GE current LRXB Series Lumination LED Luminaire Installation Guide
- June 9, 2024
- GE current
Table of Contents
GE current LRXB Series Lumination LED Luminaire
BEFORE YOU BEGIN / AVANT DE COMMENCER
Read these instructions and IOTA ILB-CP instruction manual completely and
carefully.
Wear work gloves to prevent dirt and oil from being transferred to the
luminaire.
WARNING
RISK OF FIRE OR ELECTRIC SHOCK
- Turn power off before inspection, installation or removal.
- Install this kit only in the luminaires that has the construction features and dimensions shown in the photographs and/or drawings.
- Installation of this product requires a person familiar with the construction and operation of the luminaire’s electrical system and the hazard involved. If not qualified, do not attempt installation. Contact a qualified electrician.
- To prevent wiring damage or abrasion, do not expose wiring to edges of sheet metal or other sharp objects.
- Do not make or alter any open holes in an enclosure of wiring or electrical components during kit installation.
- Installation requires input rating of the retrofit kit to not exceed the input rating of the luminaire.
CAUTION
- Fixture suitable for wet locations, covered ceiling mount only.
- Fixture may fall down if not installed properly, follow installation instructions.
- Wear appropriate Personal Protective Equipment (PPE) during installation and maintenance.
- Use only UL certified wires, wire connectors, minimum 18AWG, minimum rated 90°C.
Prepare Electrical Wiring
Electrical Requirements
- The LED luminaire must be connected to the mains supply according to its ratings on the product label.
- Class 1 wiring should be in accordance with NEC.
Grounding Instructions
- The grounding and bonding of the overall system shall be done in accordance to local electric code of the country where the luminaire is installed.
FCC STATEMENT
This device complies with Part 15 of the FCC Rules. Operation is subject to the following two conditions:
- This device may not cause harmful interference, and
- This device must accept any interference received, including interference that may cause undesired operation.
CAN ICES-005(A)/ NMB-005(A)
Note: This equipment has been tested and found to comply with the
limits for a Class A digital device, pursuant to part 15 of the FCC Rules.
These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instructions, may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be required to correct the interference at their own expense.
Direct-Mount Installation
Provided Components
The components have been properly packed to avoid damage during transit.
Inspect the components to confirm there is no physical damage. Do not install
damaged components.
Components List
- LRXB Fixture Kit
- Installation Instructions
Luminaire Installation
Before installation, check the fixture size and the diameter of ceiling
opening according to below Tab1.
Tab 1
Fixture Size| Fixture Type| Opening Size in
Ceiling (inch)| Fixture weight (kg)| Suitable
Ceiling Max Thickness
4| Round| 4.5~5.0| 0.475| 5/8″
6| Round| 6.0~6.7| 0.525| 3/4″
8| Round| 7.8~8.8| 0.615| 1″
10| Round| 10.2~11.2| 1.260| 1″
12| Round| 12.2~13.2| 1.410| 1″
4| Square| 4.5~5.0| 0.600| 5/8″
6| Square| 6.0~6.8| 0.700| 3/4″
8| Square| 8.0~9.0| 0.870| 1″
NOTE: For 10’’ and 12’’ fixtures, a suitable UL Listed frame-kit is recommended to be used with the fixture for installation safety.
-
Ensure that the power to the unit is turned off. Use proper lockout/tagout procedures. See fig A.
-
Cut an access opening in the ceiling with the diameter listed in Tab 1, and install the fixture to the ceiling per the codes. Make sure the ceiling can withstand the weight of the fixture and the thickness of ceiling be less than the list in Tab1. Ensure the center of existing J-Box cover is visible through the access opening, and the connections to the branch circuit supply are visible through the access opening.
-
Connect the black, white, yellow/green leads from the conduit to the power-supply with UL listed wire connectors according to the wiring diagram C2. Be sure all connection are made inside the existing J-Box. Optional Dimmer: When connecting a dimming Controller, connect the violet (dimming+) and pink (dimming-) wires to the violet and pink wires of the fixture.
Note: Cap all unused dimming leads with wire nuts.
Note: Phase cut dimmers must be wired to the power feed “hot” line (L). For 0-10V and phase cut dimming compatibility, please visit: www.gecurrent.com/dimming -
Select Lumen (8” luminaires with 3000lm are not lumen selectable):
NOTE: For 1000/650lm luminaires, the default lumen is 1000lm. Push the switch down to activate 650lm. See fig D1. NOTE: For 4000/5000/6000lm luminaires, the default lumen is 6000lm. Push the switch left to activate 4000lm and 5000lm respectively.
See fig D3.
NOTE: For 1800/1000/650lm luminaires, the default lumen is 1000lm. Push the switch up to activate 650lm. Push the switch down to activate 1800lm. See fig D2. -
Select CCT
NOTE: For 2700K/3000K/3500K luminaires, the de-fault CCT is 3500K. Push the switch up to activate 2700K, push the switch down to activate 3000K. See fig E1 or E4. NOTE: The cover of the lumen/CCT switches can be used as a tool to select lumen and CCT.
See fig E3.Place the switch cover back after lumen and CCT setting.
ONLY FOR 10IN AND 12IN FIXTURES: The CCT switch plug must be placed back after CCT selection to
avoid light leakage and dust/bug ingress. See fig E5.
ATTACH THE SAFETY TETHER TO THE RECOMMENDED FRAME-KIT FOR REDUNDANT INSTALLATION SAFETY.
CAUTION
RISK OF PERSONAL INJURY – Operators shall ensure no appendages are in the path
of the torsion springs as they are a pinch hazard when released. The springs
will release
when the arm is flexed downward. Be cautious that no body part is in the path
of the spring when released.
- Load springs into upright position by twisting the springs upward and carefully insert the fixture into ceiling opening. The springs will rotate back into position and hold the fixture tight to the ceiling.
NOTE: For 3500K/4000K/5000K luminaires, the default CCT is 4000K. Push the switch up to activate 3500K, push the switch down to activate 5000K. See fig E2 or E4. NOTE: For 10in and 12in fixtures, the CCT switch is located on the housing sealed by a plug, and the cover of the lumen switch can be used as a tool to select lumen and CCT. See fig E4 .
Retrofit Installation
Note: Installers should examine all parts that are not intended to be replaced by the retrofit kit for damage and replace any damaged parts prior to installation of the retrofit kit.
Luminaire Installation
Before installation, verify that the existing junction box and frame-kit are metal construction, designed similarly to fig 2.
Fixture Size| Fixture Type| Existing Bracket
Hole Size (inch)
---|---|---
4| Round| 4.5~5.0
6| Round| 6.0~6.7
8| Round| 7.8~8.8
10| Round| 10.2~11.2
12| Round| 12.2~13.2
4| Square| 4.5~5.0
6| Square| 6.0~6.8
8| Square| 8.0~9.0
-
Ensure that the power to the unit be turned off.
Use proper lockout/tagout procedures. -
Remove existing lamps, fixture and ballast. Leave wiring in junction box. Verify that the
AC supply line is provided with a ground wire connected to the luminaire. See fig 2B. -
Connect conduit end with input leads to existing J-Box and make the proper connections according to diagram C1/C2.
Make all electrical connections sing UL Listed wire connectors. Securely close J-Box after wiring. See fig 2C.
Optional Dimmer: Optional Dimmer: When connecting a dimming controller, low-voltage dimming wires must route through a separate knockout.
Connect the violet (dimming+) and pink (dimming-) wires to the violet and pink wires of the fixture.
Note: Cap all unused dimming leads with wire nuts
Note: Phase cut dimmers must be wired to the power feed “hot” line (L). For 0-10V and phase cut dimming compatibility, please visit: www.gecurrent.com/dimming
About selecting CCT or lumen level, refer to step D and E on page 3 and 4. -
Only for 10 in and 12 in:
ATTACH THE SAFETY TETHER TO THE FRAME KIT FOR REDUNDANT INSTALLATION SAFETY.
See fig 2E. CAUTION
RISK OF PERSONAL INJURY – Operators shall ensure no appendages are in the path of the torsion springs as they are a pinch hazard when released. The springs will release when the arm is flexed downward. Be cautious that no body part is in the path of the spring when released. -
Load springs into upright position by twisting the springs upward and carefully insert the fixture to ceiling opening.
The springs will rotate back into position and hold the fixture tight to the ceiling .
New Construction Installation
Provided Components
The components have been properly packed to avoid damage during transit.
Inspect the components to confirm
there is no physical damage. Do not install damaged components. See Fig 3A and
Tab 3.
Frame Installation
Tab 3
| Provided Item| Qty.
1| Frame (4-inch, 6-inch, 8-inch, 10-inch or 12-inch)| 1
2| Mounting Brackets| 2
3| L-Bracket| 2
5| Wing Nut| 3
Tab 4
Fixture Size| Fixture Type| Suitable Frame|
Suitable Ceiling Max Thickness
4| Round| FRAME4R| 5.0~5.5
6| Round| FRAME6R| 6.6~7.1
8| Round| FRAM8R| 8.2~8.7
10| Round| FRAME10R| 10.6~11.2
12| Round| FRAME12R| 12.5~13.3
4| Square| FRAME4S| 5.1~5.6
6| Square| FRAM6S| 6.9~7.4
8| Square| FRAME8S| 8.5~9.4
-
Cut an appropriate hole on the ceiling tile according to Tab 4. Ensure the ceiling hole diameter match the frame opening diameter.
-
Place side L-brackets on existing frame screws and tighten with screwdriver on both sides of the frame. Then attach mounting brackets to both L-brackets with wing nuts (provided).
-
Mounting brackets could also be fixed on the short side of frame.
-
Slide hanger bars (order separately) through adjustable mounting brackets.
-
Option A: Mount fixture by attaching hanger bars to T-Grid ceiling (BH3 SKU 94890).
Option B: Mount fixture with ½” EMT conduit. (Not Supplied) Adjust fixture height to be flush with ceiling and tighten both mounting bracket wing nuts. -
Refer to steps C-F of the retrofit installation above to finish the installation.
gecurrent.com/lamination
© 2022 Current Lighting Solutions, LLC. All rights reserved. GE and the GE
monogram are trademarks of the General Electric Company and are used under
license. Information and specifications subject to change without notice. All
values are design or typical values when measured under laboratory conditions.
IND668-Lumination-LRXB_Series-LED_Luminaire-Retrofit_andNew Construction- Install-Guide
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>