ALL O MATIC APS1000-12 Battery Backup Power Inverter User Manual

June 9, 2024
ALL O MATIC

APS1000-12 Battery Backup Power Inverter

POWER INVERTER
APS1000-12, APS2000-24 & APS4000-48

Table of Contents
Important Safety Information . . . . . . . . . . . . . . . . . . . . . . 1 General Safety Precautions. . . . . . . . . . . . . . . . . . . . . . 1 Precautions When Working With Batteries . . . . . . . . . . . . . . 1
General Informtion . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 Application . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 Basis System Architecture . . . . . . . . . . . . . . . . . . . . . . . 4 Product Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Unpacking and Inspection . . . . . . . . . . . . . . . . . . . . . . 5 Preparation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 Mounting The Unit . . . . . . . . . . . . . . . . . . . . . . . . . . 6 Battery Connection . . . . . . . . . . . . . . . . . . . . . . . . . . 7 AC Input/Output Connection . . . . . . . . . . . . . . . . . . . . . 9 Electrical Performance . . . . . . . . . . . . . . . . . . . . . . . . . 11 LCD Display Icons . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14 Relay connections for gate operator auto open/close functions . . . 15 Operating Mode Description . . . . . . . . . . . . . . . . . . . . . . 16 Warning Code/Audible Alarm . . . . . . . . . . . . . . . . . . . . . . 19 Troubleshooting Guide . . . . . . . . . . . . . . . . . . . . . . . . . 20

Important Safety Information
í ! wb Lb D
This manual contains important instructions for APS1000-12 & APS2000-24 models that shall be followed during installation and maintenance of the inverters.
General Safety Precautions
1. Before installing and using the inverter/charger, read all instructions and cautionary markings on the inverter/charger and all appropriate sections of this guide. Be sure to read all instructions and cautionary markings for any equipment attached to this unit.
2. Install this unit away from direct sun light and where is not exposed to water sprinklers.
3. To reduce risk of fire hazard, do not cover or obstruct the ventilation openings. Do not install the inverter/charger in a zero-clearance compartment. Otherwise overheating may occur.
4. Use only attachments recommended or sold by the manufacturer. Doing otherwise may result in a risk of fire, electric shock, or injury to persons.
5. To avoid a risk of fire and electric shock, make sure that existing wiring is in good condition and that wire is not undersized. Do not connect the inverter/charger with damaged or substandard wiring.
6. Do not operate the inverter/charger if it has received a sharp blow, been dropped, or otherwise damaged in any way. If the inverter/charger is damaged, read the warranty section.
7. Do not disassemble the inverter/charger. It contains no user-serviceable parts. See warranty for instructions on obtaining service. Attempting to service the inverter/charger yourself may result in a risk of electrical shock or fire. Internal capacitors remain charged after all power is disconnected.
8. The inverter contains more than one live circuit (batteries and AC line). Power may be present at more than one source. To reduce the risk of electric shock, disconnect both AC and DC power from inverter/charger before attempting any maintenance or cleaning or working on any circuits connected to the inverter/charger. Turning off controls will not reduce this risk.
9. Use insulated tools to reduce the chance of short-circuits when installing or working with the inverter or the batteries.
Precautions When Working with Batteries
1. Make sure the batteries are well ventilated. Avoid blocking enclosure vents. 2. Never smoke or allow a spark or flame near the inverter or batteries. 3. Use caution to reduce the risk of dropping a metal tool on the batteries. It could
spark or short circuit the battery or other electrical parts and could cause an explosion. 4. Remove all metal items, like rings, bracelets, and watches when working with lead-acid batteries. Lead-acid batteries produce a short circuit current high enough to weld metal to skin. 5. Make sure someone is close enough to aid should anything dangerous occur when you’re working near a lead-acid battery.

6. Prepare enough fresh water and soap in case battery acid contacts skin, clothing or eyes. 7. Wear complete eye protection and clothing protection. Avoid touching your eyes while working near batteries. 8. If battery acid contacts skin or clothing, wash immediately with soap and water. If acid enters your eyes, immediately flood in cold water and get medical attention immediately. 9. If you need to remove a battery, always remove the ground terminal from the battery first. Make sure all accessories are off so you don’t cause a spark. 10. Always use identical types of batteries. 11. Never install old or untested batteries. Check each battery’s date code label to ensure age and type. 12. Batteries are temperature sensitive. For optimal performance, they should be installed in a stable temperature environment. 13. Always recycle old batteries. Contact your local recycling center for proper disposal information.
General Information Thank you for purchasing the APS inverter series. The inverter is a combination of an inverter, charger. It is packed with unique features and it is one of the most advanced inverter/charger in the market today. The inverter features an AC bypass circuit, powering your gate operators and access controls or any appliance from the utility power or generator power while charging the battery. When utility power fails, the battery backup system keeps your equipment powered until utility power is restored. Internal protection circuits prevent overdischarging the batteries by shutting down inverter when a low battery condition occurs. When utility or generator power is restored, the inverter transfer to the AC source and recharges the batteries. The series inverter can also serve as a central hub of renewable energy system. Set the series inverter to battery priority mode to designate it to inverter-preferred UPS configuration. In this configuration, the load power is normally provided by the inverter, However, if the inverter output is interrupted, an internal transfer switch automatically transfers the load from the inverter to commercial utility power. The transfer time between inverter and line is short(6ms typically), and such transfers are normally not detected by even highly sensitive loads. Upon restoration of battery capacity, the inverter will transfer back to inverter power (battery). In the line priority mode, when utility power cuts off (or drops below acceptable range), the transfer relay is de-energized and the load is automatically transferred to inverter output. Once the qualified utility power is restored, the relay is energized and the load is automatically reconnected to utility power. It features power factor, sophisticated multi-stage charging and pure sine wave output with unprecedentedly high surge capability to meet demanding power needs of inductive loads without endangering the equipment. The inverter is equipped with a powerful charger of up to 70Amp (depending on mode). The overload capacity is 125~150% of continuous output for up to 20 seconds to reliably support tools and equipment longer. Another important feature is that the inverter can be easily customized to solar priority by DIP switch, this helps to extract maximum power from solar in renewable energy systems. To get the most out of the power inverter, it must be installed, used and maintain properly. Please read the instructions in the manual before installing.

Gate operators, access control devices and accessories. Power tools-circular saws, drills, grinders, sanders, buffers, weed and hedge trimmers, air compressors.
Office equipment such as computers, printers, monitors, facsimile machines, scanners. Household items, vacuum cleaners, fans, fluorescent and incandescent lights, shavers, sewing machines.
Kitchen appliances-coffe makers, blenders, ice makers, toasters. Industrial equipment-metal halide lamp, high-pressure sodium lamp. Home entertainment electronics-television, VCRs, video gate consoles, stereos, musical instruments, satellite equipment.
Y Pure sine wave output Y AC/Battery priority Via function DIP switch Y Auto generator start. For gate operators Auto open
relay.
Y Max. AC charge current 35A Y Built-in pure copper transformer Y Low battery trip voltage 10.5V/11.0V setting Y Auto sense 50HZ/60HZ

The following illustration shows basic application for this inverter. It also includes following devices to have a complete running system:
Generator or Utility. Battery
Also Gate Operators and accessories.

BATTERY INVERTER

AC INPUT
GENERATOR AC OUTPUT

LAPTOP LIGHTING AIR CONDITIONING TV

FANS

APS1000-12 includes two 35Ahr batteries APS2000-24 includes two 50Ahr batteries APS4000-48 includes four 50Ahr batteries

INVERTER OFF ON

Power ON

Connectors 8, 9 and 10 are extended to the inverter front panel for easy wiring.

Before installation, please inspect the unit. Be sure that nothing inside is damaged. You should see the following items inside the main enclosure of the APS series inverters:

Y Main inverter Unit Y Batteries
Two 35Ahr for APS1000-12 Two 50Ahr for APS2000-24 Four 50Ahr for APS4000-48 Y Battery breaker on the left side inside enclosure

Y AC Input/Output and relay connector on inverter front panel

Mounting the unit
Consider the following before selecting where to install the unit:
Y Do not install the inverter on flammable construction materials. Y Mount on a solid surface. Y Install the inverter at eye level in order to read the LCD display clearly. Y For proper air circulation to dissipate heat, leave at least 3″ gap above, below and
sides of the inverter enclosure.
Y The ambient temperature should be between 0ºF and 105ºF to ensure optimal
operation.
Y The recommended installation position is to be against the wall horizontally.

SUITABLE FOR MOUNTING ON CONCRETE OR OTHER NON-COMBUSTIBLE SURFACE ONLY.

Install the unit using 4 screws on four mounting holes

Mounting holes

Mounting holes behind packaging foam

Battery Connection
CAUTION: For safety and regulation compliance, it’s requested to install a separate DC over-current protector between battery and inverter. DO NOT bypass the over-current breaker that’s installed between inverter and batteries. Doing so, will increase the risk of fire and possible harm to persons.
DC Wiring Recommendation
It is recommended the battery bank be kept as close as possible to the inverter. the following is the recommended wiring options for 3 feet long cable. APS series inverters use 4AWG cable that meet or exceed this requirement. If there is a need to replace the battery cables, you must use the proper size to handle the power. If Batteries need to be moved outside the inverter enclosure and need to extend the cable, also increase the wire gauge thickness.

Model
APS1000-12 APS2000-24 APS4000-48

Battery Voltage Wire gauge/Min (0-3 feet length)

12VDC

1*4AWG

24VDC

1*4AWG

48VDC

1*4AWG

Over-Current Breaker

Two Batteries

4AWG BATTERY

Four for APS4000-48

CABLE

One cable is always best, but cable is just copper and copper is what’s required, so it does not matter if you use one cable or 10 cables as long as the square are adds up. Performance of any product will be improved by thicker cable and shorter runs, so it is recommended to keep the cables as short as possible.

Please follow steps below in case battery cables need to be replaced: 1. Install battery ring terminals on recommended cable and terminal size. 2. Connect battery pack as unit requires. APS1000-12 must have batteries connected in parallel, and the APS2000-24 in series.
NOTE: Please only use Sealed Lead Acid or Sealed GEL/AGM Lead-Acid Batteries. 3. Connect ring terminals of battery cable into inverter battery connector and make sure bolts are tightened. Make sure polarity is correct at both ends of the cable (battery terminals and inverter connectors) and that ring terminals are tightly screwed to battery terminals.

PARALLEL

12V

-+

12V

12V

35Ahr

35Ahr

+-

SERIES

24V

-+

12V

12V

50Ahr

50Ahr

APS1000-12 Main battery bank, 12VDC. (35Ahr included) wired in parallel.

+-

24V

-+

12V

12V

50Ahr

50Ahr

+48V –

APS2000-24 Main battery bank, 24VDC. (50Ahr included) wired in series.
SERIES

-+

-+

12V

12V

50Ahr

50Ahr

APS4000-48 Main battery bank, 48VDC. (50Ahr included) wired in series.

AC Input/Output Connection
Caution!! Before connecting AC input power source, please install a separate AC breaker between inverter and AC input power source. This will ensure the inverter can be safely disconnected during maintenance and fully protected from over current of AC input. The recommended AC breaker is 30A for both APS1000-12 and APS2000-24 models.
Caution!! Please don’t connect the output AC to “Grid” terminals nor connect the grid to the “Load” terminals. Doing so will permanently damage inverter.
WARNING! All wiring must be performed by a qualify person. WARNING! It’s very important for system safety and efficiency operation to use appropriate cable for Grid connection. To reduce risk of injury, please use the recommended proper cable size as below.
AC Wiring We recommend using 12AWG wire to the AC terminal block. If the inverter is installed farther than 70 feet from main power source, wire gauge must be sized properly to avoid big voltage drops. Be sure all wiring is UL compliant, call our tech support if you are not sure how to wire any part of the inverter.
WARNING! It’s very important to do the wiring correctly on battery terminals and high voltage AC side.

APS1000-12 APS2000-24
APS4000-48

10AWG

COMMON N.O.
COMMON N.O.

RLY 2

RLY 1

120V AC 60Hz 1000W
L NN L
INPUT OUTPUT

AC Wiring (120VAC, Single phase, 60Hz) Input: Groung +Hot line +Neutral (Main Source) Output: Neutral +Hot line +Ground (Load)

Please follow these steps to connect inverter to Load/Grid: 1. Before making Load/Grid connection, be sure to open DC protector/breaker first. 2. Strip each individual wire/conductor about 3/8″. 3. Connect grid wires according to polarity indicated on terminal block and tighten the
terminal screws. Be sure to connect protective earth conductor ( ) first.
-> Ground (green) L-> LINE (black) N-> Neutral (white)

RLY 2 RLY 1

120V AC 60Hz 1000W
L NN L
INPUT OUTPUT

COMMON N.O.
COMMON N.O.

4. Then, connect Load (output) wires according to polarity indicated on terminal block and
tighten terminal screws. Be sure to connect protective earth conductor ( ) first.
-> Ground (green) L-> LINE (black) N-> Neutral (white)

COMMON N.O.
COMMON N.O.

RLY 2 RLY 1

120V AC 60Hz 1000W
L NN L
INPUT OUTPUT

5. Make sure all wires are securely connected.

AC output (load)

CAUTION: Appliances such as air conditioner require at least 2~3 minutes to restart to have enough time to balance refrigerant gas inside of circuits. If a power outage occurs and recovers in a short time, it will cause damage to your connected appliance. To prevent this kind of damage, please check manufacturer of air conditioner if it’s equipped with time-delay function before installation. Otherwise, this inverter will trigger overload fault and cut off output to protect your appliance but it is still possible it will cause internal damage to the air conditioner.

APS1000-12

APS2000-24
120Vac 75Vac 2% 80Vac 2% 140Vac 2% 135Vac 2% 140Vrms

APS4000-48

Same as Input Waveform

30A

40A

63

APS1000-12

APS2000-24

120VAC

APS4000-48
4000 4000

2,000VA

4,000VA

8000VA

Instant Reverse Gate Motors Two 1/2 HP or One 1HP

Instant Reverse Gate Motors Four 1/2 HP or Two 1HP

Instant Reverse Gate Motors eight 1/2 HP or four 1HP up to one 5HP

11V 11Vdc ± 0.3Vdc 10.5Vdc ± 0.3Vdc 16Vdc ± 0.3Vdc 15.5Vdc ± 0.3Vdc

22V 22Vdc ± 0.6Vdc 21Vdc ± 0.6Vdc 32Vdc ± 0.6Vdc 31Vdc ± 0.6Vdc

22V 44Vdc ± 1.2Vdc 42Vdc ± 1.2Vdc 64Vdc ± 1.2Vdc 62Vdc ± 1.2Vdc

APS1000-12 10.5-15.7Vdc

APS2000-24 120Vac
75-140Vac
30A
21V-31.4Vdc

APS4000-48 42V-62.8Vdc

15.7Vdc

31.4Vdc

62.8Vdc

Alarm beeps 0.5s second & Fault after 60s

14

15

Auto generator start (AGS) There is an extra connector in front of the inverter (Relay 2) used to start a generator or to trigger a gate operator to open the gate before battery runs out of power. If the utility power is abnormal and single battery discharges below 11VDC, the inverter will send out a signal to either a generator start circuit or to a gate operator to trigger the gate to open. Once the battery is charged to 13.5VDC or higher, the signal will deactivate and switch to normal operation.
Auto AC power off signal Includes a relay N.O. contact used to trigger a gate operator to open the gate on AC utility power failure. Once AC utility power fails, the relay will trigger the signal.

Relay Function for gate operators:
RELAY 1: Activates immediately after a power outage. I can be to trigger a gate operator to open the gate. One time open. It will stay active until power is restored.
RELAY 2: Activates after a power failure and battery voltage has reached the low level threshold. It could be used to trigger a gate operator to open before battery is fully depleted. Using this relay to trigger a gate to open, will allow a gate operator to run on battery backup but will ensure gate opens before battery fails. For Failsafe connect to gate operator OPEN CMD For Failsecure connect to gate operator CLOSE_CMD

COMMON N.O.
COMMON N.O.

RLY 2 RLY 1

120V AC 60Hz 1000W
L NN L
INPUT OUTPUT

Battery voltage restart After low battery voltage shut off (10.5V for 12V model / 20V for 24V model), the inverter is able to restore operation after the battery recovers to 13V for 12V model and 26V for 24V model (with power switch still in the “ON” position). This function helps to save the users extra work reactivating the inverter when the low battery voltage returns to an acceptable range in the renewable energy systems. the built in battery charger will automatically reactivate as soon as utility/generator ac has been stable for 15 seconds.

APS1000-12/APS2000-24 APS1000-12/APS2000-24

Low trip to AC model 11.5V/23V

14V/28V

USA

14V/28V

AGM 1

14.1V/28.2V

AGM 2

14.6V/29.2V

14.4V/28.8V

EURO

14.4V/28.8V

Open lead acid

14.8V/29.6V

7

Calcium

15.1V/30.2V

13.4V/27.4V 13.4V/26.8V 13.7V/27.4V 13.6V/27.2V 13.8V/27.6V 13.3V/26.6V 13.6V/27.2V

De sulphation

15.5V/31V

4 hours then off

Note: APS series inverter include Sealed Lead Acid Batteries. If different chemistry batteries are used, this setting must be adjusted to match the charging voltage appropriate for the type of battery.

18

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals