connector

DIP Switch

Switch Function Description
1 Module address +1 Setting module address from 0 to 31
2 Module address +2
3 Module address +4
4 Module address +8
5 Module address +16
6 Restoring default settings Restoring default settings

Module Registers

Registered Access

Modbus Address| Decimal Address| Hex Address| Register Name| Access| Description
---|---|---|---|---|---
30001| 0| 0x00| Version/Type| Read| Version and type of the device
30002| 1| 0x01| Switches| Read| Switches state
40003| 2| 0x02| Baud Rate| Read/write| RS485 baud rate
40004| 3| 0x03| Stop Bits & Data Bits| Read/write| No. of stop bits & data bits
40005| 4| 0x04| Parity| Read/write| Parity bit
40006| 5| 0x05| Response Delay| Read/write| Response delay in ms
40007| 6| 0x06| Modbus Mode| Read/write| Modbus mode (ASCII or RTU)
40009| 8| 0x08| Watchdog| Read/write| Watchdog
40013| 12| 0x0C| Default Outputs State| Read/write| Default outputs state
40033| 32| 0x20| Received Packets LSR (Least Significant Register)| Read/write| No. of received packets
40034| 33| 0x21| Received Packets MSR (Most Significant Register)| Read/write
40035| 34| 0x22| Incorrect Packets LSR| Read/write| No. of received packets with error
40036| 35| 0x23| Incorrect Packets MSR| Read/write
40037| 36| 0x24| Sent Packets LSR| Read/write| No, of sent packets
40038| 37| 0x25| Sent Packets MSR| Read/write
40052| 51| 0x33| Outputs| Read/write| Outputs state

Bit Access

Modbus Address| Decimal Address| Hex Address| Register Name| Access| Description
---|---|---|---|---|---
193| 192| 0x0C0| Default Output 1 State| Read/write| Default output 1 state
194| 193| 0x0C1| Default Output 2 State| Read/write| Default output 2 state
195| 194| 0x0C2| Default Output 3 State| Read/write| Default output 3 state
196| 195| 0x0C3| Default Output 4 State| Read/write| Default output 4 state
197| 196| 0x0C4| Default Output 5 State| Read/write| Default output 5 state
198| 197| 0x0C5| Default Output 6 State| Read/write| Default output 6 state
817| 816| 0x330| Output 1| Read/write| Output 1 state
818| 817| 0x331| Output 2| Read/write| Output 2 state
819| 818| 0x332| Output 3| Read/write| Output 3 state
820| 819| 0x333| Output 4| Read/write| Output 4 state
821| 820| 0x334| Output 5| Read/write| Output 5 state
822| 821| 0x335| Output 6| Read/write| Output 6 state

Configuration Software

The SfAR Configurator is a software which is designed to set the communication module registers over Modbus network as well as to read and write the current value of other registers of the module. It is a convenient way to test the system as well as to observe real-time changes in the registers. Communication with the module is done via a USB cable. The module does not require any drivers.

Configuration Software

The SfAR Configurator is a universal software, where it is possible to configure all available modules.

STAR CONFIGUTATOR

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

iSMA CONTROLLI User Manuals

Related Manuals