BI-LEVEL PIR SENSOR • 54885
INSTALL INSTRUCTIONS
PLEASE FIND A QUALIFIED ELECTRICIAN FOR INSTALLATION. Please read the
instructions before you install the sensor and use the luminaire.
GENERAL:
ALL ELECTRICAL CONNECTIONS MUST BE IN ACCORDANCE WITH LOCAL AND NATIONAL
ELECTRICAL CODE (N.E.C.) STANDARDS. IF YOU ARE UNFAMILIAR WITH PROPER
ELECTRICAL WIRING CONNECTIONS OBTAIN THE SERVICES OF A QUALIFIED ELECTRICIAN.
REMOVE THE TRIM FROM THE BOX AND MAKE SURE THAT NO PARTS ARE MISSING.
- WARNING – Risk of fire or electric shock. Sensor installation requires knowledge of luminaires electrical systems. If not qualified, do not attempt installation. Contact a qualified electrician.
- WARNING – Risk of fire or electric shock. Install this sensor only in luminaires that have the construction features and dimensions shown in the photographs and/or drawings and where the input rating of the sensor does not exceed the input rating of the luminaire.
- WARNING – To prevent wiring damage or abrasion, do not expose wiring to edges of sheet metal or other sharp objects.
- Risk of Electric Shock: Disconnect power or circuit breaker before installing or servicing.
- Do not make or alter any open holes in an enclosure of wiring or electrical components during installation.
WARNING – NOTE:
- Warm up time is 40 seconds. After the sensor connects input power for the first time, the light will stay on for 40 seconds, then go to dimming to work normally.
- Factory Default Settings: Sensitivity set to 100%. Hold on time 10 seconds. Daylight sensor at 30 Lux. Dimming level at 30%. Dimming time at 60 minutes.
- If any setting is changed with DIP Switch or remote control (RC-100, sold separately), the LED light will turn on/off as confirmation of connection.
CAUTION FOR YOUR SAFETY: IF YOU ARE UNSURE ABOUT ANY PART OF THESE INSTRUCTIONS, CONSULT A QUALIFIED ELECTRICIAN.
SENSOR INFORMATION
SPECIFICATIONS
Power Load| 120-480VAC 50/60Hz
Maximum Load
@ -40° – 158°F| Tungsten – 800W @ 120V / 1200W @ 277V
Electronic Ballast – 8A @ 120V / 5A @ 277V / 5A @ 347V
Standard Ballast – 5A @ 480V
Dim Control Output| 0-10V, Max. 25mA Sinking Current
Detection Radius / Angle| Max 26.2ft / 360°
Mounting Height| Max 40ft
Time Setting| 10 Sec. -15 Min. (adjustable)
Light-Control| 10-2000 Lux (adjustable)
Humidity| Max. 95% RH
Temperature| -40° – 158°F
WIRING DIAGRAM
SENSOR COVERAGE
WARNING DISCONNECT POWER BEFORE INSTALLING OR SERVICING.
PARAMETER SETTING BY DIP SWITCH
- Switches 1 and 2 are to set the sensitivity of the sensor.
- Switches 3 and 4 are to set the hold time of the sensor.
- Switches 5 and 6 are to set the lux of the sensor.
- Switches 7 and 8 are to set the stand-by light level of the fixture.
- Switches 9 and 10 are to set the stand-by time.
OCCUPANCY SENSOR SETTINGS
Detection Range Setting (Sensitivity): Detection range is a term used to
describe the radius of the more or less circular detection zone produced on
the ground after mounting the sensor light at a height of 40ft. Flip switch to
the ON position as “ ”, or to the OFF position as “ ”, switch location and
detection range of the corresponding table is shown in Fig. 1.
Hold Time Setting: The light can be set to stay ON for any period of time
between approximately 10 seconds and a maximum of 15 minutes. Any movement
detected before this time has elapsed will re-start the timer. It is
recommended to select the shortest time for adjusting the detection zone and
for performing the walk test.
Flip switch to the ON position as “ ”, or to the OFF position as “ ”, switch
location and settings of the corresponding table is shown in Fig. 2.
Light Control Setting (Lux) : The chosen light response threshold ranges
from approximately 10-50 lux. Flip switch to the ON position as “ ”, or to the
OFF position as “ ”, switch location and light-control of the corresponding
table is shown in Fig. 3.
Stand-By Light Level Setting: Switch in the ON position is “ ”, and the
OFF position is “ ”, switch location and settings are shown in Fig. 4.
Stand-By Time Setting: Switch in the ON position is “ ”, and the OFF
position is “ ”, switch location and settings are shown in Fig. 5.
Specifications subject to change without notice. Photos and line drawings may
not be to scale and are for general reference only.