Reimers ELECTRA STEAM RXHC­36­120 Steam Boiler Instruction Manual

June 9, 2024
Reimers ELECTRA STEAM

Reimers ELECTRA STEAM RXHC­36­120 Steam Boiler

Reimers-ELECTRA-STEAM-RXHC­36­120-Steam-Boiler-prouduct-
image

RX 36‐120 STEAM BOILERS

Reimers-ELECTRA-STEAM-RXHC­36­120-Steam-Boiler-prouduct-
image

Features
  • Miniature boiler max. vessel volume 5ft3
  • Maximum safety valve setting 100psi
  • All  boilers  are  manufactured  in  accordance  with  the  requirements  of  the  A.S.M.E. Boiler and Pressure Vessel Code and A.S.M.E. CSD‐1. Each boiler bears the National Board Stamp “M”.
  • High quality saturated steam, operating pressure range 0 – 85psig
  • Heavy duty carbon steel pressure vessel. Vessel jacket 304 stainless steel and electrical enclosure powder coated carbon steel.
  • Large selecton of optional equipment

Standard Equipment of Each Boiler Includes:

  • A.S.M.E. pressure relief valve
  • One (1) quick opening boiler bottom blow off valve as per A.S.M.E. Code B31.1
  • ½” NPT Bronze steam outlet ball valve
  • High pressure feed pump in RBH‐ and RBHC‐models
  • Low water cutoff control with manual reset
  • One (1) high pressure cutoff control with manual reset
  • One (1) operating pressure control
  • Magnetic contactors
  • Main supply power distribution block
  • Indicator  lights  for  POWER,  REFILLING,  HEATING,  ALARMS  and  Automatic  Boiler Blow off Status
  • Pressure and water level gauge
Applications
  • Laboratories
  • Breweries
  • Process Heating
  • Shrink Wrap Labels
  • Food Service
  • Dry Cleaning

(*) DIRECT STEAM APPLICATIONS TO FOOD PRODUCTS: Reimers offers stainless steel boilers or #OPT1030 Brass/Bronze free boiler trim option (see Page 5). This
alone does not guarantee the production of culinary grade steam. Applicable safety standards (i.e. 3‐A T609) must be considered.

Model Number Key

Reimers-ELECTRA-STEAM-RXHC­36­120-Steam-Boiler-02

  1. Each  boiler  model  requires  two  (2)  power  supplies: Primary heating power and secondary control voltage. Nominal control voltage is 120V, 50/60Hz. Boiler models rated for 380V and 415V are equipped with control voltage transformers that require 220/240V applied to their primary side in order to provide the 120V AC control voltage to the boiler. As an option, all boiler models can be equipped with control voltage transformers so that only the heating power supply needs to be connected to the boiler.
  2. Also available in 240V 1PH
  3. On  boiler  equipped  with  condensate  tank,  add  90lbs (41.0kg) to shipping weight
  4. The  STEAM  CAPACITY  listed  above  is  based  on  the evaporation rate from and at 212°F, at 0 psig. If the boiler feed water temperature is 50°F, then the STEAM CAPACITY for each model listed above is approximately 15% lower.
  5. RX100 model, rated 208V, 3ph is limited to 307lbs/hr, 90kW, 9BHP

Please note that all information provided within this brochure is approximate and subject to change without notice. Please contact Reimers Electra Steam, Inc. with any questions regarding the specifications or dimensions detailed within.

LIMITED WARRANTY – STEAM GENERATORS

Reimers  Electra  Steam,  Inc.  warrants  the  following  products  of  its own  manufacture  against  defects  in  materials and workmanship under normal use and service. This warranty is in lieu and excludes all other expressed or implied warranties or merchantability of fitness for any particular use. No person is authorized to extend the terms of this warranty or assume any other liability except by written statement signed by an officer of Reimers Electra Steam, Inc. Clear Brook, Virginia 22624.

WARRANTY PERIOD
The  pressure  vessel  and  electrical  &  mechanical  components  are warranted  for  one  year  from  date  of  shipment from Reimers Electra Steam, Inc. in Clear Brook, VA 22624.

LIMITATIONS
Products must be installed, used and maintained in accordance with our instructions, including reasonable & necessary  maintenance  by  the  user. Users  are  responsible  for  the  suitability  of  the  products  to  their application. There is no warranty for damage resulting from improper installation, abuse, power failure, fire, flood, lightening, improper water, misuse, improper specification, misapplication or other operating conditions beyond our control or parts that are normally expendable in usual course of operation.
Claims  against  carriers  for  damage  in  transit  must  be  filed  by  the buyer.    Reimers  liability,  if  any,  will  not  exceed the price of Reimers products claimed to be defective.
Components  manufactured  by  any  supplier  other  than  Reimers  shall  bear only  that  warranty  made  by  the  manufacturer of that product and service for that warranty shall be the responsibility of that manufacturer and not Reimers.

REMEDY
Claims under this Limited Warranty must be made by obtaining a Return Authorization Number from our office (PHONE:  540­662­3811,  FAX: 540­665­8101)  &  returning  the  defective  part,  freight  prepaid  to: Reimers  Electra Steam, Inc., 4407 Martinsburg Pike, Clear Brook, Virginia 22624
Defective items will be repaired or replaced as necessary within a reasonable time without charge, other than incidental charges such as freight prepayment. Such repair or replacement within a reasonable time is the exclusive remedy available from Reimers Electra Steam, Inc., under this Limited Warranty.

CONSEQUENTIAL DAMAGES
Reimers Electra Steam, Inc., is not liable for labor costs incurred in the removal, reinstallation, or unauthorized repair of product, or for damages of any type whatsoever, including incidental and/or consequential damages.

THIS WARRANTY SUPERSEDES ALL PREVIOUS WARRANTIES.

Read this manual before installing and using this product. Failure to do so can result in serious injury or death.
You have just purchased a quality steam boiler designed to the ASME Boiler Code and registered with the National Board of Boiler Inspectors. Treat this industrial equipment with care and respect. It is safe when installed, maintained, and used properly. Read the instruction carefully and contact the factory if you have any questions.

WARNING
Read this manual before installing and using this product.
Failure to do so can result in serious injury or death.

Your boiler should be marked with a complete set of WARNING/CAUTION labels shown below. If one of these labels is missing, please contact our factory immediately.

US and All Other Non­Francophone Countries Canada and All Other Francophone Countries

Located on electrical enclosure door

Reimers-ELECTRA-STEAM-RXHC­36­120-Steam-Boiler-03Located on end caps of cylindrical boiler pressure vessel jacket

Reimers-ELECTRA-STEAM-RXHC­36­120-Steam-Boiler-04Located on end caps of cylindrical boiler pressure vessel jacket

Reimers-ELECTRA-STEAM-RXHC­36­120-Steam-Boiler-05

This manual contains safety messages. Each of the safety messages are preceded by one of the following signal word panels:

DANGER: Safety messages preceded by this label contain information, that if not followed will result in death or serious injury.
WARNING: Safety  messages  preceded  by  this  label  contain information,  that  if  not  followed  could  result  in  death  or  serious injury.
CAUTION: Safety  messages  preceded  by  this  label  contain information,  that  if  not  followed  could  result  in  minor  or  moderate injury.
NOTICE: Messages preceded by this label contain important information, but are not hazard related.

Ensure that this manual is available to the boiler operator at any time.

Read carefully all safety labels attached to the boiler. If any safety label was damaged during shipment, contact the factory immediately:
Ph. 540­662­3811; e­mail: sales@reimersinc.com

Important Safety Information

WARNING

  1. BLOWDOWN VALVE: This valve is utilized to blow impurities from the boiler chamber. When opened, a large volume of hot water and steam is discharged. Ensure that this valve is properly piped for such discharge. State and local codes must be met as applicable.

  2. ELECTRICAL: All field wiring to the boiler must be in accordance with the National Electric Code and any local codes that may apply. Wiring must be made by a competent certified electrician. Use copper wire only.
    Ensure  that  all  electrical  components  are  in  a  dry  location,  free from  any  possibility  of  water  soaking.  Electric  foot  switches  when supplied must not be placed on a wet floor. They must be placed on dry surface, not subject to steam or water.

  3. GAUGE GLASS: The gauge glass protector guards must be on at all times. When replacing the glass, be sure that the unit is not under pressure and is cool to touch. The gauge glass should be replaced once per year. If cracks or wear is evident, replace the gauge glass immediately.

  4. MODIFICATION/MISUSE: This boiler has been designed and constructed in accordance with the ASME Boiler and Pressure Vessel Code. Any modification or misuse can result in a dangerous situation. Reimers Electra Steam, Inc. is not liable for any product that has been modified or improperly used.

  5. PRESSURE GAUGE: The pressure gauge indicates the internal pressure of the boiler. It can fail. Periodically have your boiler inspector compare the gauge with a known gauge utilizing the test valve arrangement provided

  6. REGISTRATION: Most states and cities require boiler registration and inspection. Check with your government authorities.

  7. INSTALLATION AND REPAIR:
    Installation and repair work of this unit must be performed only by experienced personnel. Before commencing a repair, ensure that the boiler is cold, not pressurized and electrically disconnected. All standard electrical and steam safety precautions must be taken during testing.

  8. SAFETY   VALVE:   The  safety  valve  is  designed  to  discharge  hot  steam  when  the  set  pressure  is  exceeded.    Ensure  that  the discharge port is pointing toward the back of the unit away from the operator or any aisles. Test the safety valve periodically to ensure that it is operating properly. Test carefully at full pressure by lifting lever using pliers and let it “slapping” shut. Steam discharge can scald. Ensure no one is exposed.

  9. STEAM INSTALLATION:
    Steam piping must be of black pipe, not galvanized. Work must be done by an experienced steam fitter. All state and local codes must be met as applicable.

  10. WATER:   Ensure  that  all  electrical  components  are  in  a  dry  location,  free  from  any  possibility  of  water  soaking.    Electric  foot switches when supplied must not be placed on a wet floor. They must be placed on dry surface not subject to steam or water.

Installation

REIMERS ELECTRA STEAM, INC. boilers are heated by one or more immersion type heating elements. Automatic controls are provided to maintain pre­set operating pressure and proper water supply. Safety features include automatic low water cutoff, automatic pressure control, safety valve and visible water level gauge. Each boiler is manufactured in accordance with  the ASME  Power Boiler  Code  Standards  and  is  individually  inspected  and  stamped  by an  authorized  National  Board  Insurance Inspector. All boilers are registered with the National Board of Boiler and Pressure Vessel Inspectors. When boiler is received, make sure it has not been damaged in shipment.

NOTE:
ASME DATA PLATE IS LOCATED ON END OF PRESSURE VESSEL BEHIND LABEL STAMPED WITH NATIONAL BOARD NUMBER OF UNIT.
When boiler is received, make sure it has not been damaged in shipment.

Location

Place the boiler in a level position, close to the equipment which it is to supply. This will insure minimum heat losses and allow more economical piping arrangements. All steam lines should be insulated. Review the overall dimensions of your boiler model on page 6 to select proper boiler location.
Regardless of the NFPA­70 working space requirements shown below, provide a minimum of 3ft clearance on both sides of the boiler for element servicing, 3ft of clearance to the front of the boiler and 1.5ft to the rear of the boiler.

  • Working space:
    Electric boiler spacing is dictated by NFPA­70, Table 110.26 as follows:

Note: Where the conditions are as follows:

Condition 1 — Exposed live parts on one side of the working space and no live or grounded parts on the other side of the working space, or exposed live parts on both sides of the working space that are effectively guarded by insulating materials.
Condition 2 — Exposed live parts on one side of the working space and grounded parts on the other side of the working space. Concrete, brick, or tile walls shall be considered as grounded.
Condition 3 — Exposed live parts on both sides of the working space.

  • Dead­Front Assemblies. Working space shall not be required in the back or sides of assemblies, such as dead­front switchboards or motor control centers, where all connections and all renewable or adjustable parts, such as fuses or switches, are accessible from
    locations other than the back or sides. Where rear access is required to work on non­electrical parts on the back of enclosed equipment, a minimum horizontal working space of 762 mm (30 in.) shall be provided.

  • Alcove or closet installation per UL834: Proper location of this boiler model with regard to combustible and noncombustible surfaces and materials is coded on the boiler name plate. The following decoding sketch and description is provided for the user information:

Description of dimensions and symbols
  • A – Clearance above top of boiler

  • B – Clearance from front of boiler
    Prefix C to numeral indicates suitability for closet or alcove installation
    Prefix A indicates suitability for alcove but not for closet installation

  • D – Clearance from back of boiler

  • EL – Clearance from left side of boiler

  • ER – Clearance from right side of boiler

  • F – Indicates type of flooring: “NC” for noncombustible floor / “C” for combustible floor. Numeral indicates minimum clearance below suspended units to combustible floor

Reimers-ELECTRA-STEAM-RXHC­36­120-Steam-Boiler-08

Water Supply

On  models  with  pump  and/or  solenoid  valve,  connect  incoming water supply to strainer on intake side of solenoid valve.

On models furnished with condensate return tank, connect water  line  to makeup  valve  located  at  tank  end.  (See  Instruction Supplement 1 in this manual) R, RH and RHC steam boiler models require four (4) gallons of feed water per hour for each 10 kW of electric heating capacity of the boiler. Lines  should  be  of  adequate  size  and  meet  local  plumbing codes.
In  order  to  ensure  long  term  trouble­ free  boiler  operation,  we recommend that the water used as boiler feed water to be tested for hardness. If the water in your area is harder than  1grain  (17mg/L),  use  a  water softener.  The  main  cause for premature heating element failure in electric steam boilers is water hardness. If severe corrosion during inspection  of the  pressure  vessel  as  indicated  in  chapter  3.4 of this manual becomes evident, additional tests of your boiler feed water must be performed. A water analysis should  be  performed  by  a  qualified  and  recognized  water treatment company located in your area.
Recommended levels for boiler feed water:

Recommended  levels  for  boiler  water  (water  inside  pressure vessel when boiler is operating)

NOTICE
Do not add any chemicals to the  boiler feed water unless specifically recommended  by  a  qualified  and  recognized water treatment company.

Steam Outlet

All  piping  from  and  to  the  boiler  must  comply  with  the  A.S.M.E. B31.1 Power Piping Code. All State and local codes must be met. All piping must be done by a qualified steam fitter.
Connect steam line of sufficient size from steam line valve to  the equipment.  Steam  piping  must  be  black  steel  pipe,  not galvanized. Work must be done by an experienced steamfitter. All state and local codes must be met.

Condensate Return

If the condensate is to be returned by gravity (no tank) in a closed system, the load discharge should be at least 2 feet above the boiler level so that the weight of the condensate will actuate the check valve. When applicable, install steam return lines at sufficient height to allow a pitch of 2 inches for every 10 feet of pipe length.

Note:   For  condensate  return  systems  (with  tank),  see  special sheet.

Safety Relief Valve

The safety valve is designed to discharge hot steam when the  set  pressure is  exceeded.  Ensure  that  the  discharge  port is pointing toward the back of the unit away from the operator  and  any  aisles.  If  it  is  required that  discharge  piping be installed from the safety valve, the pipe should not  be  smaller  than  the  valve  outlet  and  should  be  rigidly supported so as not to place weight on the valve itself.
Important: No valve in this line!

Reimers-ELECTRA-STEAM-RXHC­36­120-Steam-Boiler-12

Electrical

Install a fused disconnect switch near the boiler. It should be fused as marked on the boiler name plate. Connect the power supply from the disconnect switch to the terminals in the boiler control panel. A copy of the wiring diagram is in the control panel.
Important: Electrical connections to the boiler control panel (FIG. 7)should be made by a qualified  Electrician.  All wiring must comply with local electrical codes.

Three Phase Boiler Models Without Power Supply Extension Box

Reimers-ELECTRA-STEAM-RXHC­36­120-Steam-Boiler-13

Three­Phase Boiler Models With Power Supply Extension Box

Reimers-ELECTRA-STEAM-RXHC­36­120-Steam-Boiler-14 All  boiler  models  that  are  equipped  with  a  transformer  option (OPT1010 or OPT1011) don’t require a separate external control voltage power supply.

Blowdown Valve

CAUTION When the blowdown valve is utilized, a large volume of hot water and  steam  is  discharged.    Ensure  that  this  valve  is  properly piped for this discharge. State and local codes must be met as applicable.

Operation

Boiler Startup
  • Open steam line valve slightly. This will allow the boiler to be filled without producing back pressure.

Reimers-ELECTRA-STEAM-RXHC­36­120-Steam-Boiler-15

  • Open upper and lower gauge glass fixture valve
  • Ensure that the feed water shutoff valve is in the OPEN­ position
  • Close the boiler blow down valve
  • Throw  the  fused  disconnect  switch  (not  provided  by factory) to the ON­ position and turn on the boiler control voltage

Reimers-ELECTRA-STEAM-RXHC­36­120-Steam-Boiler-16

  • After approximately 2 seconds, the WATER FEED light turns on and water enters the boiler. As soon as the water level reaches approximately half height in the gauge glass, the automatic water feed turns off.

NOTICE Do  not  let  the  pump  to  run  dry  for  an  extended time as this will cause damage to the pump.

Reimers-ELECTRA-STEAM-RXHC­36­120-Steam-Boiler-17As  soon  as  no  boiler  alarms  are  indicated,  the  HEATING light turns on and the boiler starts to build up pressure. Observe the pressure gauge while pressure builds up, until working pressure is reached. The working pressure should have been factory set to your specification. However, if you wish  to  change  the  working  pressure  setting,  proceed as  follows.

WARNING Stand clear of scalding water or steam. Disconnect  the  boiler from  all  power  supplies.

All pressure controls are factory preset and require no adjustment. However, if a change of the operating steam pressure is required, then proceed as follows:

  • Disconnect all power supplies from the boiler.
  • Close the steam outlet valve
  • Remove the cover from the pressure control enclosure.
  • Turn  the  black  knob  of  the  operating  pressure  switch clockwise  to  increase  the pressure and counterclockwise to decrease the pressure.

Reimers-ELECTRA-STEAM-RXHC­36­120-Steam-Boiler-18h.)  To  shut  off  the  boiler,  turn  the  POWER  switch  on the  boiler controller OFF.

See Boiler Control Manual for detailed instructions.
The control provides four basic functions and two optional functions. The following overview describes the functions.

Low water cutoff
Boiler high pressure cutoff
High water level feed shutoff Automatic boiler refill Automatic boiler blowoff (Optional)
Remote  controlled  boiler  ON/OFF  and  boiler  status  (Optional)

Control Functions

Low Water Cut­ Off Function
The  low  water  cutoff  function  of  the  boiler  control  de­energizes the heating elements when the water level in the boiler pressure vessel falls below the minimum acceptable operating  level.  The  control  senses  the water  level  in  the  boiler pressure vessel through a probe, E3. When the tip of the  probe  is  in  contact  with  water  in  the  boiler,  the  boiler operates normally. When the water level in the boiler falls below  the  tip of  the  probe  the  control  senses  that  water  level is low. The control will not de­energize the heating elements  when  the  probe  loses  contact with  the  boiler  water for short periods of time. But, when the probe loses contact with the probe for a set time, the control de­ener­ gizes  the heating  elements  and  turns  on  the  “LOW  WATER” boiler alarm light. Boiler operation can only be resumed after determining why water level is low, restoring normal  water  level  in  the  boiler  and  pressing  the  “LOW WATER” reset button [R]. After presseing the “LOW WATER” reset button the alarm light “LOW WATER” turns off,  the  lockout  is  reset  and  the  heating elements  are  energized.
The Low Water Cut­Off function short cycling timer can be adjusted. See the Boiler Control Manual (Doc. #9101)

High Pressure Cutoff Function
If  the  operating  pressure  control  fails,  the  steam  pressure  in the boiler can reach the value set on the high limit pressure  control.  In  that case,  the  high  limit  pressure  control de­energizes the heating elements and locks them out. The boiler alarm light “HIGH PRESSURE” comes on. After the  pressure  control  is  replaced  the  HIGH  PRESSURE alarm light turns off.

High Water Level Feed Shutoff
When the high water level cut­off probe (E2) comes in con­ tact with boiler water, the boiler control turns off the auto­ mastic refilling device, feed pump and/or solenoid valve. At the same time the boiler controller de­energizes the heat­ing elements, closes the steam outlet line through the sole­ node valve (SOL2) and displays a flashing “2” on the LED display. As soon  as  the  probe  E2  looses  contact  with  the  boiler water the boiler controller resumes normal boiler operation automatically. (The boiler controller can be set to require that the “E­ Key be pressed to resume boiler oper­ation. See the Boiler Control Manual for instructions.)

Automatic Boiler Refill
When the POWER switch is turned on and the water level probe  (E1)  is  in contact  with  the  boiler  water,  the  boiler  control keeps the boiler water feed pump and/or solenoid valve de­energized. When the water level probe (E1) loses contact  with  the  boiler  water,  the  boiler  control  energizes the boiler feed pump and/or the solenoid valve after a set ON delay time. When the water level probe makes contact with the boiler water, the boiler controller de­energizes the boiler water feed pump and/or solenoid valve after a set re­fill OFF delay time.
The  ON  and  OFF  delay  time  can  be  adjusted. See the boiler control manual for instructions.
If the feedwater pump and/or solenoid valve remains on for longer than the ON delay time the boiler control de­energizes the feed water pump and/or solenoid valve and dis­  plays a flashing  “0” on the control LED display.  The “E” ;key must be pressed to start a new re­filling attempt

Automatic Boiler Blowoff (Optional)
See Boiler Control Manual for instructions.

Remote  controlled  boiler  ON/OFF  and  boiler  status. (Optional)
See Boiler Control Manual for instrucitons.

Boiler Monitor Definitions

The  following  are  definitions  for  all  boiler  monitor  indications. See the control manual for details including adjusting all pa­ rameters.
Flashing  “0”:  Boiler  feed  pump  and/or  solenoid  remained  energized longer than the set time. Boiler feed pump and/or solenoid are de­energized. Press “E” key to re­set alarm and start a new re­filling cycle.
Flashing “1”: Following a blowdown cycle, the automatic re­ fill device did not stay on for the set time. Press”E” key to re­set the alarm.
Flashing “2”: The high water level probe (E2) has come in to contact with boiler water. The feed pump and or solenoid is  de­energized  and  the heating  elements  are  de­energized. As soon as the probe (E2) loses contact with the  boiler  water  normal  control  operation  resumes.  (This  function may be set to require re­set using the E key.)

Boiler Maintenance

WARNING   Boiler  repairs  must  be  performed  by  experi­  enced personnel only. Ensure boiler water is cold and drained and that there is no pressure and all electricity to the boiler is shut­off.

Boiler Blow off

All  boilers  must  be  blown  off  periodically  to  remove  minerals, scale and other foreign matter, which accumulate inside  the  pressure  vessel.  The concentration  of  this  deposit depends in part upon the condition of the water in the  area.  When  water  is  naturally  soft,  or  has  been softened chemically, boiler blowoffs are required less often than  in  areas where  hard  water  is  found.  Water  softeners  are suggested in hard water areas to minimize the formation of hard scale on heating elements. Another factor affecting  water  condition  is  the  amount  of  condensate,  if  any, that is being returned to the boiler. Since condensate is  essentially  clean distilled  water,  it  contains  very  few  impurities. If a large part of the condensate is being returned and little make­up water is used, the boiler need not be blown down as often as when little or no condensate is  returned  to the  boiler.  We  recommend  blowoff  of  newly  installed steam boilers once per day until the first heating element and pressure vessel inspection is performed (refer to  chapter  3.4).  If  no  significant  amount  of  sediment is  found on the bottom of the pressure vessel and on the heating element sheaths, then the boiler blowoff frequency can be reduced accordingly. The safest method to blowoff R­series  steam  boilers  is  to  install  a  Reimers Electra  Steam, Inc. properly sized and fully trimmed blowdown tank,  model BTANK­10  (Figures  10  and  11).  Reimers  blowdown tanks are designed and constructed to Section VIII  of  the  A.S.M.E.  Code  and  inspected  by a commissioned National Board Boiler inspector.

Boiler Blow off Frequency
In areas where water is soft or has been softened chemically:

  • When little condensate is returned blowdown once every second day
  • When a large part of the condensate is returned and little make­up water is used, blowdown once every week

In areas where hard water exists:

  • When little or no condensate is returned, blowdown once a day
  • When a large part of the condensate is returned and little make­up water is used, blowdown once every second day
Safety Valve Test

WARNING
Stand clear of scalding water or steam. Ensure  that  the  Boiler  Bottom Blowoff  Valve is properly piped.

This test should be performed once per month. Proceed as follows:

Reimers-ELECTRA-STEAM-RXHC­36­120-Steam-Boiler-19

  • Increase  the  steam  pressure  as shown in chapter 2.1. to maximum operating pressure.
  • Keep  the  steam  outlet  valve closed
  • Pull the trip lever and hold open for five (5) seconds in order to flush off the valve seat.
  • Permit the valve to “slap” shut. If a leak occurs, repeat this test and if necessary, replace the valve.
Element Replacement and Element Cleaning

WARNING
Ensure  that  the  boiler  is  cold,  drained  and all power supplies are disconnected

Clean the element rods every six (6) months. To clean the element rods, or if an element must be replaced, proceed as follows:

  • Remove the element terminal cover from the front of the boiler.

  • Disconnect and label the terminal wires

  • Remove all four (4) nuts from each element flange and pull out the heating element

  • Use a stiff  wire brush to remove all scale and foreign matter from the element rods.

  • Clean the element flange surfaces before installing new elements and gaskets

Water Level Probe and Probe Baffle Box Cleaning

WARNING Ensure that the boiler is cold, drained and all power supplies are disconnected.

In  order  to  provide  reliable  automatic  water  level  control,  the water level probes are located inside a funnel shaped probe  baffle,  welded  to the  inner  wall  of  the  pressure  vessel. The probe baffle has direct connection to the top and bottom of the pressure vessel so that the probes can read  the  water  level,  protected  from  foam  and  bursting  steam bubbles that form on the surface of the boiler water.
The probe baffle must be cleaned every six (6) months of sediments and other debris that accumulates at the bottom of the baffle. To accomplish this, proceed as follows:

Step 1:
Remove  the  water  level probe cover, disconnect  from  each  probe the wire and label it.
Remove first the Short Probe and inspect the probe rod. If sediment has accumulated, use a stiff wire brush to remove  it. Install the probe in its place in the shell. Repeat  the  above  cleaning procedure for the other probes.
Don’t install the Long Probe yet.

Step 2:
Remove the pipe plug from the boiler blow off line as shown in FIGURE 16.

Step 3:
Insert two (2) 1/4in OD copper tubes or any other soft rods through the Long Probe opening and through the boiler blow off opening into the pressure vessel to remove sediments from the bottom of the probe baffle.

Step 4:
Put a flash light above the  Long  Probe  opening and observe whether light is visible through the boiler blow off opening. If no light  is  visible,  then repeat inserting the copper  tube  through  the Long Probe opening and pushing towards the bottom to remove further sediment from the probe baffle.
If there is a significant amount of sediment visible at the bottom of the pressure vessel, then the heating elements must be removed as shown in chapter 3.4 and the  sediments scooped out through the element openings.
Step 5:
Install the Long Probe into the shell and connect all probe wires.
Frequency: Minimum once per year.

Gauge Glass Replacement

WARNING Ensure that the boiler is cold, drained and all power supplies are disconnected.

Reimers-ELECTRA-STEAM-RXHC­36­120-Steam-Boiler-23

Troubleshooting

Ensure that the boiler is cold and has no pressure.
Electrical trouble shooting must be performed by a qualified electrician.

If trouble shooting did not resolve problem, please contact our service technicians at:
Phone: 540­662­3811
Email: techsupport@reimersinc.com

Parts list for R, RH and RHC Boiler Models

WARNING:
Use Reimers replacement parts. All components are designed and approved to be used in this Underwriters Laboratories listed and ASME National Board Stamped boiler. Failure to do so may cause serious injury or death.

Reimers-ELECTRA-STEAM-RXHC­36­120-Steam-Boiler-25

Reimers-ELECTRA-STEAM-RXHC­36­120-Steam-Boiler-26

Reimers-ELECTRA-STEAM-RXHC­36­120-Steam-Boiler-27

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals